A fotó reprezentatív
Download
Eaton SWD4 MB-Power-cable, IP67, 20 m, 4 pole, Prefabricated on one side with 7/8" straight socket
| Product Name |
Eaton SWD4 Accessory MB-Power-cable
|
| Catalog Number |
183207
|
| EAN |
4015081781409
|
| Product Length/Depth |
307.692 mm
|
| Product Height |
102.564 mm
|
| Product Width |
307.692 mm
|
| Product Weight |
3.273 kg
|
| Certifications |
CSA
UL |
| Catalog Notes |
Condensation: permissible
|
| Model Code |
SWD4-20LR4P-S
|
| Features |
Oil resistant (acc. EN 60811-404)
Oil resistant (acc. IEC 60811-404) Radial water blocking cable UV resistant |
| Fitted with: |
7/8" straight socket on one side
|
| Functions |
For directly connecting the power supply to EU6E.., EU8E.. IP67 SmartWire-DT modules
|
| Cable length |
20 m
|
| Number of poles |
Four-pole
|
| Outer diameter - approximate |
11 mm
|
| Outer sheath material |
Polyvinyl chloride (PVC)
|
| Permitted bending radius, moving application with free movement - min |
0 mm
|
| Product category |
SmartWire-DT accessories
|
| Suitable as |
Signaling cable
|
| Ambient operating temperature - min |
-25 °C
|
| Ambient operating temperature - max |
70 °C
|
| Flame retardant |
In accordance with EN 60332-1-2
|
| Equipment heat dissipation, current-dependent Pvid |
0 W
|
| Heat dissipation capacity Pdiss |
0 W
|
| Heat dissipation per pole, current-dependent Pvid |
0 W
|
| Rated operational current for specified heat dissipation (In) |
0 A
|
| Static heat dissipation, non-current-dependent Pvs |
0 W
|
| 10.2.2 Corrosion resistance |
Meets the product standard's requirements.
|
| 10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard's requirements.
|
| 10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard's requirements.
|
| 10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects |
Meets the product standard's requirements.
|
| 10.2.4 Resistance to ultra-violet (UV) radiation |
Meets the product standard's requirements.
|
| 10.2.5 Lifting |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.2.6 Mechanical impact |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.2.7 Inscriptions |
Meets the product standard's requirements.
|
| 10.3 Degree of protection of assemblies |
Meets the product standard's requirements.
|
| 10.4 Clearances and creepage distances |
Meets the product standard's requirements.
|
| 10.5 Protection against electric shock |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.6 Incorporation of switching devices and components |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.7 Internal electrical circuits and connections |
Is the panel builder's responsibility.
|
| 10.8 Connections for external conductors |
Is the panel builder's responsibility.
|
| 10.9.2 Power-frequency electric strength |
Is the panel builder's responsibility.
|
| 10.9.3 Impulse withstand voltage |
Is the panel builder's responsibility.
|
| 10.9.4 Testing of enclosures made of insulating material |
Is the panel builder's responsibility.
|
| 10.10 Temperature rise |
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
|
| 10.11 Short-circuit rating |
Is the panel builder's responsibility.
|
| 10.12 Electromagnetic compatibility |
Is the panel builder's responsibility.
|
| 10.13 Mechanical function |
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
|