Eaton xComfort KLV LV systems Final Distribution Boards. Compact distribution board-flush mounting, Hybrid, 5-rows, 24MU, flat sheet steel door, 60UPP-HY24-F
| Product Name |
Eaton xComfort KLV hybrid distribution board
|
| Catalog Number |
302426
|
| EAN |
9010238160996
|
| Product Length/Depth |
100 mm
|
| Product Height |
840 mm
|
| Product Width |
360 mm
|
| Product Weight |
6.99 kg
|
| Compliances |
RoHS conform
|
| Certifications |
IEC/EN 62208
IEC/EN 60670-24 (PD) |
| Model Code |
KLV-60UPP-HY24-F
|
| Fitted with: |
Installation instructions
Mounting plate 1x single-way socket outlet Imprintable sheet 3D adjustment element for mounting designed to adjust the mounting depth by up to 18 mm Cable retainer Wall trough Front cover Nail lugs Microperforated mounting plate Neutral and protective conductor terminals with KSK plug-in terminal technology Device holder Door/Frame Spirit level for leveling Device support rails |
| Functions |
Basic device
Extension possible Sealable |
| Protection class |
II (totally insulated)
|
| RAL-number |
9016
|
| Special features |
|
| Used with |
Basic device
KLV hybrid Installation distribution boards |
| Application |
Indoor
|
| Color |
Traffic white (RAL 9016)
White |
| Type |
|
| 10.10 Temperature rise |
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
|
| 10.11 Short-circuit rating |
Is the panel builder's responsibility.
|
| 10.12 Electromagnetic compatibility |
Is the panel builder's responsibility.
|
| 10.13 Mechanical function |
Meets the product standard's requirements.
|
| 10.2.2 Corrosion resistance |
Meets the product standard's requirements.
|
| 10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard's requirements.
|
| 10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard's requirements.
|
| 10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects |
650 °C; meets the product standard's requirements.
|
| 10.2.4 Resistance to ultra-violet (UV) radiation |
Not relevant to indoor installations.
|
| 10.2.5 Lifting |
Does not apply to enclosures without lifting aids.
|
| 10.2.6 Mechanical impact |
IK05
|
| 10.2.7 Inscriptions |
Meets the product standard's requirements.
|
| 10.3 Degree of protection of assemblies |
IP30
|
| 10.4 Clearances and creepage distances |
Is the panel builder's responsibility.
|
| 10.5 Protection against electric shock |
Protection class 2, therefore not applicable.
|
| 10.6 Incorporation of switching devices and components |
Is the panel builder's responsibility.
|
| 10.7 Internal electrical circuits and connections |
Is the panel builder's responsibility.
|
| 10.8 Connections for external conductors |
Is the panel builder's responsibility.
|
| 10.9.2 Power-frequency electric strength |
Ui = 400 V AC
|
| 10.9.3 Impulse withstand voltage |
4 kV
|
| 10.9.4 Testing of enclosures made of insulating material |
Meets the product standard's requirements.
|
| Ambient operating temperature details |
-5 °C - 40 °C
|
| Frequency rating of contacts |
50 Hz
|
| Built-in depth |
80 mm
|
| Cable entry postion |
Cable entries on top and bottom, side, back plate
|
| Closure type |
Other
|
| Cover/door color |
White
|
| Cover/door model |
With notch
|
| Cover/door type |
Door
Single |
| Degree of protection |
IK05
IP30 |
| Enclosure material |
Plastic
|
| Internal depth |
80 mm
|
| Material |
Polystyren (plastic)
Sheet steel, powder-coated |
| Module rack type |
Rail frame / Media mounting plate
|
| Number of module space units per row |
12
|
| Number of rows |
5
|
| PE and N terminal number and cross section |
N - Fi: 1 x (2.5 mm² - 25 mm²) + 7 x (0.5 mm² - 4 mm²)
N: 2 x (2.5 mm² - 25mm²) + 14 x (0.5 mm² - 4 mm²) PE: 2 x (2.5 mm² - 25 mm²) + 14 x (0.5 mm² - 4 mm²) |
| Protective shrouding material |
Plastic
|
| Terminal type |
Plug-in terminals
|
| Width in number of modular spacings |
12
|
| Mounting method |
DIN-rail
Flush mounted (plaster) Flush mounting |
| Heat diss. ambient 35°C delta T:20°C flush mount individ. encl. top(IEC 60890) |
28 W
|
| Heat diss. ambient 35°C delta T:35°C flush mount individ. encl. top(IEC 60890) |
58 W
|