Medium-voltage motor control systems

SC9000 CI medium-voltage variable frequency drive

Designed for use with 4160 V induction or synchronous motors up 2500 hp, the SC9000 CI medium-voltage variable frequency drive delivers the reliable performance and energy savings you expect from an SC9000 VFD but in up to 40% less floorspace! The SC9000 CI drive positions the optional output filter above the inverter, delivering a small footprint especially when long cable lengths are required. The SC9000 CI medium-voltage drive is a fully integrated drive with main bus, isolation switch, power fuses and vacuum contactor. 

Voltage class
5 kV
Horsepower
up to 1250 hp
Main bus rating
up to 3000 A

핵심 기능

The SC9000 CI drive incorporates the same highly reliable neutral-point clamp topology as the SC9000 EP drive in addition to: 

  • Compact 3-phase inverter positioning the output filter within the enclosure without increasing footprint
  • 24-pulse transformer for IEEE® 519 compliance
  • Modular roll-in/roll-out inverter
  • Eaton’s exclusive “Soft-Mag” pre-charge system
  • Main bus, isolation switch, power fuses and main contactor are provided as standard

Efficient use of your most valuable resources

The industry leading compact design of the SC9000 CI drive is also equipped with the lowest inverter part count and low mean time before failure (MTBF) increasing reliability for your operation. Further benefit from a lower total cost of ownership due to the availability of component level inverter spares and the roll-in/roll-out inverter design simplifying routine maintenance activities.

Inrush current, meet your match

SC9000 family of medium-voltage VFDs utilize a “Soft-mag” pre-charge system which:

  • Eliminates drive inrush current
  • Simplifies protection and coordination
  • Provides a possible reduction of incident energy and PPE level at the drive

Integrated control gear streamlines multi-configuration lineups

Compact and economical solution combining Eaton’s Ampgard main breaker and motor starters with the SC9000 medium-voltage drive family across a common bus in a single high quality, integrated assembly.
사양

RATINGS

POWER RATING                         100-1250 hp
INPUT VOLTAGE RATING 2400-4160 V
OUTPUT VOLTAGE RATING

0-2400 V

0-3300 V

0-4160 V

Contact Eaton if higher output voltage is required 

BASIC IMPULSE LEVEL (BIL)
60 kv BIL
INTERRUPTING RATING 50 kA rms symmetrical
AMBIENT TEMPERATURE (WITHOUT DERATING)
0 to 40 degrees C
STANDARD OVERLOAD RATING (VARIABLE TORQUE)
110% for 1 minute out of 10 minutes
OPTIONAL OVERLOAD RATING (CONSTANT TORQUE)
150% for 1 minute out of 10 minutes
OUTPUT FREQUENCY
1-120 Hz

Standards

UL                                                                                        347A
NEMA ICS6/ICS7
CSA C22.2
THIRD PARTY RECOGNITION/APPROVAL UL/cUL available for most configurations
SEISMIC QUALIFICATION IBC

Enclosure

ENCLOSURE TYPE                                                                                         
Indoor with gaskets and filters                                 
ACCESSIBILITY
Front                                                                  
INDOOR SECTION DIMENSIONS (TYPICAL)

65" w x 50" d x 92" h

Consult factory for applications above 1250 hp

BUS INSULATION Heat shrink sleeve
BUS SUPPORTS Glass polyester
COOLING Forced air

DEVICES

SWITCHING DEVICE                                           
Medium voltage IGBT        
DEVICE MOUNTING
Draw-out inverter
ISOLATION TRANSFORMER 24-pulse
INPUT POWER CIRCUIT PROTECTION Vacuum contactor with current limiting fuses

APPLICATION DATA

HEAT LOSS 23 Watts/horsepower (typical)