197215
EASY-E4-AC-12RC1

Eaton Moeller® series EASY Control relays easyE4 with display (expandable, Ethernet), 100 - 240 V AC, 110 - 220 V DC (cULus: 100 - 110 V DC), Inputs Digital: 8, screw terminal EASY-E4-AC-12RC1

Especificaciones generales

Product Name
Eaton Moeller® series EASY Control relay
Catalog Number
197215
EAN
4015081939442
Product Length/Depth
58 mm
Product Height
90 mm
Product Width
72 mm
Product Weight
0.25 kg
Compliances
Eaton supports the product until its end of life
Certifications
UL File No.: E205091
CE
UL hazardous location group C (ethylene)
UL hazardous location class I
UL hazardous location group D (propane)
UL hazardous location group A (acetylene)
UL hazardous location group B (hydrogen)
UL hazardous location division 2
cULus Ordinary Location
DNV
TAA00002HT
cULus Hazard Location
UL File No.: E523283
EN 61131-2
IEC 61131-2
EN IEC 61000-6-3
IEC 61000-6-3
EN IEC 61010-2-201
IEC 61010-2-201
UL 61010-1
UL 61010-2-201
CSA C22.2 No. 61010-1
CSA C22.2 No. 61010-2-201
UL 121201
CSA C22.2 No. 213
Catalog Notes
Accuracy of the real-time clock depending on ambient air temperature - fluctuations of up to ± 5 s/day (± 0.5 h⁄year) are possible

