Eaton Moeller® series MFD I/O module with temperature measuring, range A, 6DI(2AI), 2I-Pt100, 4DO-Trans, 1AO
| Product Name |
Eaton Moeller® series MFD I/O module
|
| Catalog Number |
106045
|
| EAN |
4015081058136
|
| Product Length/Depth |
44 mm
|
| Product Height |
90 mm
|
| Product Width |
88 mm
|
| Product Weight |
0.12 kg
|
| Certifications |
UL
CSA CSA File No.: 012528 IEC 60068-2-27 CSA-C22.2 No. 142-M1987 EN 61000-6-1/-2/-3/-4 UL Category Control No.: NRAQ UL File No.: E135462 IEC 60068-2-6 UL 508 CE CSA Class No.: 2252-01 + 2258-02 CSA-C22.2 No. 213-M1987 |
| Model Code |
MFD-TAP13-PT-A
|
| Constant acceleration |
2 g, 57 - 150 Hz, according to IEC/EN 60068-2-6, Vibrations
|
| Constant amplitude |
0,15 mm, 10 - 57 Hz, according to IEC/EN 60068-2-6, Vibrations
|
| Drop and topple |
50 mm Drop height, Drop to IEC/EN 60068-2-31
|
| Height of fall (IEC/EN 60068-2-32) - max |
1 m
|
| Mounting position |
Horizontal
Vertical |
| Shock resistance |
15 g, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 11 ms, 18 Impacts
|
| Air pressure |
795 - 1080 hPa (operation)
|
| Ambient operating temperature - max |
55 °C
|
| Ambient storage temperature - max |
70 °C
|
| Ambient operating temperature - min |
-25 °C
|
| Ambient storage temperature - min |
40 °C
|
| Environmental conditions |
Condensation: prevent with appropriate measures
Clearance in air and creepage distances according to EN 50178, UL 508, CSA C22.2, No. 142 |
| Relative humidity |
5 - 95 % (non-condensing)
|
| 10.10 Temperature rise |
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
|
| 10.11 Short-circuit rating |
Is the panel builder's responsibility.
|
| 10.12 Electromagnetic compatibility |
Is the panel builder's responsibility.
|
| 10.13 Mechanical function |
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
|
| 10.2.2 Corrosion resistance |
Meets the product standard's requirements.
|
| 10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard's requirements.
|
| 10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard's requirements.
|
| 10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects |
Meets the product standard's requirements.
|
| 10.2.4 Resistance to ultra-violet (UV) radiation |
Meets the product standard's requirements.
|
| 10.2.5 Lifting |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.2.6 Mechanical impact |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.2.7 Inscriptions |
Meets the product standard's requirements.
|
| 10.3 Degree of protection of assemblies |
Meets the product standard's requirements.
|
| 10.4 Clearances and creepage distances |
Meets the product standard's requirements.
|
| 10.5 Protection against electric shock |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.6 Incorporation of switching devices and components |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.7 Internal electrical circuits and connections |
Is the panel builder's responsibility.
|
| 10.8 Connections for external conductors |
Is the panel builder's responsibility.
|
| 10.9.2 Power-frequency electric strength |
Is the panel builder's responsibility.
|
| 10.9.3 Impulse withstand voltage |
Is the panel builder's responsibility.
|
| 10.9.4 Testing of enclosures made of insulating material |
Is the panel builder's responsibility.
|
| Equipment heat dissipation, current-dependent Pvid |
2 W
|
| Heat dissipation capacity Pdiss |
0 W
|
| Heat dissipation per pole, current-dependent Pvid |
0 W
|
| Rated operational current for specified heat dissipation (In) |
0 A
|
| Static heat dissipation, non-current-dependent Pvs |
2 W
|
| Input current |
1 mA (Analog inputs)
< 1.6 mA (Analog inputs temperature resistance Pt100 or Ni1000 sensors) 2.2 mA (Digital inputs, at 24 V DC, at signal 1, I11, I12) |
| Rated operational current (Ie) |
Max. 0.5 A at signal „1” DC per channel
|
| Rated operational voltage |
> 15 V DC (I1 - I4) on 1 signal
24 V DC (digital inputs) 20.4 - 28.8 V DC (Transistor outputs) < 5 V DC (I1 - I4) on 0 signal < 8 V DC (I11, I12) on 0 signal > 8 V DC (I11, I12) on 1 signal 24 V DC |
| Supply current |
24/44 mA, Normally⁄max., On 1 signal, Transistor outputs
18/32 mA, Normally⁄max., On 0 signal, Transistor outputs |
