Codice del modello: MFD-CP10-ME

Eaton Moeller® series MFD Central processing unit/power supply unit, 24 V DC, expandable, without easyNet, double memory like MFD-CP 8

General specifications

Product Name
Eaton Moeller® series MFD Power supply unit
Catalog Number
133801
EAN
4015081306718
Product Length/Depth
30 mm
Product Height
90 mm
Product Width
107 mm
Product Weight
0.145 kg
Certifications
UL 508
CSA Class No.: 2252-01 + 2258-02
CSA-C22.2 No. 142-M1987
IEC 60068-2-6
UL File No.: E135462
UL Category Control No.: NRAQ
CE
CSA File No.: 012528
IEC 60068-2-27
CSA-C22.2 No. 213-M1987
EN 61000-6-1/-2/-3/-4
Catalog Notes
Current consumption at 24 V DC
Model Code
MFD-CP10-ME

Ambient conditions, mechanical

Constant acceleration
2 g, 57 - 150 Hz, according to IEC/EN 60068-2-6, Vibrations
Constant amplitude
0,15 mm, 10 - 57 Hz, according to IEC/EN 60068-2-6, Vibrations
Drop and topple
50 mm Drop height, Drop to IEC/EN 60068-2-31
Height of fall (IEC/EN 60068-2-32) - max
1 m
Mounting position
Horizontal
Vertical
Shock resistance
15 g, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 11 ms, 18 Impacts

Climatic environmental conditions

Air pressure
795 - 1080 hPa (operation)
Ambient operating temperature - max
55 °C
Ambient storage temperature - max
70 °C
Ambient operating temperature - min
-25 °C
Ambient storage temperature - min
40 °C
Environmental conditions
Clearance in air and creepage distances according to EN 50178, UL 508, CSA C22.2, No. 142
Condensation: prevent with appropriate measures
Operating temperature - max
55 °C
Operating temperature - min
25 °C
Relative humidity
5 - 95 % (non-condensing)

Communication

Bus termination
First and last station, Network easyNet
Connection
Expandable: Digital/analog inputs/outputs and AS-Interface, PROFIBUS-DP, CANopen®, DeviceNet bus systems
Connection type
Spring-cage terminals
Data transfer rate
20 kBit/s, 700 m, easyNet
10 kBit/s, 1000 m, easyNet
125 kBit/s, 125 m, easyNet
50 kBit/s, 300 m, easyNet
500 kBit/s, 25 m, easyNet
250 kBit/s, 40 m, easyNet
1000 kBit/s, 6 m, easyNet
Memory
Program and screen memory
Double program and screen memory
Memory capacity
64
Number of modules
Max. 8
Write cycles of the retentive memory
10,000,000,000 read-write cycles

Design verification

10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility.
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard's requirements.
10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of assemblies
Meets the product standard's requirements.
10.4 Clearances and creepage distances
Meets the product standard's requirements.
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9.2 Power-frequency electric strength
Is the panel builder's responsibility.
10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material
Is the panel builder's responsibility.
Equipment heat dissipation, current-dependent Pvid
3.4 W
Heat dissipation capacity Pdiss
0 W
Heat dissipation per pole, current-dependent Pvid
0 W
Rated operational current for specified heat dissipation (In)
0 A
Static heat dissipation, non-current-dependent Pvs
3.4 W

Display

Number of colors of the display
0
Screen size (diagonal)
0 in
Touch technology
None

Electrical rating

Input current
200 mA (at 24 V DC)
Permissible voltage
24 V DC
Rated operational voltage
24 V DC (-15 %/+ 20 % - power supply)
Supply voltage at AC, 50 Hz - max
0 VAC
Supply voltage at AC, 50 Hz - min
0 VAC
Supply voltage at DC - max
28.8 VDC
Supply voltage at DC - min
20.4 VDC

Electro magnetic compatibility

Air discharge
8 kV, according to IEC/EN 61000-4-2, Level 3, ESD
Burst impulse
2 kV, Supply cable, according to IEC/EN 61000-4-4, Level 3
2 kV, Signal cable, according to IEC/EN 61000-4-4, Level 3
Contact discharge
6 kV, according to IEC/EN 61000-4-2, Level 3, ESD
Electromagnetic fields
10 V/m (according to IEC EN 61000-4-3)
Immunity to line-conducted interference
10 V (according to IEC/EN 61000-4-6)
Radio interference class
Class B (EN 55011)
Class B (EN 55022)
Surge rating
2 kV, Supply cables, symmetrical, power pulses (Surge), EMC
2 kV, Supply cables, symmetrical, MFD-AC-CP8.., IEC/EN 61000-4-5, level 2, EMC
Voltage dips
≤ 10 ms

Features & Functions

Fitted with:
Message indication
Bus system easyNet optional on board
SW interfaces
Functions
Process value representation (output) possible
Process default value (input) possible
Additional software components, loadable

General information

Accuracy
± 0.02 %, Repetition accuracy of timing relays (of values)
± 5 s/day (± 0.5 h⁄year), Real-time clock, normally
Degree of protection
IP20
Degree of protection (front side)
NEMA 1
IP20
Distance
5 m, easyNet
Insulation resistance
According to EN 50178
Mounting method
Snap fitting (on the fixing shaft of the display or on top-hat rail according to IEC/EN 60715, 35 mm deep, without display)
Rail mounting possible
Product category
Multi-function-display MFD-Titan
Residual ripple
≤ 5 %
Resolution
  • 1 min (Range H:M)
  • 1 s (Range M:S)
  • 5 ms (Range S)
Software
Delivery with user program possible with MFD-COMBINATION product (Article no. 201801)
Type
Power supply unit/CPU module
Voltage type
DC

Safety

Potential isolation
Between easyNet and Inputs: yes
Between easyNet and PC interface, memory card, easyNet, easyLink: yes
Between easyNet and Power supply POW: yes
Between easyNet and Outputs: yes

Terminal capacities

Screwdriver size
0.6 x 3.5 mm
Terminal capacity
0.2 - 2.5 mm² (24 - 12 AWG), flexible with ferrule
0.2 - 4 mm² (24 - 12 AWG), solid

Esporta le caratteristiche del prodotto

Nota: Se il formato .zip scaricato presenta dei file mancanti, il loro formato non è supportato per il download.