Dokumentum letöltése () 20
Működésbe hozzuk az igazán fontos dolgokat.*

104611
Modellkód: NZM1-XFIU

Eaton Moeller series NZM Earth-fault release, 0.03-3A, 3p, bottom

General specifications

Product Name
Eaton Moeller series NZM Earth leakage relay
Catalog Number
104611
EAN
4015081044214
Product Length/Depth
180 mm
Product Height
80 mm
Product Width
90 mm
Product Weight
0.9 kg
Compliances
IEC
RoHS conform
Certifications
IEC/EN 60947-2 annex B
IEC/EN 60947-2
Model Code
NZM1-XFIU

Műszaki adatok - villamos

Sensitivity type
Pulse-current sensitive as per core-balance principle (type A)
Voltage rating
200 - 415 V AC, min. 80 V AC for detection of fault currents type A/AC (dependent on mains voltage)
Rated operating voltage (Ue) - max
415 V
Rated control supply voltage (Us) at AC, 50 Hz - min
200 V
Rated control supply voltage (Us) at AC, 50 Hz - max
415 V
Rated control supply voltage (Us) at AC, 60 Hz - min
200 V
Rated control supply voltage (Us) at AC, 60 Hz - max
415 V
Rated control supply voltage (Us) at DC - min
0 V
Rated control supply voltage (Us) at DC - max
0 V
Current rating - min
15 A
Current rating - max
100 A
Rated fault current - min
0.03 A
Rated fault current - max
3 A
Fault current detection range
50/60 Hz
Frequency rating
50 Hz / 60 Hz
Power on-delay time - min
30 ms
Power on-delay time - max
30 ms

Műszaki adatok - kommunikáció

Rated control supply voltage (Us) at AC, 50 Hz - min
200 V
Rated control supply voltage (Us) at AC, 50 Hz - max
415 V
Rated control supply voltage (Us) at AC, 60 Hz - min
200 V
Rated control supply voltage (Us) at AC, 60 Hz - max
415 V
Rated control supply voltage (Us) at DC - min
0 V
Rated control supply voltage (Us) at DC - max
0 V
Current rating - min
15 A
Current rating - max
100 A
Rated fault current - min
0.03 A
Rated fault current - max
3 A
Fault current detection range
50/60 Hz
Frequency rating
50 Hz / 60 Hz
Power on-delay time - min
30 ms
Power on-delay time - max
30 ms

Műszaki adatok - mechanikai

Mounting Method
Bottom
Mounting position
Vertical and 90° in all directions
Degree of protection
IP20 (operating component area)
Shock resistance
20 g (half-sinusoidal shock 20 ms)
Lifespan, mechanical
20000 operations

Termékjellemzők exportja