SmartPro 1440VA 1100W Line-Interactive Sine Wave UPS, AVR, 120V, 5 Outlets, Network Card Option, LCD, USB, 1U Rack/Tower
Product Name |
Eaton Tripp Lite series SmartPro UPS
|
Catalog Number |
SMC1500RT1U
|
UPC |
037332239358
|
Product Length/Depth |
21.81 in
|
Product Height |
1.73 in
|
Product Width |
17.32 in
|
Product Weight |
0.001 lb
|
Compliances |
FCC Class B
ENERGY STAR certified RoHS CE Marked REACH FCC Compliant |
Certifications |
NOM
UL 1778 CSA certified |
Topology |
Line-interactive
|
Form factor |
Rackmount/Tower
|
Rack size |
1U
|
Package contents |
|
Input nominal voltage |
100 VAC/120 VAC/127 VAC
|
Nominal frequency |
50/60 Hz
|
Input frequency range |
50/60 Hz
|
Receptacle |
5-15R
|
Output nominal voltage |
120V
|
Electric current - max |
11.3A (100V); 12A (120V); 10.8A (127V)
|
Battery replacement |
RBC367-1U
|
Runtime at half load |
8 min
|
Noise level |
40 dBA maximum, front side 1m
|
Relative humidity |
0-95% non-condensing
|
Front Panel LCD Display |
Front panel LCD information and configuration screen offers detailed UPS and site power status and operating data, plus configuration of voltage, frequency, operating mode, alarm function and a variety of additional options (see manual)
|
Output Receptacles |
5-15R
|
Product Features |
Individually Controllable Load Banks
Emergency Power Off (EPO)/Remote On-Off (ROO) |
Product Highlights |
Maintains continuous 120V nominal output during brownouts as low as 90V
Optional WEBCARDLX offers 24/7 remote access for enhanced real-time management 5-15R outlets power and protect networking, telecom and other sensitive equipment Keeps AC power running during outages to allow time for file saves and safe shutdown Protects equipment against blackouts, brownouts, transient surges and line noise |
PowerAlert Software |
For local monitoring via the UPS’s built-in communication ports, download PowerAlert software at https://tripplite.eaton.com/products/power-alert
|
Nominal Output Voltage |
120V
|
Network Management Cards |
WEBCARDLXE
|
Network Management Cards Details |
Network management card optional
|
Output power factor |
0.76
|
Phase (input) |
Single-phase
|
Runtime at full load |
2 min. (1100W)
|
Communication interface |
USB (HID enabled)
Slot for SNMP / Web interface EPO (emergency power off) USB cabling included |
Battery Access |
Battery access panel
|
Emergency Power Off/Remote On-Off Details |
Phoenix-style connection supports Emergency Power Off and Remote ON/OFF functions.
|
Dc Voltage |
36
|
Operating Temperature Range |
32° to 104°F (0° to 40°C)
|
Communications Cable |
USB cabling included
|
Grounding Details |
Back panel grounding lug
|
Input Circuit Breakers |
15A
|
High Voltage Transfer to Battery Power |
162 VAC (120VAC/127VAC INPUT), 139 VAC (100VAC INPUT) +/- 5%
|
Low Voltage Transfer to Battery Power |
100V: 80VAC +/- 5% (HI sensitivity), 70VAC +/- 5%, (LO sensitivity), @120V: 89VAC +/- 5% (HI sensitivity), 70VAC+/- 5% (LO sensitivity), @127V: 93VAC+/- 5%, (HI sensitivity), 70VAC+/- 5%, (LO sensitivity)
|
Undervoltage Correction |
Voltage boost of 15% applies when input is 89V (HI Sensitivity) / 70V (LO sensitivity) to 102V @120V, 93V (HI sensitivity) / 70V (LO sensitivity) to 108V @127V, 80V (Hi sensitivity)/ 70V @100V; All voltage setpoints within ±5% tolerance
|
Application |
|
Switch configuration |
ON button controls UPS ON, Cold-start, Self-test, and menu functions. OFF button controls unit off, fault clearance, and menu functions. Alarm/Enter button control audible alarm state and menu confirmation.
|
AC suppression joule rating |
540
|
Housing material |
Steel
|
Output AC waveform (AC mode) |
Pure Sine wave
|
Output AC waveform (battery mode) |
Pure Sine wave
|
Output Capacity (kVA) |
1.44
|
Output Capacity (kW) |
1.1
|
Output Capacity (VA) |
1440
|
Output Capacity Details |
1440 VA @ 120VAC and 127VAC, 100VAC: 1080 VA
|
Operating Elevation |
0-3280 ft. (0-1000 m)
|
Primary UPS Depth (mm) |
554
|
Primary UPS Height (mm) |
44
|
Primary UPS Width (mm) |
440
|
AC Suppression Response Time |
Instantaneous
|
Audible Alarms |
Audible alarm indicates UPS startup, power-failure, warnings, and low-battery conditions
|
Battery Start Capability |
Cold-start operation supported
|
Cooling Method |
Fan
|
Battery Replacement Description |
Hot-swappable, user replaceable batteries
|
LED Indicators |
2 LEDs indicate AC output status (Green); UPS fault (Solid Red)/ UPS abnormal conditions (Flashing Red).
|
Frequency Rating Details |
Output is regulated to +/-0.05Hz when input frequency exceeds +/-5Hz of nominal.
|
Output Voltage Regulation (Line Mode) |
For 100V: 90VAC +/-5% -115VAC +/- 5% (78VAC +/- 5% -115VAC +/- 5%(@70VAC Input)) For 120V: 102VAC +/- 5% -139VAC +/- 5%, (78VAC +/- 5% -139VAC +/- 5%(@70VAC Input)), For 127V: 108VAC +/- 5% -145VAC +/- 5% (78VAC +/-5% -145VAC +/- 5% (@70VAC Input))
|
Output Voltage Regulation(Battery Mode) |
-10%, +6%
|
Overvoltage Correction |
Voltage reduction of 15% applies when input is 139V to 162V (120V), 145V to 162V (127V), 115V to 139V (100v); All voltage setpoints within ±5% tolerance
|
Rechargeable Battery |
6 Hours to 90%
|
Recommended Electrical Service |
15A 120V
|
Storage Temperature |
5° to 122°F (-15° to 50°C)
|
Included Mounting Accessory Description |
Included mounting brackets provide front-rail installation in 2 or 4 post racks, plus upright tower configurations
|
Network Monitoring Port Description |
Supports detailed monitoring of UPS and site power conditions
|
Nominal Voltage Details |
120V sinusoidal in line mode and 120V sinusoidal in battery mode
|
Voltage Regulation Description |
Automatic voltage regulation (AVR) maintains line power operation with input voltage as low as 70V @ 120V/127V/100V (±5%). Input voltage range of 70V to 139V @ 100V; 70V to 162V @ 120V / 127V settings
|
WatchDog Compatibility |
Supports Watchdog application, OS and hard-reboot restart options for remote applications
|
Maximum Input Amps |
12
|
Minimum Required Rack Depth (cm) |
63.5
|
Minimum Required Rack Depth (inches) |
25
|
UPS Input Cord Length (m) |
1.8
|
Power Mode Transfer Time |
6-8 ms typical ( < 10 ms max)
|
Connected Equipment Insurance |
$250,000 Ultimate Lifetime Insurance
|
EMI AC Noise Suppression |
EMI / RFI AC Noise Suppression
|
UPS Input Connection Type |
5-15P
|
High Availability UPS Features |
Automatic voltage regulation (AVR)
Remote management Hot swappable batteries Surge/noise protection Auto probe monitoring (requires WEBCARDLXE) |