Eaton DG1 Variable frequency drive, 400 V AC, 3-phase, 9 A, 4 kW, IP21/NEMA1, Brake chopper, DC link choke
| Product Name | 
                                                Eaton DG1 variable frequency drive
                                             | 
| Catalog Number | 
                                                9702-1011-00P
                                             | 
| EAN | 
                                                4015081710829
                                             | 
| Product Length/Depth | 
                                                200.9 mm
                                             | 
| Product Height | 
                                                327 mm
                                             | 
| Product Width | 
                                                153 mm
                                             | 
| Product Weight | 
                                                6.7 kg
                                             | 
| Certifications | 
                                                UkrSEPRO  CUL UL Category Control No.: NMMS, NMMS7 Certified by UL for use in Canada RoHS, ISO 9001 UL IEC/EN 61800-3 Specification for general requirements: IEC/EN 61800-2 UL508 Safety requirements: IEC/EN 61800-5 IEC/EN61800-5 EAC IEC/EN61800-3 UL report applies to both US and Canada CSA-C22.2 No. 274-13 C-Tick UL File No.: E134360 CE | 
| Catalog Notes | 
                                                The brake resistors are assigned based on the maximum rated power of the variable frequency drive. Additional brake resistors and designs (e.g. different duty cycles) are available upon request.
                                             | 
| Model Code | 
                                                DG1-349D0FB-C21C
                                             | 
| Features | 
                                                Temperature-controlled fan  Tool-less swapping of fan Parameterization: Fieldbus Parameterization: Keypad Parameterization: Power Xpert inControl | 
| Functions | 
                                                4-quadrant operation possible
                                             | 
| Air volume capacity | 
                                                24 m³/h
                                             | 
| Cable length | 
                                                C2 ≤ 10 m, Radio interference level, maximum motor cable length  C3 ≤ 50 m, Radio interference level, maximum motor cable length 100 m, screened, maximum permissible, Motor feeder | 
| Degree of protection | 
                                                IP21  NEMA 1 | 
| Electromagnetic compatibility | 
                                                1st and 2nd environments (according to EN 61800-3)
                                             | 
| Environmental class | 
                                                3C2, 3S2 (Air quality)
                                             | 
| Fitted with: | 
                                                DC link choke  Additional PCB protection PC connection IGBT inverter Brake chopper Breaking resistance Multi-line graphic display Control unit Radio interference suppression filter Internal DC link | 
| Frame size | 
                                                FS1
                                             | 
| Mounting position | 
                                                Vertical
                                             | 
| Number of slots | 
                                                2 (expansion)
                                             | 
| Overvoltage category | 
                                                III
                                             | 
| Pollution degree | 
                                                2
                                             | 
| Product Category | 
                                                Variable frequency drives
                                             | 
| Protection | 
                                                Finger and back-of-hand proof, Protection against direct contact (BGV A3, VBG4)
                                             | 
| Radio interference class | 
                                                Optional external radio interference suppression filter for longer motor cable lengths and for use in different EMC environments  C1: with external filter, for conducted emissions only C2, C3: depending on the motor cable length, the connected load, and ambient conditions. External radio interference suppression filters (optional) may be necessary. | 
| Safety function/level | 
                                                STO (Safe Torque Off, SIL1, PLc Cat 1)
                                             | 
| Shock resistance | 
                                                UPS drop test (for weights inside the UPS frame)  Storage and transportation: maximum 15 g, 11 ms (inside the packaging) Mechanical, According to EN 61800-5-1, IEC/EN 60068-2-27 | 
| Suitable for | 
                                                Branch circuits, (UL/CSA)
                                             | 
| Vibration | 
                                                Resistance: 5 - 15.8 Hz, Amplitude 1 mm (peak)  Resistance: 15.8 – 150 Hz, 1 g, Maximum acceleration amplitude Resistance: 5 - 150 Hz, According to EN 61800-5-1, IEC/EN 60068-2-6 | 
| Altitude | 
                                                Max. 1000 m  Max. 2000 m for Corner Grounded TN Systems Max. 3000 m Above 1000 m with 1 % derating per 100 m | 
| Ambient operating temperature - min | 
                                                -10 °C
                                             | 
| Ambient operating temperature - max | 
                                                50 °C
                                             | 
| Ambient operating temperature at 150% overload - min | 
                                                -30 °C
                                             | 
| Ambient operating temperature at 150% overload - max | 
                                                50 °C
                                             | 
| Ambient storage temperature - min | 
                                                -40 °C
                                             | 
| Ambient storage temperature - max | 
                                                70 °C
                                             | 
| Climatic proofing | 
                                                < 95 average relative humidity (RH), no condensation, no corrosion
                                             | 
| Current limitation | 
                                                0.1 - 2 x IH (CT), motor, main circuit
                                             | 
| Efficiency | 
                                                98.1 % (η)
                                             | 
