SmartPro 120V 2200VA 1920W Line-Interactive Sine Wave UPS, 2U, Extended Run, WEBCARDLX, LCD, USB, DB9
Product Name |
Eaton Tripp Lite series SmartPro UPS
|
Catalog Number |
SM2200RMXL2UPN
|
UPC |
037332257819
|
Product Length/Depth |
24 in
|
Product Height |
8.8 in
|
Product Width |
21.7 in
|
Product Weight |
64 lb
|
Compliances |
FCC Class A
RoHS |
Certifications |
NOM
CSA certified UL 1778 |
Topology |
Line-interactive
|
Form factor |
Rackmount
|
Rack size |
2U
|
Package contents |
|
Input nominal voltage |
120 VAC
|
Nominal frequency |
60 Hz
|
Input frequency range |
60 Hz
|
Receptacle |
|
Output nominal voltage |
110 / 120V
|
Electric current - max |
16A
|
Battery replacement |
RBC94-2U
|
Runtime at half load |
12 min
|
Noise level |
45 dBA maximum, front side 1m
|
Relative humidity |
0-95% non-condensing
|
Front Panel LCD Display |
Front panel LCD information and configuration screen offers detailed UPS and site power status and operating data, plus configuration of voltage, operating mode, alarm function and a variety of additional options (see manual for detailed LCD configuration and monitoring options)
|
Output Receptacles |
5-15/20R
5-15R |
Product Features |
Individually Controllable Load Banks
Expandable Runtime |
Product Highlights |
Pre-installed WEBCARDLX network interface supports Auto Probe feature
Protects equipment against blackouts, brownouts, overvoltages, surges and line noise Maintains continuous 120V nominal output during brownouts and overvoltages Easy-to-read LCD allows real-time monitoring of voltage, battery status and other data Keeps AC power running during blackouts to allow time for file saves and safe shutdown Pre-installed WEBCARDLXE network interface supports Auto Probe feature |
PowerAlert Software |
For local monitoring via the UPS’s built-in USB / Serial ports, download PowerAlert software at https://tripplite.eaton.com/products/power-alert
|
Nominal Output Voltage |
110 / 120V
|
Network Management Cards |
WEBCARDLXE
|
Network Management Cards Details |
Network management card included
|
Output power factor |
0.87
|
Phase (input) |
Single-phase
|
Runtime at full load |
4.5 min. (1920W)
|
Communication interface |
USB (HID enabled)
Slot for SNMP / Web interface DB9 Serial EPO (emergency power off) Pre-installed network card USB and DB9 serial cables included |
Battery Access |
Front panel battery access door
|
Typical Battery Runtime |
Expandable Runtime
|
Dc Voltage |
48
|
Operating Temperature Range |
32° to 104°F (0° to 40°C)
|
Communications Cable |
USB and DB9 cabling included
|
Grounding Details |
Back panel grounding lug
|
Optional Mounting Accessory Notes |
Optional 2-9USTAND enables upright tower UPS placement; 2POSTRMKITWM enables wall-mount and 2-post rackmount installation; 4POSTRAILKITWM enables installation in 4-post short-depth racks from 14.5 to 23.5 inches (368 to 597mm); UPSHDEARKIT enables installation in 2 or 4-post racks using front vertical rails only, without rear support
|
Load Management Receptacles |
Two switched single outlet load banks (1 5-15/20R & 1 5-15R)
|
High Voltage Transfer to Battery Power |
145
|
Low Voltage Transfer to Battery Power |
83
|
Undervoltage Correction |
Voltage boost of 12% applies when input voltage is between 96 and 108
|
Network UPS Tools (NUT) Compatibility |
NUT compatible. See a full list of NUT compatible Tripp Lite UPS systems at https://networkupstools.org/stable-hcl.html?manufacturer=Tripp%20Lite
|
Application |
Large Network
|
Switch configuration |
3 pushbutton switches control OFF / ON power status, MODE selection and MUTE / ENTER control functions
|
AC suppression joule rating |
570
|
Housing material |
Steel
|
Output AC waveform (AC mode) |
Pure Sine wave
|
Output AC waveform (battery mode) |
Pure Sine wave
|
Output Capacity (kVA) |
2.2
|
Output Capacity (kW) |
1.92
|
Output Capacity (VA) |
2200
|
Output Capacity Details |
Supports 1920 watts output capacity when used with external battery packs
|
Primary UPS Depth (mm) |
483
|
Primary UPS Height (mm) |
89
|
Primary UPS Width (mm) |
445
|
AC Suppression Response Time |
Instantaneous
|
Alarm Interface |
Power-fail alarm can be temporarily silenced using alarm-cancel switch; silent mode alarm configuration option available
|
Audible Alarms |
Audible alarm indicates power-failure, overload and low-battery conditions
|
Battery Start Capability |
Cold-start operation supported
|
Cooling Method |
Fan
|
Battery Replacement Description |
Hot-swappable, user replaceable batteries
|
Minimum Required Rack Depth With External Battery Pack |
26
|
Minimum Required Rack Depth Without External Battery Pack |
24.5
|
Output Voltage Regulation (Line Mode) |
-14%, +6%
|
Output Voltage Regulation(Battery Mode) |
+/- 5%
|
Overvoltage Correction |
Voltage reduction of 12% applies when input is between 127 and 145
|
Rechargeable Battery |
Less than 4.5 hours from 10% to 90% (typical, full load discharge)
|
Recommended Electrical Service |
20A 120V
|
Storage Temperature |
5° to 122°F (-15° to 50°C)
|
Included Mounting Accessory Description |
Included 4POSTRAILKIT mounting bracket enables installation in 4 post racks from 20.5 to 36 inches (521 to 914mm)
|
Network Monitoring Port Description |
Pre-installed WEBCARDLXE Network Management Card interface
|
Nominal Voltage Details |
120v nominal output in battery mode
|
Voltage Regulation Description |
Automatic voltage regulation (AVR) maintains regulated line power output with an input voltage range of 83 and 145
|
WatchDog Compatibility |
Supports Watchdog application, OS and hard-reboot restart options for remote applications
|
Maximum Input Amps |
16
|
Minimum Required Rack Depth (cm) |
55.88
|
Minimum Required Rack Depth (inches) |
22
|
UPS Input Cord Length (m) |
3.1
|
UPS Power Module Dimensions |
3.50 x 17.50 x 19.00
|
Power Mode Transfer Time |
5 milliseconds (line to battery mode); 1 millisecond (battery to line mode)
|
Connected Equipment Insurance |
$250,000 Ultimate Lifetime Insurance
|
Optional Accessories |
2 post rackmount (2POSTRMKITWM)
2-4 post front rail rackmount (UPSHDEARKIT) 4 post rackmount short-depth (4POSTRAILKITWM) Tower (2-9USTAND) Wallmount (2POSTRMKITWM) |
EMI AC Noise Suppression |
EMI / RFI AC Noise Suppression
|
UPS Input Connection Type |
5-20P
|
External Battery Pack Compatibility |
BP48V24-2U (limit 1)
BP48V27-2US (multi-pack compatible) BP48V60RT3UTAA (multi-pack compatible) |
Green Energy-Saving Features |
Greater than 95% efficiency - GREEN UPS
Individually controllable load banks |
High Availability UPS Features |
Remote management
Automatic voltage regulation (AVR) Hot swappable batteries Auto probe monitoring and reboot (included) Surge/noise protection |