Especificaciones del producto

Used with
easyE4
Type
easyE4 base device
Features
Networkable (Ethernet)
Expandable
Display indication of 6 lines x 16 characters
Air discharge
8 kV
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility.
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard's requirements.
10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of assemblies
Meets the product standard's requirements.
10.4 Clearances and creepage distances
Meets the product standard's requirements.
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9.2 Power-frequency electric strength
Is the panel builder's responsibility.
10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material
Is the panel builder's responsibility.
Cable type
Ethernet: CAT5
Fitted with:
Relay output
Timer
Keypad
Display
Real time clock
Pollution degree
2
Accuracy
± 1 %, Repetition accuracy of timing relays (of values)
± 2 s/day, Real-time clock to inputs (± 0.2 h⁄Year)
Burst impulse
2 kV, I/O port
2 kV, Power supply port
1 kV, communication port
According to IEC/EN 61131-2
Utilization category
B 300 Light Pilot Duty, UL/CSA Control Circuit Rating Codes AC
R 300 Light Pilot Duty, UL/CSA Control Circuit Rating Codes DC
Rated impulse withstand voltage (Uimp)
Relay outputs: 6 kV (contact-coil)
Air pressure
795 - 1080 hPa (operation)
Category (EN 954-1)
None
Explosion safety category for dust
None
Environmental conditions
Condensation: prevent with appropriate measures
Clearance in air and creepage distances according to EN 50178, EN 61010-2-201, UL61010-2-201, CSA-C22.2 NO. 61010-2-201
Indication
LCD-display used as status indication of digital I/Os
Explosion safety category for gas
None
Mounting method
Screw fixing using fixing brackets ZB4-101-GF1 (accessories)
Rail mounting possible
Top-hat rail fixing (according to IEC/EN 60715, 35 mm)
Wall mounting/direct mounting
Front build in possible
Screwdriver size
3.5 x 0.6 mm, Terminal screw
Voltage type
AC/DC
Mounting position
Horizontal
Vertical
Output
4 Relay Outputs
min. recommended load: 12 V AC/DC > 500 mA
Contact discharge
6 kV
Base type
Yes
Safety performance level (EN ISO 13849-1)
None
SIL (IEC 61508)
None
Ambient operating temperature - max
55 °C
Ambient operating temperature - min
-25 °C
Ambient storage temperature - max
70 °C
Ambient storage temperature - min
-40 °C
Display temperature - max
55 °C
Display temperature - min
0 °C
Equipment heat dissipation, current-dependent Pvid
1 W
Heat dissipation capacity Pdiss
0 W
Heat dissipation per pole, current-dependent Pvid
0 W
Height of fall (IEC/EN 60068-2-32) - max
0.3 m
Number of HW-interfaces (industrial ethernet)
1
Number of HW-interfaces (other)
0
Number of HW-interfaces (parallel)
0
Number of HW-interfaces (RS-232)
0
Number of HW-interfaces (RS-422)
0
Number of HW-interfaces (RS-485)
0
Number of HW-interfaces (serial TTY)
0
Number of HW-interfaces (USB)
0
Number of HW-interfaces (wireless)
0
Overvoltage category
Power supply + Inputs + Extension interface: III
Relay outputs: III
Duty factor
100 %
Software
EASYSOFT-SWLIC/easySoft
Surge rating
1 kV, Line-to-Line, Power supply port
2 kV, Line-to-Earth, Power supply port
1 kV, Line-to-Line, Input port
2 kV, Line-to-Earth, Input port
1 kV, Line-to-Earth, communication port
According to IEC/EN 61131-2
Cable length
Digital inputs (I1 - I6, AC): ≤ 40 m (unshielded)
Digital inputs (I7 - I8, AC): ≤ 100 m (unshielded)
Electromagnetic fields
10 V/m at 0.08 - 1.0 GHz (according to IEC/EN 61131-2)
3 V/m at 1.0 - 6 GHz (according to IEC/EN 61131-2)
Display type
Monochrome
Protection against polarity reversal
Yes
Number of inputs (analog)
0
Connection type
Screw terminal
Ethernet: RJ45 plug, 8-pole
Drop and topple
50 mm Drop height, Drop to IEC/EN 60068-2-31
Immunity to line-conducted interference
10 V (according to IEC/EN 61131-2)
Radio interference class
Class B (EN 61000-6-3)
Number of outputs (digital)
4
Data transfer rate
10/100 MBit/s
Relative humidity
5 - 95 % (IEC 60068-2-30, IEC 60068-2-78)
Degree of protection
IP20
Safe isolation
Relay outputs: 300 V AC, Between two contacts
Relay outputs: 300 V AC, Between coil and contact
Delay time
Digital inputs (100 - 240 V DC): 20 ms, from 0 to 1, Debounce ON
Digital inputs (100 - 240 V DC): 0.03 ms typ., from 0 to 1, Debounce OFF
Digital inputs (100 - 240 V DC): 20 ms, from 1 to 0, Debounce ON
Digital inputs (100 - 240 V DC): 0.03 ms typ., from 1 to 0, Debounce OFF
Digital inputs (100 - 240 V AC 50 Hz): 45 ms, from 0 to 1, Debounce ON
Digital inputs (100 - 240 V AC 50 Hz): 45 ms, from 1 to 0, Debounce ON
Digital inputs (100 - 240 V AC 60 Hz): 38 ms, from 0 to 1, Debounce ON
Digital inputs (100 - 240 V AC 60 Hz): 21 ms typ., from 0 to 1, Debounce OFF
Digital inputs (100 - 240 V AC 60 Hz): 38 ms, from 1 to 0, Debounce ON
Digital inputs (100 - 240 V AC 60 Hz): 21 ms typ., from 1 to 0, Debounce OFF
Digital inputs (100 - 240 V AC 50 Hz): 25 ms typ., from 1 to 0, Debounce OFF
Digital inputs (100 - 240 V AC 50 Hz): 25 ms typ., from 0 to 1, Debounce OFF
Protocol
Modbus TCP
Residual ripple
Power supply: ≤ 5 %
Supply frequency
50/60 Hz (± 5%)
Insulation resistance
According to EN IEC 61010-2-201, UL61010-2-201, CSA-C22.2 NO. 61010-2-203
Vibration resistance
8.4 - 150 Hz, 1 g constant acceleration
5 - 8.4 Hz, 3.5 mm constant amplitude
According to IEC/EN 61131-2
Input current
2 x 4 mA (I7 - I8, at 115 VAC, 60 Hz, at signal 1)
6 x 0.25 mA (I1 - I6, at 115V AC, 60 Hz, at signal 1)
2 x 6 mA (I7 - I8, at 230 VAC, 50 Hz, at signal 1)
6 x 0.5 mA (I1 - I6, at 230 VAC, 50 Hz, at signal 1)
Shock resistance
15 g, Mechanical, acc. to IEC/EN61131-2, Half-sinusoidal shock 11 ms, 18 Impacts
Input frequency
50/60 Hz (Digital inputs at AC)
Input voltage
Condition 0: 0 - 40 V AC/DC (Digital inputs)
Condition 1: 79 - 264 V AC/DC (Digital inputs)
Rated breaking capacity
300000 Operations at AC-15, 250 V AC, 3 A (600 Ops./h)
200000 Operations at DC-13, L/R ≦ 150 ms, 24 V DC, 1 A (500 Ops./h)
Lifespan, electrical
25,000 Operations (Fluorescent lamp load 1 x 58 W at 230/240 V AC, conventional, compensated)
25,000 Operations (Fluorescent lamp load 10 x 58 W at 230/240 V AC, with upstream electrical device)
25,000 Operations (Filament bulb load at 1000 W, 230/240 V AC)
25,000 Operations (Fluorescent lamp load 10 x 58 W at 230/240 V AC, uncompensated)
25,000 Operations (Filament bulb load at 500 W, 115/120 V AC)
Lifespan, mechanical
10,000,000 Operations
Making/breaking capacity
3600/360 VA (AC, at B 300)
28/28 VA (DC, at R 300)
Parallel switching
Not permitted
Potential isolation
Power supply + Inputs + Extension interface against Outputs: yes
POW+Inputs+Extension interface vs. Ethernet+Functional Earth: yes
Outputs against Ethernet + Functional Earth: yes
Outputs against each other: yes
Number of inputs (digital)
8
Power loss
10 VA
Voltage dips
10 ms at 100 V DC
20 ms at 100 V AC
Uninterrupted current
5 A AC, max. thermal continuous current cos ϕ = 1 at B 300 (UL/CSA)
8 A AC, at 240 V AC (UL/CSA)
8 A DC, at 24 V DC (UL/CSA)
1 A DC, at R 300 (UL/CSA)
10 A AC, at 240 V AC (UL/CSA)
Number of interfaces (PROFINET)
0
Number of outputs (analog)
0
Static heat dissipation, non-current-dependent Pvs
4 W
Supply voltage at AC, 50 Hz - max
264 VAC
Supply voltage at AC, 50 Hz - min
85 VAC
Supply voltage at AC, 60 Hz - max
264 VAC
Supply voltage at AC, 60 Hz - min
85 VAC
Supply voltage at DC - max
264 VDC
Supply voltage at DC - min
85 VDC
Switching current
8 A
Product category
Control relays easyE4
Protection
B16 circuit breaker or 8 A (T) fuse, Protection of an Output relay
Power consumption
4 W
Rated operational voltage
Power supply: 100 - 240 V AC (-15 %/+ 10 %)
Power supply: 100 - 240 V DC (-15 %/+ 10 %) (IEC)
Power supply: 100 - 110 V DC (-15 %/+ 10 %) (cULus)
Relay outputs: max. 300 V AC/DC
Inputs: shall be identical to the power supply voltage
Short-circuit protection
≥ 1A (T), Fuse, Power supply
Switching frequency
10 Hz, Relay outputs
2 Hz, Resistive load/lamp load, Relay outputs
0.5 Hz, Inductive load, Relay outputs
Terminal capacity
0.2 - 4 mm² (AWG 22 - 12), solid
0.2 - 2.5 mm², flexible with ferrule
0.2 - 2.5 mm², flexible without ferrule
Tightening torque
0.6 Nm, Screw terminals