| Input current ILN at 110% overload | 
                                                11.2 A
                                             | 
| Input current ILN at 150% overload | 
                                                8.4 A
                                             | 
| Leakage current at ground IPE - max | 
                                                2.9 mA
                                             | 
| Mains current distortion | 
                                                35.3 %
                                             | 
| Mains switch-on frequency | 
                                                Maximum of one time every 60 seconds
                                             | 
| Mains voltage - min | 
                                                380 V
                                             | 
| Mains voltage - max | 
                                                500 V
                                             | 
| Operating mode | 
                                                U/f control  Speed control with slip compensation Sensorless vector control (SLV) Torque regulation | 
| Output frequency - min | 
                                                0 Hz
                                             | 
| Output frequency - max | 
                                                400 Hz
                                             | 
| Output voltage (U2) | 
                                                500 V AC, 3-phase  480 V AC, 3-phase 400 V AC, 3-phase | 
| Overload current IL at 110% overload | 
                                                13.2 A
                                             | 
| Overload current IL at 150% overload | 
                                                13.5 A
                                             | 
| Rated conditional short-circuit current (Iq) | 
                                                100 kA
                                             | 
| Rated control supply voltage | 
                                                10 V DC (Us, max. 10 mA)
                                             | 
| Rated frequency - min | 
                                                45 Hz
                                             | 
| Rated frequency - max | 
                                                66 Hz
                                             | 
| Rated operational current (Ie) at 110% overload | 
                                                12 A
                                             | 
| Rated operational current (Ie) at 150% overload | 
                                                9 A
                                             | 
| Rated operational power at 380/400 V, 50 Hz, 3-phase | 
                                                4 kW
                                             | 
| Rated operational power at 380/400 V, 50 Hz, 3-phase, 110% overload | 
                                                5.5 kW
                                             | 
| Rated operational power at 500 V, 50 Hz, 3-phase | 
                                                5.5 kW
                                             | 
| Rated operational power at 500 V, 50 Hz, 3-phase, 110% overload | 
                                                5.5 kW
                                             | 
| Rated operational voltage | 
                                                480 V AC, 3-phase  500 V AC, 3-phase 400 V AC, 3-phase | 
| Resolution | 
                                                0.01 Hz (Frequency resolution, setpoint value)
                                             | 
| Short-circuit protection rating | 
                                                15 A, UL (Class CC or J), Safety device (fuse or miniature circuit-breaker), Power Wiring
                                             | 
| Starting current - max | 
                                                200 %, IH, max. starting current (High Overload), For 2 seconds every 20 seconds, Power section
                                             | 
| Supply frequency | 
                                                50/60 Hz
                                             | 
| Switching frequency | 
                                                4 kHz, 1 - 12 kHz adjustable, fPWM, Power section, Main circuit
                                             | 
| System configuration type | 
                                                TN-S, TN-C, TN-C-S, TT, IT
                                             | 
| Voltage rating - max | 
                                                500 VAC
                                             | 
| Assigned motor current IM at 400 V, 50 Hz, 110% overload | 
                                                11.5 A
                                             | 
| Assigned motor current IM at 400 V, 50 Hz, 150% overload | 
                                                8.5 A
                                             | 
| Assigned motor current IM at 440 - 480 V, 60 Hz, 150% overload | 
                                                7.6 A
                                             | 
| Assigned motor current IM at 440/480 V, 60 Hz, 110% overload | 
                                                11 A
                                             | 
| Assigned motor current IM at 500 V, 50 Hz, 110% overload | 
                                                9 A
                                             | 
| Assigned motor current IM at 500 V, 50 Hz, 150% overload | 
                                                6.8 A
                                             | 
| Assigned motor power at 460/480 V, 60 Hz, 3-phase | 
                                                5 HP
                                             | 
| Assigned motor power at 460/480 V, 60 Hz, 3-phase, 110 % overload | 
                                                7.5 HP
                                             | 
| Apparent power at 400 V | 
                                                8.3 kVA
                                             | 
| Apparent power at 480 V | 
                                                10.4 kVA
                                             | 
| Number of inputs (analog) | 
                                                2
                                             | 
| Number of inputs (digital) | 
                                                8
                                             | 
| Number of outputs (analog) | 
                                                2
                                             | 
| Number of outputs (digital) | 
                                                1
                                             | 
| Number of relay outputs | 
                                                3 (parameterizable, 2 changeover contacts and 1 N/O, 6 A (240 V AC) / 6 A (24 V DC))
