Atsisiųsti dokumentą () iš 20
Užtikriname, kad tai, kas svarbu, veiktų*

110012
Modelio kodas: NZMS3-4-VE400/250

NZMS3-4-VE400/250. Circuit-breaker, 4 p, 400A, selective

General specifications

Product Name
Eaton Moeller series NZM molded case circuit breaker electronic
Catalog Number
110012
EAN
4015081095780
Product Length/Depth
166 mm
Product Height
275 mm
Product Width
185 mm
Product Weight
8.4 kg
Compliances
RoHS conform
Model Code
NZMS3-4-VE400/250

Gaminio specifikacijos

Amperage Rating
400 A
Voltage rating
690 V - 690 V
Features
Motor drive optional
Protection unit
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard's requirements.
10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of assemblies
Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances
Meets the product standard's requirements.
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9.2 Power-frequency electric strength
Is the panel builder's responsibility.
10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material
Is the panel builder's responsibility.
Pollution degree
3
Mounting Method
Built-in device fixed built-in technique
Equipment heat dissipation, current-dependent
72 W
Number of auxiliary contacts (change-over contacts)
0
Number of auxiliary contacts (normally closed contacts)
0
Number of auxiliary contacts (normally open contacts)
0
Degree of protection
IP20
Electrical connection type of main circuit
Screw connection
Overvoltage category
III
Number of poles
Four-pole
Type
Circuit breaker
Position of connection for main current circuit
Front side
Handle type
Rocker lever
Short delay current setting (Isd) - max
4000 A
Short delay current setting (Isd) - min
800 A
Instantaneous current setting (Ii) - max
4400 A
Instantaneous current setting (Ii) - min
800 A
Overload current setting (Ir) - max
400 A
Overload current setting (Ir) - min
200 A
Rated short-circuit breaking capacity Ics (IEC/EN 60947) at 230 V, 50/60 Hz
100 kA
Rated short-circuit breaking capacity Ics (IEC/EN 60947) at 400/415 V, 50/60 Hz
70 kA
Rated short-circuit breaking capacity Ics (IEC/EN 60947) at 440 V, 50/60 Hz
65 kA
Rated short-circuit breaking capacity Ics (IEC/EN 60947) at 525 V, 50/60 Hz
18 kA
Rated short-circuit breaking capacity Ics (IEC/EN 60947) at 690 V, 50/60 Hz
6 kA
Rated short-circuit breaking capacity Icu (IEC/EN 60947) at 525 V, 50/60 Hz
36 kA
Rated short-circuit breaking capacity Icu (IEC/EN 60947) at 400/415 V, 50/60 Hz
70 kA
Rated short-circuit breaking capacity Icu (IEC/EN 60947) at 230 V, 50/60 Hz
100 kA
Rated short-circuit breaking capacity Icu (IEC/EN 60947) at 690 V, 50/60 Hz
25 kA
Rated short-circuit breaking capacity Icu (IEC/EN 60947) at 440 V, 50/60 Hz
65 kA
Rated short-circuit breaking capacity Icu (UL489, CSA22.2) at 240 V, 60 Hz
100 kA

Eksportuoti gaminio specifikaciją

Serial Number Verified :
Authenticated:
The product is verified as being authentic; however, this does not guarantee the condition or fit for purpose of the product.

Patvirtinti gaminį

Nurodykite 16–17 skaitmenų serijos numerį
Įvedamame serijos numeryje neturi būti specialiųjų simbolių. Įvestas serijos numeris klaidingas – turi būti 16 arba 17 skaitmenų. Nurodytas serijos numeris nerastas. Bandykite dar kartą arba pranešti apie šį nesklandumą papildomai pagalbai. Įvestas serijos numeris neatitinka gaminio. Patikrinkite gaminio serijos numerį ir bandykite dar kartą. Spustelėkite čia atverti įvesto serijos numerio gaminio puslapį „Eaton“ sistemai šios serijos numeris kelia įtarimų, bandykite dar kartą arba pranešti apie šį nesklandumą papildomai pagalbai.
Serijos numeris
Nustatyti iš naujo „Eaton“ sistemai šios serijos numeris kelia įtarimų, bandykite dar kartą arba pranešti apie šį nesklandumą papildomai pagalbai. Šis serijos numeris yra klaidingas, todėl „Eaton“ sistema jo neatpažįsta. Naudokite šią formą pranešti apie šį nesklandumą papildomai pagalbai.
Įveskite 6 skaitmenų patvirtinimo kodą
Įvestas gaminio kodas kelia įtarimų! Bandykite dar kartą arba pranešti apie šį nesklandumą papildomai pagalbai. Įvestas patvirtinimo kodas neatitinka įrašų apie šį serijos numerį. Bandykite dar kartą arba pranešti apie šį nesklandumą papildomai pagalbai. Klaidingas patvirtinimo kodas. Ilgis turi būti 6 simbolių. pranešti apie šį nesklandumą papildomai pagalbai. Būtinas patvirtinimo kodas pranešti apie šį nesklandumą papildomai pagalbai.
Prieš patvirtindami tapatumą atlikite „Captcha“ užduotį.