Tripp Lite series SmartPro 3000VA 3000W 208V Line-Interactive Sine Wave UPS - 10 Outlets, Extended Run, Network Card Option, LCD, USB, DB9, 2U Rack/Tower
Product Name |
Eaton Tripp Lite series SmartPro UPS
|
Catalog Number |
SMX3000XLRT2UA
|
UPC |
037332181381
|
Product Length/Depth |
23.7 in
|
Product Height |
3.4 in
|
Product Width |
17.2 in
|
Product Weight |
69.9 lb
|
Compliances |
CE Marked
RoHS |
Certifications |
IEC/EN 62040-1
GoST-R |
Topology |
Line-interactive
|
Form factor |
Rackmount/Tower
|
Rack size |
2U
|
VA rating |
3000 VA
|
Wattage |
3000 W
|
Rack mounting kit |
Yes
|
Package contents |
|
Input connection |
C20
|
Input cord length |
6 ft
|
Input nominal voltage |
208V default (200/208/220/230/240V)
|
Nominal frequency |
50/60 Hz
|
Input frequency range |
50/60 Hz
|
Input power factor |
1
|
Receptacle |
|
Number of Outputs C13 |
8
|
Number of Outputs C19 |
2
|
Output waveform |
Sine wave
|
Output nominal voltage |
208V default (200/208/220/230/240V)
|
Electric current - max |
16A
|
Runtime graph |
View runtime graph
|
Battery replacement |
Pre-February 2024: RBC94-2U
Post February 2024: EBP-1617
|
Battery type |
Valve Regulated Lead Acid (VRLA)
|
Extended battery capability |
Extended runtime supported via optional 72VDC BP72VRM2U external battery packs only.
|
Runtime at half load |
9 min
|
User interface |
LCD display
|
Altitude |
Up to 10,000 ft (3000m) without de-rating
|
Noise level |
50 dBA maximum, front side 1m
|
Relative humidity |
20-95% non-condensing
|
Front Panel LCD Display |
Front panel LCD information and configuration screen offers detailed UPS and site power status and operating data, plus configuration of voltage, operating mode, alarm function and a variety of additional options (see manual for detailed LCD configuration and monitoring options)
|
Output Receptacles |
C19
C13 |
Product Features |
Expandable Runtime
Individually Controllable Load Banks Emergency Power Off (EPO)/Remote On-Off (ROO) |
Product Highlights |
Corrects brownouts and overvoltages without switching to battery power
Unity power factor ensures maximum power possible at each power rating Delivers stable sine wave output in battery mode compatible with sensitive equipment WEBCARDLXE network interface (sold separately) allows 24/7 remote access and control ENERGY STAR 2.0-certified to save electricity, lower costs and protect the environment |
PowerAlert Software |
For local monitoring via the UPS’s built-in communication ports, download PowerAlert Office software at https://tripplite.eaton.com/poweralert
|
Nominal Output Voltage |
208V default (200/208/220/230/240V)
|
Network Management Cards |
WEBCARDLXE
|
Network Management Cards Details |
Optional WEBCARDLXE only (Sold separately). Not compatible with WEBCARDLX.
|
Output power factor |
1
|
Output voltage range |
200V; 208V; 220V; 230V; 240V
|
Phase (input) |
Single-phase
|
Runtime at full load |
3 min. (3000W)
|
Communication interface |
USB (HID enabled)
Slot for SNMP / Web interface Contact closure DB9 Serial USB and DB9 serial cables included |
Battery Access |
Front panel battery access door
|
Typical Battery Runtime |
Expandable Runtime
|
Dc Voltage |
72
|
Operating Temperature Range |
32° to 104°F (0° to 40°C)
|
Communications Cable |
USB and DB9 cabling included
|
Grounding Details |
Rear panel grounding lug
|
Included Output Power Cables |
Set of 2x 6ft. C13 to C14 power cables included.