                                             | 
| Rated control voltage (Uc) | 
                                                24 V DC (external, max. 250 mA options incl.)
                                             | 
| Communication interface | 
                                                PROFIBUS, optional  Modbus TCP, built in CANopen®, optional SmartWire-DT, optional DeviceNet, optional BACnet MS/TP, built in Ethernet IP, built in Modbus RTU, built in | 
| Connection to SmartWire-DT | 
                                                In conjunction with DXG-NET-SWD SmartWire DT module  Yes | 
| Protocol | 
                                                PROFINET IO  CAN MODBUS BACnet Other bus systems TCP/IP PROFIBUS DeviceNet EtherNet/IP | 
| Equipment heat dissipation, current-dependent Pvid | 
                                                167 W
                                             | 
| Heat dissipation capacity Pdiss | 
                                                0 W
                                             | 
| Heat dissipation per pole, current-dependent Pvid | 
                                                0 W
                                             | 
| Rated operational current for specified heat dissipation (In) | 
                                                9 A
                                             | 
| Static heat dissipation, non-current-dependent Pvs | 
                                                15.1 W
                                             | 
| Heat dissipation details | 
                                                Operation (with 150 % overload), allow for derating
                                             | 
| 10.2.2 Corrosion resistance | 
                                                Meets the product standard's requirements.
                                             | 
| 10.2.3.1 Verification of thermal stability of enclosures | 
                                                Meets the product standard's requirements.
                                             | 
| 10.2.3.2 Verification of resistance of insulating materials to normal heat | 
                                                Meets the product standard's requirements.
                                             | 
| 10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects | 
                                                Meets the product standard's requirements.
                                             | 
| 10.2.4 Resistance to ultra-violet (UV) radiation | 
                                                Meets the product standard's requirements.
                                             | 
| 10.2.5 Lifting | 
                                                Does not apply, since the entire switchgear needs to be evaluated.
                                             | 
| 10.2.6 Mechanical impact | 
                                                Does not apply, since the entire switchgear needs to be evaluated.
                                             | 
| 10.2.7 Inscriptions | 
                                                Meets the product standard's requirements.
                                             | 
| 10.3 Degree of protection of assemblies | 
                                                Does not apply, since the entire switchgear needs to be evaluated.
                                             | 
| 10.4 Clearances and creepage distances | 
                                                Meets the product standard's requirements.
                                             | 
| 10.6 Incorporation of switching devices and components | 
                                                Does not apply, since the entire switchgear needs to be evaluated.
                                             | 
| 10.7 Internal electrical circuits and connections | 
                                                Is the panel builder's responsibility.
                                             | 
| 10.8 Connections for external conductors | 
                                                Is the panel builder's responsibility.
                                             | 
| 10.9.2 Power-frequency electric strength | 
                                                Is the panel builder's responsibility.
                                             | 
| 10.9.3 Impulse withstand voltage | 
                                                Is the panel builder's responsibility.
                                             | 
| 10.9.4 Testing of enclosures made of insulating material | 
                                                Is the panel builder's responsibility.
                                             | 
| 10.10 Temperature rise | 
                                                The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
                                             | 
| 10.11 Short-circuit rating | 
                                                Is the panel builder's responsibility. The specifications for the switchgear must be observed.
                                             | 
| 10.12 Electromagnetic compatibility | 
                                                Is the panel builder's responsibility. The specifications for the switchgear must be observed.
                                             | 
| 10.13 Mechanical function | 
                                                The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
                                             |