Informacijos paieška
Atsisiųsti dokumentą () iš 20
Užtikriname, kad tai, kas svarbu, veiktų*

066167
Modelio kodas: EMT6-DB

Eaton Moeller® series EMT6 Thermistor overload relay for machine protection, 24-240V50/60HZ/DC

General specifications

Product Name
Eaton Moeller® series EMT6 Thermistor overload relay
Catalog Number
066167
EAN
4015080661672
Product Length/Depth
103 mm
Product Height
83 mm
Product Width
23 mm
Product Weight
0.132 kg
Certifications
UL File No.: E29184
UL
EN 55011
CSA Class No.: 3211-03
IEC/EN 60947
CE
UL 508
IEC/EN 61000-4-2
CSA
UL Category Control No.: NKCR
IEC/EN 60947-8
CSA-C22.2 No. 14
CSA File No.: 12528
VDE 0660
IEC/EN 61000-4-3
Model Code
EMT6-DB

Klimato ir aplinkos sąlygos

Ambient operating temperature - max
60 °C
Ambient storage temperature - max
85 °C
Ambient operating temperature - min
-25 °C
Ambient operating temperature (enclosed) - max
45 °C
Ambient operating temperature (enclosed) - min
-25 °C
Ambient storage temperature - min
-45 °C
Climatic proofing
Damp heat, cyclic, to IEC 60068-2-30
Damp heat, constant, to IEC 60068-2-78

Kontaktai

Number of contacts (change-over contacts)
0
Number of contacts (normally closed contacts)
1
Number of contacts (normally open contacts)
1

Gaminio patikrinimas

Equipment heat dissipation, current-dependent Pvid
0 W
Heat dissipation capacity Pdiss
0 W
Heat dissipation per pole, current-dependent Pvid
0 W
Rated operational current for specified heat dissipation (In)
0 A
Static heat dissipation, non-current-dependent Pvs
0.8 W

Elektros parametrai

Conventional thermal current Ith of auxiliary contacts (1-pole, open)
6 A
Pick-up voltage
0.85 - 1.1 V x Uₑ
Power consumption
2 W at DC
3.5 VA at AC
Rated control supply voltage (Us) at AC, 50 Hz - max
240 V
Rated control supply voltage (Us) at AC, 50 Hz - min
24 V
Rated control supply voltage (Us) at AC, 60 Hz - max
240 V
Rated control supply voltage (Us) at AC, 60 Hz - min
24 V
Rated control supply voltage (Us) at DC - max
240 V
Rated control supply voltage (Us) at DC - min
24 V
Rated insulation voltage (Ui)
400 V
Rated operational current (Ie)
3 A at AC-14, 400 V (NC)
3 A at AC-14, 380 V 400 V 415 V (NC)
3 A at AC-15, 220 V 230 V 240 V (NO)
3 A at AC-15, 220 V 230 V 240 V (NC)
3 A at AC-15, 220 V 230 V 240 V
3 A at AC-14, 300 V (NC)
1 A at AC-15, 300 V (NC)
3 A at AC-14, 300 V (NO)
1 A at AC-15, 380 V 400 V 415 V (NO)
3 A at AC-14, 380 V 400 V 415 V (NO)
1 A at AC-15, 300 V (NO)
1 A at AC-15, 380 V 400 V 415 V (NC)
Rated operational voltage (Ue) - max
240 V
Reset resistance
1600 Ω
Short-circuit protection rating
Max. 6 A gG/gL, Fuse, Contacts
Trip resistance
3600 Ω
Voltage rating - max
600 V

Elektromagnetinis suderinamumas

Air discharge
8 kV
Burst impulse
1 kV, Signal cable
2 kV, Supply cable
According to IEC/EN 61000-4-4
Contact discharge
6 kV
Electromagnetic fields
10 V/m at 80 - 1000 MHz (according to IEC EN 61000-4-3)
3 V/m at 1.4 - 2 GHz (according to IEC EN 61000-4-3)
1 V/m at 2.0 - 2.7 GHz (according to IEC EN 61000-4-3)
Immunity to line-conducted interference
10 V (according to IEC/EN 61000-4-6)
Radio interference class
Class B (EN 55011)
Surge rating
According to IEC/EN 61000-4-5, power pulses (Surge), EMC
2 kV, symmetrical, power pulses (Surge), EMC
4 kV, asymmetrical, power pulses (Surge), EMC

Features & functions

Electric connection type
Screw connection
Functions
Manual or remote resetting
Notifications of mains and faults via LED display
Test function via separate button
External reset possible
Manual reset

Bendroji informacija

Degree of protection
IP20
Mounting position
As required
Overvoltage category
III
Pollution degree
3
Product category
EMT6 thermistor overload relay for machine protection
Protection
Finger and back-of-hand proof, Protection against direct contact when actuated from front (EN 50274)
Rated impulse withstand voltage (Uimp)
6000 V AC
4000 V AC
Safe isolation
250 V AC, Between the contacts and power supply, According to EN 61140
250 V AC, Between the contacts, According to EN 61140
Shock resistance
10 g, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms
Voltage type
AC/DC

Gnybto pajėgumai

Screw size
M3.5, Terminal screw
Screwdriver size
1 x 6 mm, Terminal screw, Standard screwdriver
2, Terminal screw, Pozidriv screwdriver
Terminal capacity
1 x (0.5 - 2.5) mm², solid
1 x (0.5 - 2.5) mm², flexible with ferrule
2 x (0.5 - 1.5) mm², flexible with ferrule
2 x (0.5 - 1.5) mm², solid
20 - 14 AWG, solid or stranded
Tightening torque
1.2 Nm, Screw terminals

Eksportuoti gaminio specifikaciją

Pastaba: Jei failo atsisiųstame .zip pakete nėra, vadinasi šio tipo failas nėra tinkamas atsisiųsti kartu su kitais.