Căutare informații
Descărcați documentul () din 20
Noi facem să funcționeze  lucrurile importante*

166407
Codul modelului: N3-4-320-S15-DC

Eaton Moeller series NZM - Molded Case Circuit Breaker. Switch-disconnector 4p 320A 1500VDC

General specifications

Product Name
Eaton Moeller series NZM switch-disconnector
Catalog Number
166407
EAN
4015081629152
Product Length/Depth
166 mm
Product Height
275 mm
Product Width
185 mm
Product Weight
7.3 kg
Compliances
RoHS conform
Certifications
IEC
IEC 60947-3
CCC
Model Code
N3-4-320-S15-DC

Delivery program

Application
  • Open areas
  • Utility buildings
Type
DC switch-disconnector
Circuit breaker frame type
N3
Number of poles
Four-pole
Amperage Rating
320 A
Features
Version as emergency stop installation
Version as maintenance-/service switch
Version as main switch
Motor drive optional
Remote operation with shunt releases / remote operator
Special features
  • Main switch characteristics including positive drive to IEC/EN 60204 and VDE 0113.
  • For DC switching, all 4 contacts must be connected in series. Refer to the information on jumper kit accessories.
  • Supplied as standard: Screw connection
  • box terminal optional.
  • When working with ungrounded systems (e.g., IT), the installation must ensure that a double ground fault will be impossible.
  • Switch can not be combined with plug-in/withdrawable units and/or connection on rear.
  • Lifespan, mechanical: of which max. 50 % trip by shunt/undervoltage release
  • Rated current = rated uninterrupted current: 320 A
  • Values for rated uninterrupted current at 65 °C include jumpers.

Technical Data - Electrical

Voltage rating
1500 V - 1500 V
Rated insulation voltage (Ui)
1500 V
Current rating (Iu) at 40°C with terminal jumpers
320 A
Current rating (Iu) at 65°C with terminal jumpers
320 A
Rated operational current
320 A (DC 22-A)
Rated short-time withstand current (t = 1 s)
6.6 kA
Amperage Rating
320 A
Electrical connection type of main circuit
Screw connection
Number of operations per hour - max
60
Handle type
Rocker lever
Utilization category
DC-22 A
Overvoltage category
III
Pollution degree
2

Technical Data - Mechanical

Mounting Method
Ground mounting
Fixed
Built-in device fixed built-in technique
Intermediate mounting
Distribution board installation
Mounting Method
Ground mounting
Fixed
Built-in device fixed built-in technique
Intermediate mounting
Distribution board installation
Degree of protection
IP20
Degree of protection (IP), front side
IP20
Number of auxiliary contacts (change-over contacts)
0
Number of auxiliary contacts (normally closed contacts)
0
Number of auxiliary contacts (normally open contacts)
0
Number of switches
1
Handle color
Black
Switch positions
I, +, 0
Special features
  • Main switch characteristics including positive drive to IEC/EN 60204 and VDE 0113.
  • For DC switching, all 4 contacts must be connected in series. Refer to the information on jumper kit accessories.
  • Supplied as standard: Screw connection
  • box terminal optional.
  • When working with ungrounded systems (e.g., IT), the installation must ensure that a double ground fault will be impossible.
  • Switch can not be combined with plug-in/withdrawable units and/or connection on rear.
  • Lifespan, mechanical: of which max. 50 % trip by shunt/undervoltage release
  • Rated current = rated uninterrupted current: 320 A
  • Values for rated uninterrupted current at 65 °C include jumpers.
Lifespan, mechanical
15000 operations

