Descargar documento () de 20

192517
Código del modelo: NZMN2-VX100-BT-NA

Eaton Moeller series NZMN2 PXR20 circuit breaker, 100 A, 3-pole, box terminal, UL/CSA

Especificaciones generales

Product Name
Eaton Moeller series NZM molded case circuit breaker electronic
Catalog Number
192517
EAN
4015081932450
Product Length/Depth
149 mm
Product Height
195 mm
Product Width
105 mm
Product Weight
2.345 kg
Compliances
RoHS conform
Certifications
IEC 60947-2
CSA certified
Specially designed for North America
CSA (File No. 22086)
CE marking
UL (File No. E31593)
CSA-C22.2 No. 5-09
UL (Category Control Number DIVQ)
UL listed
UL/CSA
IEC
CSA (Class No. 1432-01)
UL 489
Model Code
NZMN2-VX100-BT-NA

Delivery program

Application
Branch circuits, feeder circuits
Type
  • Rated current = rated uninterrupted current: 100 A
  • Switches conform to UL/CSA as well as the IEC regulations. IEC switching performance values are contained on the rating plate.
Circuit breaker frame type
NZM2
Number of poles
Three-pole
Amperage Rating
100 A
Release system
Electronic release
Features
Motor drive optional
Protection unit
Special features
Circuit breaker

Technical Data - Electrical

Voltage rating
690 V - 690 V
Rated operating voltage Ue (UL) - max
600 V
Amperage Rating
100 A
Instantaneous current setting (Ii) - min
2 A
Instantaneous current setting (Ii) - max
18 A
Overload current setting (Ir) - min
40 A
Overload current setting (Ir) - max
100 A
Short delay current setting (Isd) - min
200 A
Short delay current setting (Isd) - max
1000 A
Short-circuit release delayed setting - min
80 A
Short-circuit release delayed setting - max
1000 A
Short-circuit release non-delayed setting - min
200 A
Short-circuit release non-delayed setting - max
1800 A
Rated short-circuit breaking capacity Ics (IEC/EN 60947) at 400/415 V, 50/60 Hz
50 kA
Electrical connection type of main circuit
Frame clamp
Handle type
Rocker lever

Technical Data - Mechanical

Mounting Method
Fixed
DIN rail (top hat rail) mounting optional
Built-in device fixed built-in technique
Mounting Method
Fixed
DIN rail (top hat rail) mounting optional
Built-in device fixed built-in technique
Degree of protection
IP20
Protection against direct contact
Finger and back-of-hand proof to DIN EN 50274/VDE 0106 part 110
Number of auxiliary contacts (change-over contacts)
0
Number of auxiliary contacts (normally closed contacts)
0
Number of auxiliary contacts (normally open contacts)
0
Position of connection for main current circuit
Front side
Special features
Circuit breaker

Design verification as per IEC/EN 61439 - technical data

Rated operational current for specified heat dissipation (In)
100 A
Equipment heat dissipation, current-dependent
8.25 W
Ambient operating temperature - min
-25 °C
Ambient operating temperature - max
70 °C
Ambient storage temperature - min
40 °C
Ambient storage temperature - max
70 °C

Design verification as per IEC/EN 61439

10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard's requirements.
10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of assemblies
Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances
Meets the product standard's requirements.
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9.2 Power-frequency electric strength
Is the panel builder's responsibility.
10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material
Is the panel builder's responsibility.
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.

Additional information

Functions
Systems, cable, selectivity and generator protection
Current limiting circuit breaker

Exportar especificaciones del producto

Serial Number Verified :
Authenticated:
The product is verified as being authentic; however, this does not guarantee the condition or fit for purpose of the product.

Autenticar producto

Introduzca su número de serie de 16-17 dígitos
El número de serie que ha introducido no debe contener caracteres especiales. El número de serie que ha introducido no es correcto, debe ser de 16 o 17 dígitos. No se ha encontrado el número de serie que ha introducido. Vuelva a intentarlo o informar de este problema para obtener más ayuda. El número de serie que ha introducido no coincide con el producto. Compruebe el número de serie de su producto e inténtelo de nuevo. Cliquear aquí. para navegar a la página del producto para el número de serie que ha introducido Eaton sabe que el número de serie es SOSPECHADO, inténtelo de nuevo o informar de este problema para obtener más ayuda.
Número de serie
Reiniciar Eaton sabe que el número de serie es SOSPECHADO, inténtelo de nuevo o informar de este problema para obtener más ayuda. Eaton no reconoce el número de serie y no es válido. Utilice este formulario para informar de este problema para obtener más ayuda.
Introduzca el código de autenticación de 6 dígitos
El producto que ha introducido es sospechado. Vuelva a intentarlo o informar de este problema para obtener más ayuda. El código de autenticación que introduzca no coincide con nuestros registros para este número de serie. Vuelva a intentarlo o informar de este problema para obtener más ayuda. Código de autenticación no válido. La longitud debe ser de 6 caracteres informar de este problema para obtener más ayuda. El código de autenticación es obligatorio informar de este problema para obtener más ayuda.
Complete el desafío Captcha antes de autenticar.
Contáctenos para informar de un problema
x
Informar de un problema
Por favor, introduzca sus apellidos.
x
Gracias, su problema ha sido enviado, nuestro equipo de productos se pondrá en contacto con usted pronto.
Nota: Si faltan archivo(s) en la descarga .zip, el ejecución de archivo no es compatible con la descarga masiva.