Lead the way in sustainability with Eaton’s SC9000 active front end (AFE) variable frequency drive. Built on proven industry-leading inverter technology to optimize efficiency and reliability, the AFE drive offers bi-directional power flow allowing you to recapture energy when braking and provides power-factor correction, further reducing the costs of your electric grid. The SC9000 AFE is available stand-alone or can be seemlessly integrated into a full lineup of switchgear and controls for maximum footprint and cost savings.

Voltage Class
5 kV
Horsepower
up to 2000 hp
Main Bus Rating
up to 3000 A

핵심 기능

  • Single compact design up to 2000 hp
  • Lowest inverter part count for increased reliability
  • Easily perform routine maintenance with roll-in/roll-out inverters
  • Main bus, isolation switch, power fuses and main contactor included as standard

Synchronous Transfer Systems available for all SC9000 drives 

Eaton's Synchronous Transfer System maximizes capital efficiency by operating multiple motors of varying hp with one single drive.  The incorporation of Ampgard motor control with the double bus designs ensures superior performance. Learn more about synchronous drives transfers and benefits.

    Integrated control gear streamlines multi-configuration lineups

    Compact and economical solution combining Eaton’s Ampgard main breaker and motor starters with the SC9000 medium-voltage drive family across a common bus in a single high quality, integrated assembly.
    사양

    RATINGS

    POWER RATING                         500-2000 hp
    INPUT VOLTAGE RATING 2400-4160 V
    OUTPUT VOLTAGE RATING

    0-2400 V

    0-4160 V

    Contact Eaton if higher output voltage is required 

    BASIC IMPULSE LEVEL (BIL)
    60 kv BIL
    INTERRUPTING RATING 50 kA rms symmetrical
    AMBIENT TEMPERATURE (WITHOUT DERATING)

    0 to +40 degrees C

    0 to +50 degrees C with de-rating

    STANDARD OVERLOAD RATING (VARIABLE TORQUE)
    110% for 1 minute out of 10 minutes
    OPTIONAL OVERLOAD RATING (CONSTANT TORQUE)
    150% for 1 minute out of 10 minutes
    OUTPUT FREQUENCY
    1-120 Hz
    EFFICIENCY >97%
    POWER LOSS RIDE THROUGH 5 cycles

    Standards

    IEEE 519/1566
    UL 347A
    NEMA ICS6/ICS7
    CSA C22.2
    THIRD PARTY RECOGNITION/APPROVAL UL/cUL available for most configurations

    Enclosure

    ENCLOSURE TYPE                                                                                         
    Indoor with gaskets and filters                                 
    ACCESSIBILITY

    500-2000 hp:    112” w x 113” h x 50” d          

    BUS INSULATION Heat shrink sleeve
    BUS SUPPORTS Glass polyester
    COOLING Forced air

    DEVICES

    SWITCHING DEVICE                                           
    Medium voltage IGBTs        
    DEVICE MOUNTING
    Draw-out inverters
    INPUT POWER CIRCUIT PROTECTION Vacuum contactor with current limiting fuses

    APPLICATION DATA

    HEAT LOSS 23 W/hp or 25 W/hp when output filter is included