| Supply voltage at DC - max |
24 VDC
|
| Air discharge |
8 kV, according to IEC/EN 61000-4-2, Level 3, ESD
|
| Burst impulse |
2 kV, Signal cable, according to IEC/EN 61000-4-4, Level 3
2 kV, Supply cable, according to IEC/EN 61000-4-4, Level 3 |
| Contact discharge |
6 kV, according to IEC/EN 61000-4-2, Level 3, ESD
|
| Electromagnetic fields |
10 V/m (according to IEC EN 61000-4-3)
|
| Immunity to line-conducted interference |
10 V (according to IEC/EN 61000-4-6)
|
| Radio interference class |
Class B (EN 55022)
Class B (EN 55011) |
| Surge rating |
2 kV, Supply cables, symmetrical, power pulses (Surge), EMC
0.5 kV, Supply cables, symmetrical, IEC/EN 61000-4-5, level 2, EMC |
| Electric connection type |
Spring clamp connection
|
| Features |
Measurement value resolution analog/digital depending upon the scaling
Configurable temperature range Additional measurement aids: Filter for the suppression of certain frequencies and their multiples: 50, 60, 250, 500 Hz Input signal, configurable Parallel connection of transistor outputs with resistive load, inductive load with external suppressor circuit, combination within a group - Group 1: Q1 to Q4 Overload and short-circuit protection Input, resistance thermometer Additional measurement aids: Filtering (software), smoothing of analog input signal (PT1 behavior), only with set sampling time, selectable per sensor: yes Analog outputs configurable Output, voltage Input, voltage Measuring principle: Two or three wire per sensor, selectable by connection of sensor |
| Functions |
Wire break diagnostic per sensor
Diagnostics upper sensor measuring range exceeded Card diagnostic Diagnostics below lower measurement range Thermal cutout |
| Accuracy |
1 %, Analog outputs at 25 °C
± 0.8 % of measuring range, Ni1000 sensor (offset error, linearity error, repetition accuracy, temperature error of device included) ± 3 %, of actual value, two MFD devices (Analog Inputs) ± 2 %, of actual value, within a single device (Analog Inputs) 1 %; max. 1.6 % (Pt), 1.2 % (Ni), Analog inputs temperature resistance Pt100 or Ni1000 sensors, two MFD devices between each other (without electromagnetic compatibility) ± 0.8 % of measuring range, Pt100 sensor (offset error, linearity error, repetition accuracy, temperature error of device included) 2 %, Analog outputs at-25 °C - 55 °C |
| Degree of protection |
IP20
|
| Duty factor |
100 % (Inductive load to EN 60947-5-1, Without external suppressor circuit, T0.95 = 15 ms, R = 48 Ω, L = 0.24 H)
100 % (Inductive load to EN 60947-5-1, Without external suppressor circuit, T0.95 = 1 ms, R = 48 Ω, L = 16 mH) 100 % (Inductive load to EN 60947-5-1, Without external suppressor circuit, DC-13, T0.95 = 72 ms, R = 48 Ω, L = 1.15 H) 100 % (Inductive load to EN 60947-5-1, With external suppressor circuit) |
| Insulation resistance |
According to EN 50178
|
| Mounting method |
Snap fitting (into the power supply unit)
|
| Operating frequency |
Depending on the suppressor circuit (Inductive load to EN 60947-5-1, With external suppressor circuit, Max. switching frequency, max. duty factor)
40000 Operations/h at resistive load |
| Pollution degree |
2
|
| Recovery time |
100 µs
|
| Resolution |
|
| Signal level |
0 V - 10 V, Signal voltage range, Analog outputs
|
| Switching frequency |
Max. 1500 Operations (Inductive load to EN 60947-5-1, without external suppressor circuit, DC-13, T0.95 = 72 ms, R = 48 Ω, L = 1.15 H, f = 0.5 Hz (max. DF = 50 %))
Max. 1500 Operations (Inductive load to EN 60947-5-1, without external suppressor circuit, T0.95 = 15 ms, R = 48 Ω, L = 0.24 H, f = 0.5 Hz (max. DF = 50 %)) Max. 1500 Operations (Inductive load to EN 60947-5-1, without external suppressor circuit, T0.95 = 1 ms, R = 48 Ω, L = 16 mH, f = 0.5 Hz (max. DF = 50 %)) |
| Cable length |
10 m, screened, Analog inputs temperature resistance Pt100 or Ni1000 sensors
30 m, screened, Analog inputs 100 m, unscreened, Digital inputs 24 V DC 20 m, screened, Digital inputs 24 V DC |
| Conversions |
200 - 65535 ms, Analog inputs temperature resistance Pt100 or Ni1000 sensors, with sampling time (adjustable), selectable per sensor
