Reset
Eaton Moeller series NZMN2 PXR20 circuit breaker, 160 A, 3-pole, box terminal, UL/CSA
Product Name |
Eaton Moeller series NZM molded case circuit breaker electronic
|
Catalog Number |
192518
|
EAN |
4015081932467
|
Product Length/Depth |
149 mm
|
Product Height |
195 mm
|
Product Width |
105 mm
|
Product Weight |
2.345 kg
|
Compliances |
RoHS conform
|
Certifications |
UL 489
CSA-C22.2 No. 5-09 CSA certified CSA (File No. 22086) UL (Category Control Number DIVQ) Specially designed for North America IEC CE marking UL listed UL (File No. E31593) IEC 60947-2 UL/CSA CSA (Class No. 1432-01) |
Model Code |
NZMN2-VX160-BT-NA
|
Voltage rating |
690 V - 690 V
|
Rated operating voltage Ue (UL) - max |
600 V
|
Amperage Rating |
160 A
|
Instantaneous current setting (Ii) - min |
2 A
|
Instantaneous current setting (Ii) - max |
18 A
|
Overload current setting (Ir) - min |
64 A
|
Overload current setting (Ir) - max |
160 A
|
Short delay current setting (Isd) - min |
320 A
|
Short delay current setting (Isd) - max |
1600 A
|
Short-circuit release delayed setting - min |
128 A
|
Short-circuit release delayed setting - max |
1600 A
|
Short-circuit release non-delayed setting - min |
320 A
|
Short-circuit release non-delayed setting - max |
2880 A
|
Rated short-circuit breaking capacity Ics (IEC/EN 60947) at 400/415 V, 50/60 Hz |
50 kA
|
Electrical connection type of main circuit |
Frame clamp
|
Handle type |
Rocker lever
|
Amperage Rating |
160 A
|
Instantaneous current setting (Ii) - min |
2 A
|
Instantaneous current setting (Ii) - max |
18 A
|
Overload current setting (Ir) - min |
64 A
|
Overload current setting (Ir) - max |
160 A
|
Short delay current setting (Isd) - min |
320 A
|
Short delay current setting (Isd) - max |
1600 A
|
Short-circuit release delayed setting - min |
128 A
|
Short-circuit release delayed setting - max |
1600 A
|
Short-circuit release non-delayed setting - min |
320 A
|
Short-circuit release non-delayed setting - max |
2880 A
|
Rated short-circuit breaking capacity Ics (IEC/EN 60947) at 400/415 V, 50/60 Hz |
50 kA
|
Electrical connection type of main circuit |
Frame clamp
|
Handle type |
Rocker lever
|
Mounting Method |
Fixed
DIN rail (top hat rail) mounting optional Built-in device fixed built-in technique |
Degree of protection |
IP20
|
Protection against direct contact |
Finger and back-of-hand proof to DIN EN 50274/VDE 0106 part 110
|
Number of auxiliary contacts (change-over contacts) |
0
|
Number of auxiliary contacts (normally closed contacts) |
0
|
Number of auxiliary contacts (normally open contacts) |
0
|
Position of connection for main current circuit |
Front side
|