Eaton EC4P Compact PLC, 24 V DC, 12DI(of 4AI), 6DO(R), CAN, display
Product Name |
Eaton EC4P Compact PLC
|
Catalog Number |
106393
|
Model Code |
EC4P-221-MRXD1
|
EAN |
4015081061631
|
Product Length/Depth |
72 mm
|
Product Height |
90 mm
|
Product Width |
107.5 mm
|
Product Weight |
0.374 kg
|
Certifications |
UL File No.: E135462
UL508 CSA Class No.: 2252-01 CSA File No.: 012528 UL Category Control No.: NRAQ CE CSA-C22.2 No. 0-M CSA-C22.2 No. 142-M CSA IEC/EN 61000-4-2, Level 3 UL |
Catalog Notes |
Expandable: Inputs/outputs and bus systems
|
Global Catalog |
106393
|
Features |
190 received bytes in a block (PRG interface RS232, Master mode)
Asynchronous, cyclic, acyclic PDO types (operating modes of the slave) |
Air discharge |
8 kV
|
10.10 Temperature rise |
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
|
10.11 Short-circuit rating |
Is the panel builder's responsibility.
|
10.12 Electromagnetic compatibility |
Is the panel builder's responsibility.
|
10.13 Mechanical function |
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
|
10.2.2 Corrosion resistance |
Meets the product standard's requirements.
|
10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard's requirements.
|
10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard's requirements.
|
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects |
Meets the product standard's requirements.
|
10.2.4 Resistance to ultra-violet (UV) radiation |
Meets the product standard's requirements.
|
10.2.5 Lifting |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.6 Mechanical impact |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.7 Inscriptions |
Meets the product standard's requirements.
|
10.3 Degree of protection of assemblies |
Meets the product standard's requirements.
|
10.4 Clearances and creepage distances |
Meets the product standard's requirements.
|
10.5 Protection against electric shock |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.6 Incorporation of switching devices and components |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.7 Internal electrical circuits and connections |
Is the panel builder's responsibility.
|
10.8 Connections for external conductors |
Is the panel builder's responsibility.
|
10.9.2 Power-frequency electric strength |
Is the panel builder's responsibility.
|
10.9.3 Impulse withstand voltage |
Is the panel builder's responsibility.
|
10.9.4 Testing of enclosures made of insulating material |
Is the panel builder's responsibility.
|
Fitted with: |
Power supply
Digital input module Engineering software Keypad Control unit easyNet/CANopen® on board Digital output module Other components Display Analog input module Communication module Memory unit Monitor Function module Libraries Documentation Basic device |
Pollution degree |
2
|
Accuracy |
± 3 %, of actual value, two devices (Analog Inputs)
± 5 s/day (± 0.5 h⁄year), Real-time clock, normally ± 2, (I7, I8, I11, I12) ± 0.12 V, of actual value, within a single device (Analog Inputs) |
Burst impulse |
2 kV, Supply cable
2 kV, Signal cable According to IEC/EN 61000-4-4, level 3 |
Rated impulse withstand voltage (Uimp) |
6 kV (contact-coil)
|
Utilization category |
B 300 Light Pilot Duty, UL/CSA Control Circuit Rating Codes AC
R 300 Light Pilot Duty, UL/CSA Control Circuit Rating Codes DC |
Air pressure |
1080 hPa (operation)
|
Bus termination |
EASY-NT-R plug (incl. bus terminating resistor 120 Ω),first and last station, CANopen®
|
Environmental conditions |
Condensation: prevent with appropriate measures
Clearance in air and creepage distances according to EN 50178, UL 508, CSA C22.2, No. 142 |
Indication |
LCD-display used as status indication of Digital inputs 24 V DC
|
Input |
Voltage (DC)