200 ms, Analog inputs temperature resistance Pt100 or Ni1000 sensors, without sampling time Each CPU cycle, Analog outputs Each CPU cycle, Analog inputs |
| Delay time |
0.25 ms typ., Digital inputs 24 V DC (I11 - I12), Delay time from 0 to 1, Debounce OFF
0.1 ms typ., Digital inputs 24 V DC (I1 - I4), Delay time from 0 to 1, Debounce OFF 0.2 ms typ., Digital inputs 24 V DC (I11, I12), Delay time from 1 to 0, Debounce OFF 20 ms, Digital inputs 24 V DC, Delay time from 0 to 1, Debounce ON 20 ms, Digital inputs 24 V DC, Delay time from 1 to 0, Debounce ON 0.1 ms typ., Digital inputs 24 V DC (I1 - I4), Delay time from 1 to 0, Debounce OFF |
| Frequency counter |
Counter frequency: 3 kHz (digital inputs 24 V DC)
Number: 4 (I1, I2, I3, I4 - Digital inputs 24 V DC) |
| Incremental counter |
Pulse shape: Square
Signal offset: 90° Number of counter inputs: 2 (I1 + I2, I3 + I4) Counter frequency: ≤ 3 kHz |
| Input |
2 Inputs (Pt100)
Input type resistance sensor: Platinum sensor Pt100 (according to DIN EN 60751, IEC 751: MFD-TP12-PT…) Input type resistance sensor: Nickel sensor Ni1000 (according to DIN 43760: MFD-TP12-NI…) Voltage (DC) |
| Input impedance |
11.2 kΩ
|
| Lamp load |
5 W (without Rv per channel, Q1 - Q4)
|
| Load resistance |
1 kΩ
|
| Number of inputs (analog) |
2
2 x Pt-100 or 2 x Ni1000 (temperature resistance sensors) |
| Number of inputs (digital) |
2 (I11, I12, can also be used as analog inputs)
10 2 (can also be used as analog inputs) |
| Number of outputs (analog) |
1
|
| Output |
Parallel connection of max. 4 Transistor outputs
4 Transistor Outputs Voltage (DC) |
| Output current |
Max. 0.01 A
|
| Output voltage |
Max. 2.5 V (at signal 0 at external load < 10 MΩ, transistor outputs)
U = Uₑ - 1 V (signal 1 at Iₑ = 0.5 A, transistor outputs) |
| Pulse characteristics |
Pulse shape of the frequency counter: Square (digital inputs 24 V DC)
|
| Rapid counter inputs |
Square (pulse shape)
3 kHz, Counter frequency 4 (I1, I2, I3, I4) |
| Residual current |
0.1 mA (on signal "1" per channel)
|
| Signal range |
0 V, Min. signal range, Analog inputs
10 V, Max. signal range, Analog inputs |
| Temperature measuring range - max |
400 °C
|
| Temperature measuring range - min |
-40 °C
|
| Utilization factor |
0.25 (Inductive load to EN 60947-5-1, Without external suppressor circuit, DC-13, T0.95 = 72 ms, R = 48 Ω, L = 1.15 H)
0.25 (Inductive load to EN 60947-5-1, Without external suppressor circuit, T0.95 = 15 ms, R = 48 Ω, L = 0.24 H) 0.25 (Inductive load to EN 60947-5-1, Without external suppressor circuit, T0.95 = 1 ms, R = 48 Ω, L = 16 mH) 1 (Inductive load to EN 60947-5-1, With external suppressor circuit) |
| Explosion safety category for dust |
None
|
| Explosion safety category for gas |
None
|
| Potential isolation |
Between Digital inputs 24 V DC: no
Between Analog inputs and PC interface, memory card NET, network, easyLink: yes Between Relay outputs and Power supply: yes Between Analog outputs and Power supply: no Between Analog outputs and Digital outputs: yes Between Analog outputs and PC interface, memory card, NET network, easyLink: yes Between Digital inputs 24 V DC and Outputs: yes Between Analog inputs Pt100 or Ni1000 and PC interface, memory card, easyNet, easyLink: yes Between Analog inputs and Power supply: no Between Analog inputs and Digital inputs: no Between Digital inputs 24 V DC and PC interface, memory card, easyNet, easyLink: yes Between Digital inputs 24 V DC and Power supply: no Between Transistor outputs and Inputs: yes Between Analog outputs and Digital inputs: no Between Transistor outputs and PC interface, memory card, easyNet, easyLink: yes |
| Protection against polarity reversal |
Yes (Caution: A short circuit will result if 0 V or earth is applied to the outputs in the event that the supply voltage is connected to the wrong poles.)
|
| Peak short-circuit current |
16 A
|
| Short-circuit current |
8 A, Transistor outputs
|
| Short-circuit protection |
Thermal (Q1 - Q4), (evaluation with diagnostics input I16), Transistor outputs
|
| Short-circuit tripping current |
0.7 ≤ Ie ≤ 2 per output, For Ra ≤ 10 mΩ, Transistor outputs
|
| Screwdriver size |
0.6 x 3.5 mm
|
| Terminal capacity |
0.2 - 2.5 mm² (24 - 12 AWG), flexible with ferrule