Eaton Moeller series NZM - Molded Case Circuit Breaker. Withdrawable carrier, 3p, 1600A
| Product Name |
Eaton Moeller series NZM plug-in unit
|
| Catalog Number |
266717
|
| EAN |
4015082667177
|
| Product Length/Depth |
509 mm
|
| Product Height |
240 mm
|
| Product Width |
297 mm
|
| Product Weight |
28 kg
|
| Compliances |
IEC
RoHS conform |
| Certifications |
IEC/EN 60947
|
| Features |
Version as built-in device
|
| 10.10 Temperature rise |
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
|
| 10.11 Short-circuit rating |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
| 10.12 Electromagnetic compatibility |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
| 10.13 Mechanical function |
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
|
| 10.2.2 Corrosion resistance |
Meets the product standard's requirements.
|
| 10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard's requirements.
|
| 10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard's requirements.
|
| 10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects |
Meets the product standard's requirements.
|
| 10.2.4 Resistance to ultra-violet (UV) radiation |
Meets the product standard's requirements.
|
| 10.2.5 Lifting |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.2.6 Mechanical impact |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.2.7 Inscriptions |
Meets the product standard's requirements.
|
| 10.3 Degree of protection of assemblies |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.4 Clearances and creepage distances |
Meets the product standard's requirements.
|
| 10.5 Protection against electric shock |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.6 Incorporation of switching devices and components |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.7 Internal electrical circuits and connections |
Is the panel builder's responsibility.
|
| 10.8 Connections for external conductors |
Is the panel builder's responsibility.
|
| 10.9.2 Power-frequency electric strength |
Is the panel builder's responsibility.
|
| 10.9.3 Impulse withstand voltage |
Is the panel builder's responsibility.
|
| 10.9.4 Testing of enclosures made of insulating material |
Is the panel builder's responsibility.
|
| Frame |
NZM4
|
| Mounting Method |
Withdrawable
|
| Climatic proofing |
Damp heat, constant, to IEC 60068-2-78
Damp heat, cyclic, to IEC 60068-2-30 |
| Ambient operating temperature - max |
70 °C
|
| Ambient operating temperature - min |
-25 °C
|
| Ambient storage temperature - max |
70 °C
|
| Ambient storage temperature - min |
40 °C
|
| Nominal current |
1488 A
|
| Protection against direct contact |
Finger and back-of-hand proof to VDE 0106 part 100
|
| Terminal equipment included |
Extension contacts
|
| Isolation |
300 V AC (between the auxiliary contacts)
500 V AC (between auxiliary contacts and main contacts) |
| Direction of incoming supply |
As required
|
| Electrical connection type of main circuit |
Other
|
| Mounting position |
Vertical
|
| Number of poles |
Three-pole
|
| Type |
Accessory
Extension insert for basic unit
|
| Shock resistance |
15 g (half-sinusoidal shock 11 ms)
|