|
Cable length |
30 m, screened, Analog inputs
100 m, unshielded, Digital inputs 24 V DC |
Mounting method |
Top-hat rail fixing (according to IEC/EN 60715, 35 mm)
Screw fixing using fixing brackets ZB4-101-GF1 (accessories) |
Number of outputs |
8 Transistor Outputs
Relay outputs in groups of 1 6 (relay outputs) |
Character formats |
8E1, 8O1, 8N1, 8N2, 7E2, 7O2, 7N2, 7E1, PRG interface RS232, Master mode
|
Screwdriver size |
3.5 x 0.8 mm, Terminal screw
|
Mounting position |
Horizontal
Vertical |
Contact discharge |
6 kV, Electrostatic discharge (ESD)
|
Overvoltage category |
II
|
Connection type |
RJ45, PRG Interface RS232
RJ45, Ethernet 2 x RJ45, 8 pole, CANopen® |
Constant acceleration |
2 g, 57 - 150 Hz, according to IEC/EN 60068-2-6, Vibrations
|
Constant amplitude |
0,15 mm, 10 - 57 Hz, according to IEC/EN 60068-2-6, Vibrations
|
Surge rating |
0.5 kV, Supply cables, symmetrical, EASY…DC, power pulses (Surge), EMC
According to IEC/EN 61000-4-5, power pulses (Surge), EMC 2 kV, Supply cables, symmetrical, EASY...AC, power pulses (Surge), EMC |
Terminal capacity (flexible with ferrule AWG) |
22 - 12
|
Conversions |
Each CPU cycle, Analog inputs
|
Electromagnetic fields |
10 V/m (according to IEC EN 61000-4-3)
|
Terminal capacity (solid AWG) |
22 - 12
|
Number of inputs (analog) |
4 (I7, I8, I11, I12)
|
Cycle time |
< 0.3 ms, for 1 k of instructions (Bit, Byte), CPU
|
Number of modules |
Max. 126 (slaves)
|
Drop and topple |
50 mm Drop height, Drop to IEC/EN 60068-2-31
|
Immunity to line-conducted interference |
10 V (according to IEC/EN 61000-4-6)
|
Radio interference class |
Class B (EN 55011)
Class B (EN 55022) |
Data transfer rate |
20 kBit/s at 700 m, CANopen®
9.6 kBit/s, PRG interface RS232, Master mode 19.2 kBit/s, PRG interface RS232, Master mode 57.6 kBit/s, PRG interface RS232, Master mode 250 kBit/s at 60 m, CANopen® 125 kBit/s at 125 m, CANopen® 0.6 kBit/s, PRG interface RS232, Master mode 10 kBit/s at 1000 m , CANopen® 38.4 kBit/s, PRG interface RS232, Master mode 10 MBit/s, 100 m, Ethernet 50 kBit/s at 300 m, CANopen® 4.8 kBit/s, PRG interface RS232, Master mode 1.2 kBit/s, PRG interface RS232, Master mode 0.3 kBit/s, PRG interface RS232, Master mode 2.4 kBit/s, PRG interface RS232, Master mode 500 kBit/s at 25 m, CANopen® |
Relative humidity |
5 - 95 % (non-condensing)
|
Degree of protection |
IP20
|
Safe isolation |
300 V AC, Between two contacts, According to EN 50178
300 V AC, Between coil and contact, According to EN 50178 |
Delay time |
0.25 ms typ., Digital inputs 24 DC (I5 - I12), Delay time from 0 to 1
0.02 ms typ., Digital inputs 24 DC (I1 - I4), Delay time from 0 to 1 |
Residual ripple |
≤ 5 %
|
Rapid counter inputs |
≤ 20 m (cable length, screened)
50 kHz, Counter frequency Square (pulse shape) 2 (I1, I2) at 16 Bit or 1 (I1) at 32 Bit 16/32 Bit (value range) |
Insulation resistance |
According to EN 50178
|
Functions |
Building blocks
|
Heat dissipation |
3.4 W
|
Supply voltage at DC - max |
24 VDC
|
Resolution |
|
Incremental counter |
Value range: 32 Bit
Counter frequency: ≤ 40 kHz Input for reference switch: I4 Reference input: I3 Counter inputs: I1, I2 Signal offset: 90° Number of counter inputs: 1 (I1, I2, I3, I4) Pulse shape: Square |
Station |
To DS 301 V4, Control contact rated current, Mode slave, Interfaces
|
Input current |
1 mA (Analog inputs)
3.3 mA (I1 - I6, at 24 V DC, at signal 1) 140 mA 2.2 mA (I7 - I8, at 24 V DC, at signal 1) 2.2 mA (I11 - I12, at 24 V DC, at signal 1) 3.3 mA (I9 - I10, at 24 V DC, at signal 1) |
Input impedance |
11.2 kΩ
|
Input voltage |
Signal 1: > 15 V DC (I1 - I6, I9 - I10, Digital inputs, 24 V DC)