Technical Data - Mechanical - Terminals

Standard terminals
Screw terminal
Terminal capacity (aluminum solid conductor/cable)
16 mm² (1x) at tunnel terminal
Terminal capacity (aluminum stranded conductor/cable)
25 mm² - 185 mm² (1x) at tunnel terminal
Terminal capacity (copper busbar)
Max. 30 mm x 10 mm + 30 mm x 5 mm direct at switch rear-side connection
M10 at rear-side screw connection
Max. 10 mm x 50 mm (2x) at rear-side width extension
Min. 20 mm x 5 mm direct at switch rear-side connection
Terminal capacity (copper solid conductor/cable)
16 mm² (1x) direct at switch rear-side connection
16 mm² (2x) direct at switch rear-side connection
16 mm² (2x) at box terminal
Terminal capacity (copper stranded conductor/cable)
50 mm² - 240 mm² (1x) at 2-hole tunnel terminal
25 mm² - 185 mm² (1x) at tunnel terminal
25 mm² - 120 mm² (2x) at box terminal
35 mm² - 240 mm² (1x) at box terminal
25 mm² - 240 mm² (1x) direct at switch rear-side connection
25 mm² - 240 mm² (2x) direct at switch rear-side connection
50 mm² - 240 mm² (2x) at 2-hole tunnel terminal
Terminal capacity (copper strip)
Max. 8 segments of 24 mm x 1 mm (2x) at box terminal
Max. 10 segments of 32 mm x 1 mm + 5 segments of 32 mm x 1 mm at rear-side connection (punched)
Min. 6 segments of 16 mm x 0.8 mm at rear-side connection (punched)
Max. 10 segments of 24 mm x 1 mm + 5 segments of 24 mm x 1 mm
10 segments of 50 mm x 1 mm (2x) at rear-side width extension
Min. 6 segments of 16 mm x 0.8 mm at box terminal

Design verification as per IEC/EN 61439 - technical data

Rated operational current for specified heat dissipation (In)
320 A
Equipment heat dissipation, current-dependent
62 W
Ambient operating temperature - min
-25 °C
Ambient operating temperature - max
70 °C
Ambient storage temperature - min
-40 °C
Ambient storage temperature - max
70 °C

Design verification as per IEC/EN 61439

10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard's requirements.
10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of assemblies
Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances
Meets the product standard's requirements.
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9.2 Power-frequency electric strength
Is the panel builder's responsibility.
10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material
Is the panel builder's responsibility.
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.

Additional information

Functions
Voltage release optional
Photovoltaic applications
Interlockable
Disconnectors/main switches

Exportați specificațiile produsului

Serial Number Verified :
Authenticated:
The product is verified as being authentic; however, this does not guarantee the condition or fit for purpose of the product.

Autentificare produs

Intrpduceți numărul de serie de 16-17 cifre
Numărul de serie pe care l-ați introdus nu trebuie să conțină caractere speciale. Numărul de serie pe care l-ați introdus nu este corect și ar trebui să conțină 16 sau 17 cifre. Numărul de serie pe care l-ați introdus nu a fost găsit. Vă rugăm să încercați din nou sau raportați o problemă pentru asistență suplimentară. Numărul de serie pe care l-ați introdus nu se potrivește produsului. Verificați numărul de serie al produsului și încercați din nou. Click aici pentru a naviga pe pagina produsului pentru numărul de serie pe care l-ați introdus Numărul de serie este cunoscut de către Eaton ca fiind suspect, vă rugăm să încercați din nou sau raportați o problemă pentru asistență suplimentară.
Număr de serie
Resetare Numărul de serie este cunoscut de către Eaton ca fiind suspect, vă rugăm să încercați din nou sau raportați o problemă pentru asistență suplimentară. Numărul de serie nu este recunoscut de către Eaton și este invalid. Vă rugăm să utilizați acest formular pentru raportați o problemă pentru asistență suplimentară.
Introduceți un cod de autentificare de 6 cifre
Produsul pe care l-ați introdus este suspect! Vă rugăm să încercați din nou sau raportați o problemă pentru asistență suplimentară. Codul de autentificare pe care l-ați introdus nu se potrivește înregistrărilor noastre pentru acest număr de serie. Vă rugăm să încercați din nou, sau raportați o problemă pentru asistență suplimentară. Cod de autentificare invalid. Lungimea trebuie să fie de 6 caractere raportați o problemă pentru asistență suplimentară. Codul de autentificare este necesar raportați o problemă pentru asistență suplimentară.
A completa provocarea Captcha înainte de autentificare.
Contactați-ne pentru a raporta problema
x
Raportați o problemă
Vă rugăm să introduceți numele dumneavoastră complet.
x
Vă mulțiumim, problema dumneavoastră a fost trimisă, iar echipa noastră de produse vă va contacta în curând.
Notă: Dacă fișierul(e) lipsesc din descărcarea .zip, atunci tipul de fișier nu este suportat pentru descărcarea în masă.