|
Optional Mounting Accessory Notes |
Optional 4POSTRAILKITWM enables installation in 4-post short-depth racks from 14.5 to 23.5 inches (368 to 597mm)
|
Load Management Receptacles |
Two switchable load banks: Load 1 (2x C13; C19), Load 2 (2x C13)
|
High Voltage Transfer to Battery Power |
294
|
Low Voltage Transfer to Battery Power |
160
|
Undervoltage Correction |
Increases incoming voltage between 162-184V (Normal Mode) or 151-184V (Extended Mode) by 15%
|
Network UPS Tools (NUT) Compatibility |
NUT compatible. See a full list of NUT compatible Tripp Lite UPS systems at https://networkupstools.org/stable-hcl.html?manufacturer=Tripp%20Lite
|
Application |
|
Switch configuration |
5 pushbutton switches control OFF / ON power status, ENTER, UP, and DOWN selection and ESC control functions
|
AC suppression joule rating |
175
|
Housing material |
Steel
|
Output AC waveform (AC mode) |
Pure Sine wave
|
Output AC waveform (battery mode) |
Pure Sine wave
|
Output Capacity (kVA) |
3
|
Output Capacity (kW) |
3
|
Output Capacity (VA) |
3000
|
Operating Elevation |
0-10000 ft. (0-3000 m)
|
Primary UPS Depth (mm) |
602
|
Primary UPS Height (mm) |
86
|
Primary UPS Width (mm) |
437
|
AC Suppression Response Time |
Instantaneous
|
Alarm Interface |
Press the ESC (Escape) button on the front panel display to silence the alarm. Check the alarm condition and perform the applicable action to resolve the condition. If the alarm status changes, the alarm beeps again, overriding the previous alarm silencing
|
Audible Alarms |
Audible alarm indicates UPS startup, power-failure, low-battery, overload, UPS fault and remote shutdown conditions
|
Battery Start Capability |
Cold-start operation supported
|
Cooling Method |
Fan
|
Battery Replacement Description |
Hot-swappable, replaceable batteries
|
Frequency Rating Details |
Automatic frequency selection
|
Minimum Required Rack Depth With External Battery Pack |
27
|
Minimum Required Rack Depth Without External Battery Pack |
27
|
Output Voltage Regulation (Line Mode) |
208V (-13%, +15%)
|
Output Voltage Regulation(Battery Mode) |
-10%, +6%
|
Overvoltage Correction |
Reduces incoming voltage between 265-294V (Normal Mode / Extended Mode) by 13%
|
Rechargeable Battery |
Less than 5 hours from 10 to 90% (typical, full load discharge)
|
Storage Temperature |
5° to 122°F (-15° to 50°C)
|
Included Mounting Accessory Description |
Included 4-post mounting kit enables installation in 4 post racks. Two ABS mounting stands enables the UPS to be configured in an upright tower orientation.
|
Input Connection Description |
IEC320-C20 input connection accepts included IEC C19 to L6-20P 6ft (1.8m) included input cordset. Also supports user supplied detachable C19 output cordsets to match country or site-specific power source connections.
|
Network Monitoring Port Description |
Network Card Optional. Not compatible with WEBCARDLX.
|
Nominal Voltage Details |
208v nominal inverter output voltage
|
Voltage Regulation Description |
Automatic voltage regulation (AVR) maintains line power operation with an input voltage range of 150 to 294
|
Maximum Input Amps |
16
|
Minimum Required Rack Depth (cm) |
68.58
|
Minimum Required Rack Depth (inches) |
27
|
UPS Power Module Dimensions |
3.4 x 17.2 x 23.7
|
Power Mode Transfer Time |
1-4ms for normal mode, >5ms for sensitive mode
|
Optional Accessories |
2 post rackmount (103007018-5591)
4 post rackmount short-depth (4POSTRAILKITWM) |
EMI AC Noise Suppression |
EMI / RFI AC Noise Suppression
|
UPS Input Connection Type |
C20 inlet
|
External Battery Pack Compatibility |
BP72VRM2U (limit 4)
|
Green Energy-Saving Features |
Greater than 95% efficiency - GREEN UPS
Individually controllable load banks Schedulable daily hours of economy mode operation |
High Availability UPS Features |
Remote management
Automatic voltage regulation (AVR) Surge/noise protection Expandable battery backup Hot swappable batteries Sine wave output |