Signal 0: < 8 V DC (I7 - I8, I11 - I12, Digital inputs, 24 V DC) Signal 0: < 5 V DC (I1 - I6, I9 - I10, Digital inputs, 24 V DC) Signal 1: > 8 V DC (I7 - I8, I11 - I12, Digital inputs, 24 V DC) |
Processor |
Infineon XC161
|
Shock resistance |
15 g, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 11 ms, 18 Impacts
|
Inscription |
Individual inscription possible with EC4-COMBINATION-*
|
Rated breaking capacity |
200000 Operations at DC-13, 24 V DC, 1 A (500 Ops./h)
300000 Operations at AC-15, 250 V AC, 3 A (600 Ops./h) |
Lifespan, electrical |
25,000 Operations (Fluorescent lamp load 1 x 58 W at 230/240 V AC, conventional, compensated)
25,000 Operations (Fluorescent lamp load 10 x 58 W at 230/240 V AC, uncompensated) 25,000 Operations (Fluorescent lamp load 10 x 58 W at 230/240 V AC, with upstream electrical device) 25,000 Operations (Filament bulb load at 1000 W, 230/240 V AC) 25,000 Operations (Filament bulb load at 500 W, 115/120 V AC) |
Signal range |
0 - 10 V DC, Analog inputs
|
Lifespan, mechanical |
10,000,000 Operations (Relay outputs)
10,000,000 Operations |
Making/breaking capacity |
28/28 VA (DC, at R 300)
3600/360 VA (AC, at B 300) |
Memory |
16 kByte Marker Memory
256 kByte Program memory code 4 kByte Input Memory 8 kByte Retain Memory 14 segments of 16 kByte Program memory data 4 kByte Output Memory |
Number of bytes |
190 transmission bytes (in a block)
|
Number of inputs (digital) |
12 (24 V DC)
4 (I7, I8, I11, I12, can also be used as analog inputs) 12 4 (can also be used as analog inputs) |
Parallel switching |
Not permitted
|
Voltage dips |
According to EN 61131-2
≤ 10 ms |
Uninterrupted current |
8 A DC, at 24 V DC (UL/CSA)
1 A DC, at R 300 (UL/CSA) 5 A AC, max. thermal continuous current cos ϕ = 1 at B 300 (UL/CSA) 10 A AC, at 240 V AC (UL/CSA) |
Potential isolation |
Between Digital inputs 24 V DC and Outputs: yes
Between Digital inputs 24 V DC and network easyNet, easyLink Between Relay outputs and Power supply: yes Between Analog inputs and Outputs: yes Between Analog inputs and Interface/memory card: no In groups (Relay outputs) Safe isolation according to EN 50178: 300 V AC (Relay outputs) Basic isolation: 600 V AC (Relay outputs) Between Relay outputs and Inputs: yes |
Protection of an output relay |
Miniature circuit-breaker B16 or fuse 8 A (slow)
|
Rated operational voltage |
20.4 - 28.8 V DC
24 V DC (-15 %/+ 20 % - power supply) |
Relay output |
> 500 mA (Recommended for load: 12 V AC/DC)
|
Short-circuit protection |
16 A, Short-circuit-proof cos ϕ = 0.5 to 0.7, characteristic B16 at 900 A, Contacts, Relay outputs
16 A, Short-circuit-proof cos ϕ = 1, characteristic B16 at 600 A, Contacts, Relay outputs |
Terminal capacity (flexible with ferrule) |
0.2/2.5 mm²
|
Switching frequency |
10 Hz, Relay outputs
2 Hz, Resistive load/lamp load, Relay outputs 0.5 Hz, Inductive load, Relay outputs |
Terminal capacity (solid) |
0.2/4 mm²
|
Tightening torque |
0.6 Nm
|
Write cycles of the retentive memory |
10,000,000,000 read-write cycles
|
Ambient operating temperature - max |
55 °C
|
Ambient operating temperature - min |
-25 °C
|
Ambient storage temperature - max |
70 °C
|
Ambient storage temperature - min |
-40 °C
|
Conventional thermal current Ith of auxiliary contacts (1-pole, open) |
8 A
|
Display temperature - max |
55 °C
|
Display temperature - min |
0 °C
|
Equipment heat dissipation, current-dependent Pvid |
0 W
|
Heat dissipation capacity Pdiss |
0 W
|
Heat dissipation per pole, current-dependent Pvid |
0 W
|
Height of fall (IEC/EN 60068-2-32) - max |
1 m
|
Rated insulation voltage (Ui) |
250 V
|
Rated operational current for specified heat dissipation (In) |
0 A
|
Rated operational voltage (Ue) at AC - max |
300 V
|
Rated operational voltage (Ue) at DC - max |
300 V
|
Static heat dissipation, non-current-dependent Pvs |
3.4 W
|