Exportar especificación del producto

Nota: Si faltan archivos en la descarga .zip, el tipo de archivo no es compatible con la descarga masiva.
Serial Number Verified :
Authenticated:
The product is verified as being authentic; however, this does not guarantee the condition or fit for purpose of the product.

Autenticar producto

Ingrese su número de serie de 16 a 17 dígitos
El número de serie que ingresó no debe contener caracteres especiales. El número de serie que ingresó no es correcto, debe ser de 16 o 17 dígitos. No se encontró el número de serie que ingresó. Inténtelo de nuevo. reporte este problema para obtener más ayuda. El número de serie que ingresó no coincide con el producto. Verifique el número de serie de su producto e inténtelo de nuevo. Haga clic aquí para navegar a la página del producto para el número de serie que ha ingresado El número de serie es SOSPECHOSO. reporte este problema para obtener más ayuda.
Número de serie
Restablecer El número de serie es SOSPECHOSO. reporte este problema para obtener más ayuda. Eaton no reconoce el número de serie y es inválido. Utilice este formulario para reporte este problema para obtener más ayuda.
Ingrese el código de autenticación de 6 dígitos
El producto que ingresó es sospechoso. Inténtelo de nuevo. reporte este problema para obtener más ayuda. El código de autenticación que ingrese no coincide con nuestros registros para este número de serie. Inténtelo de nuevo o reporte este problema para obtener más ayuda. Código de autenticación no válido. hex. debe tener 1 o 2 caracteres de largo reporte este problema para obtener más ayuda. El código de autenticación es obligatorio reporte este problema para obtener más ayuda.
Complete el desafío Captcha antes de autenticarse.
Contáctenos para reportar problemas
x
Reportar un problema
Ingrese su nombre completo.
x
Gracias, su problema ha sido enviado; nuestro equipo de productos se comunicará con usted pronto.

Register Product

Please complete the form to register your product