Eaton Moeller® series TM Control circuit switches, TM, 10 A, flush mounting, Contacts: 3, STOP function, With black rotary handle and locking ring, Lockable in the 0 (Off) position
| Product Name |
Eaton Moeller® series TM Accessory Control circuit isolator
|
| Catalog Number |
210955
|
| EAN |
4015082109554
|
| Product Length/Depth |
89 mm
|
| Product Height |
48 mm
|
| Product Width |
30 mm
|
| Product Weight |
0.059 kg
|
| Certifications |
UL Category Control No.: NLRV
UL 508 CSA CSA-C22.2 No. 94 UL File No.: E36332 CE Certified by UL for use in Canada CSA-C22.2 No. 14-05 IEC/EN 60947-3 IEC/EN 60947-5-1 UL IEC/EN 60947 UL report applies to both US and Canada VDE 0660 |
| Catalog Notes |
up to 250 V AC per contact
|
| Model Code |
TM-2-8292/E/SVB-SW
|
| Features |
Version as main switch
|
| Fitted with: |
Black rotary handle and locking ring
|
| Functions |
STOP function
Interlockable |
| Locking facility |
Lockable in the 0 (Off) position
|
| Number of poles |
3
|
| Degree of protection |
NEMA 12
|
| Degree of protection (front side) |
IP65
|
| Lifespan, mechanical |
1,000,000 Operations
|
| Mounting method |
Flush mounting
|
| Mounting position |
As required
|
| Number of contact units |
2
|
| Operating frequency |
1200 Operations/h
|
| Overvoltage category |
III
|
| Pollution degree |
3
|
| Product Category |
Control switches
|
| Product Category |
Control switches
|
| Rated impulse withstand voltage (Uimp) |
4000 V AC
|
| Suitable for |
Front mounting 4-hole
|
| Switching angle |
90 °
|
| Type |
Control circuit switch
|
| Ambient operating temperature - min |
-25 °C
|
| Ambient operating temperature - max |
50 °C
|
| Climatic proofing |
Damp heat, cyclic, to IEC 60068-2-30
Damp heat, constant, to IEC 60068-2-78 |
| Terminal capacity |
2 x 1.5 mm², flexible
2 x 1.0 mm², flexible with ferrules to DIN 46228 2 x 1,5 mm², solid or stranded 1 x 1.5 mm², flexible 1 x 1.5 mm², solid or stranded 1 x 1.0 mm², flexible with ferrules to DIN 46228 14 AWG, solid or flexible with ferrule |
| Screw size |
M2.5, Terminal screw
|
| Tightening torque |
0.4 Nm, Screw terminals
3.5 lb-in, Screw terminals |
| Rated operational power at AC-3, 380/400 V, 50 Hz |
0 kW
|
| Rated operational power at AC-23A, 400 V, 50 Hz |
3 kW
|
| Rated operational voltage (Ue) at AC - max |
500 V
|
| Rated uninterrupted current (Iu) |
10 A
|
| Uninterrupted current |
Rated uninterrupted current Iu is specified for max. cross-section.
|
| Rated conditional short-circuit current (Iq) |
0 kA
|
| Rated short-time withstand current (Icw) |
0 kA
|
| Short-circuit protection rating |
10 A gG/gL, Fuse, Contacts
|
| Switching capacity (main contacts, general use) |
10 A, Rated uninterrupted current max. (UL/CSA)
|
| Switching capacity (auxiliary contacts, general use) |
10A, IU, (UL/CSA)
|
| Switching capacity (auxiliary contacts, pilot duty) |
A300 (UL/CSA)
|
| Assigned motor power at 115/120 V, 60 Hz, 1-phase |
0.33 HP
|
| Assigned motor power at 115/120 V, 60 Hz, 3-phase |
0.75 HP
|
| Assigned motor power at 230/240 V, 60 Hz, 1-phase |
0.75 HP
|
| Assigned motor power at 230/240 V, 60 Hz, 3-phase |
1 HP
|
| Assigned motor power at 277 V, 60 Hz, 1-phase |
0.75 HP
|
| Control circuit reliability |
1 failure per 100,000 switching operations statistically determined, at 24 V DC, 10 mA)
|
| Number of auxiliary contacts (change-over contacts) |
0
|
| Number of auxiliary contacts (normally closed contacts) |
0
|
| Number of auxiliary contacts (normally open contacts) |
0
|
| Actuator color |
Black
|
| Actuator type |
Door coupling rotary drive
|
| Equipment heat dissipation, current-dependent Pvid |
0 W
|
| Heat dissipation capacity Pdiss |
0 W
|
| Heat dissipation per pole, current-dependent Pvid |
0.15 W
|
| Rated operational current for specified heat dissipation (In) |
10 A
|
| Static heat dissipation, non-current-dependent Pvs |
0 W
|
| 10.2.2 Corrosion resistance |
Meets the product standard's requirements.
|
| 10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard's requirements.
|
| 10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard's requirements.
|
| 10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects |
Meets the product standard's requirements.
|
| 10.2.4 Resistance to ultra-violet (UV) radiation |
UV resistance only in connection with protective shield.
|
| 10.2.5 Lifting |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.2.6 Mechanical impact |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.2.7 Inscriptions |
Meets the product standard's requirements.
|
| 10.3 Degree of protection of assemblies |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.4 Clearances and creepage distances |
Meets the product standard's requirements.
|
| 10.5 Protection against electric shock |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.6 Incorporation of switching devices and components |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.7 Internal electrical circuits and connections |
Is the panel builder's responsibility.
|
| 10.8 Connections for external conductors |
Is the panel builder's responsibility.
|
| 10.9.2 Power-frequency electric strength |
Is the panel builder's responsibility.
|
| 10.9.3 Impulse withstand voltage |
Is the panel builder's responsibility.
|
| 10.9.4 Testing of enclosures made of insulating material |
Is the panel builder's responsibility.
|
| 10.10 Temperature rise |
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
|
| 10.11 Short-circuit rating |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
| 10.12 Electromagnetic compatibility |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
| 10.13 Mechanical function |
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
|