Eaton Moeller series Power Defense - Molded Case Circuit Breaker. Circuit-breaker LZM, 4 p, 160A, B2-4-A160-I
Product Name |
Eaton Moeller series Power Defense molded case circuit-breaker
|
Catalog Number |
116431
|
Model Code |
LZMB2-4-A160-I
|
EAN |
4015081161737
|
Product Length/Depth |
142 mm
|
Product Height |
185 mm
|
Product Width |
140 mm
|
Product Weight |
3.5 kg
|
Compliances |
RoHS conform
|
Certifications |
VDE 0660
IEC IEC/EN 60947 |
Circuit breaker frame type |
LZM2
|
Application |
Use in unearthed supply systems at 440 V
|
Amperage Rating |
160 A
|
Number of poles |
Four-pole
|
Voltage rating |
440 V - 440 V
|
Rated insulation voltage (Ui) |
690 V AC
|
Rated impulse withstand voltage (Uimp) at auxiliary contacts |
6000 V
|
Rated impulse withstand voltage (Uimp) at main contacts |
8000 V
|
Rated operational current |
160 A (415 V AC-3, making and breaking capacity)
300 A (380/400 V AC-1, making and breaking capacity) 300 A (415 V AC-1, making and breaking capacity) 160 A (660-690 V AC-3, making and breaking capacity) |
Current rating of neutral conductor |
200% of phase conductor
|
Instantaneous current setting (Ii) - min |
960 A
|
Instantaneous current setting (Ii) - max |
1600 A
|
Overload current setting (Ir) |
125 A - 160 A
|
Overload current setting (Ir) - min |
125 A
|
Overload current setting (Ir) - max |
160 A
|
Short delay current setting (Isd) - min |
0 A
|
Short delay current setting (Isd) - max |
0 A
|
Short-circuit release non-delayed setting - min |
960 A
|
Short-circuit release non-delayed setting - max |
1600 A
|
Rated short-circuit breaking capacity Ics (IEC/EN 60947) at 230 V, 50/60 Hz |
30 kA
|
Rated short-circuit breaking capacity Ics (IEC/EN 60947) at 400/415 V, 50/60 Hz |
25 kA
|
Rated short-circuit breaking capacity Ics (IEC/EN 60947) at 440 V, 50/60 Hz |
18.5 kA
|
Rated short-circuit making capacity Icm at 240 V, 50/60 Hz |
63 kA
|
Rated short-circuit making capacity Icm at 400/415 V, 50/60 Hz |
53 kA
|
Rated short-circuit making capacity Icm at 440 V, 50/60 Hz |
53 kA
|
Short-circuit total breaktime |
< 10 ms
|
Electrical connection type of main circuit |
Screw connection
|
Isolation |
500 V AC (between auxiliary contacts and main contacts)
300 V AC (between the auxiliary contacts) |
Overvoltage category |
III
|
Utilization category |
A (IEC/EN 60947-2)
|
Pollution degree |
3
|
Lifespan, electrical |
6500 operations at 415 V AC-3
10000 operations at 400 V AC-1 10000 operations at 415 V AC-1 |
Type |
Circuit breaker
|
Release system |
Thermomagnetic release
|
Mounting Method |
Fixed
Built-in device fixed built-in technique DIN rail (top hat rail) mounting optional |
Degree of protection |
In the area of the HMI devices: IP20 (basic protection type)
IP20 |
Degree of protection (IP), front side |
IP66 (with door coupling rotary handle)
IP40 (with insulating surround) |
Degree of protection (terminations) |
IP00 (terminations, phase isolator and band terminal)
IP10 (tunnel terminal) |
Protection against direct contact |
Finger and back-of-hand proof to DIN EN 50274/VDE 0106 part 110
|
Shock resistance |
20 g (half-sinusoidal shock 20 ms)
|
Number of auxiliary contacts (change-over contacts) |
0
|
Number of auxiliary contacts (normally closed contacts) |
0
|
Number of auxiliary contacts (normally open contacts) |
0
|
Number of operations per hour - max |
120
|
Handle type |
Rocker lever
|
Position of connection for main current circuit |
Front side
|
Direction of incoming supply |
As required
|
Standard terminals |
Screw terminal
|
Terminal capacity (control cable) |
0.75 mm² - 2.5 mm² (1x)
0.75 mm² - 1.5 mm² (2x) |
Terminal capacity (aluminum solid conductor/cable) |
16 mm² (1x) at tunnel terminal
|
Terminal capacity (copper busbar) |
M8 at rear-side screw connection
Min. 16 mm x 5 mm direct at switch rear-side connection Max. 20 mm x 5 mm direct at switch rear-side connection |
Terminal capacity (copper solid conductor/cable) |
4 mm² - 16 mm² (2x) direct at switch rear-side connection
16 mm² (1x) at tunnel terminal 4 mm² - 16 mm² (1x) direct at switch rear-side connection 4 mm² - 16 mm² (2x) at box terminal 4 mm² - 16 mm² (1x) at box terminal |
Terminal capacity (copper stranded conductor/cable) |
25 mm² - 70 mm² (2x) direct at switch rear-side connection
25 mm² - 70 mm² (2x) at box terminal 25 mm² - 185 mm² (1x) at tunnel terminal 25 mm² - 185 mm² (1x) direct at switch rear-side connection 25 mm² - 185 mm² (1x) at box terminal |
Terminal capacity (copper strip) |
Min. 2 segements of 16 mm x 0.8 mm at rear-side connection (punched)
Max. 10 segments of 16 mm x 0.8 mm at rear-side connection (punched) Max. 10 segments of 16 mm x 0.8 mm at box terminal Min. 2 segments of 9 mm x 0.8 mm at box terminal |
Climatic proofing |
Damp heat, constant, to IEC 60068-2-78
Damp heat, cyclic, to IEC 60068-2-30 |
Lifespan, mechanical |
20000 operations
|
Rated operational current for specified heat dissipation (In) |
160 A
|
Equipment heat dissipation, current-dependent |
38.4 W
|
10.2.2 Corrosion resistance |
Meets the product standard's requirements.
|
10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard's requirements.
|
10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard's requirements.
|
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects |
Meets the product standard's requirements.
|
10.2.4 Resistance to ultra-violet (UV) radiation |
Meets the product standard's requirements.
|
10.2.5 Lifting |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.6 Mechanical impact |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.7 Inscriptions |
Meets the product standard's requirements.
|
10.3 Degree of protection of assemblies |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.4 Clearances and creepage distances |
Meets the product standard's requirements.
|
10.5 Protection against electric shock |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.6 Incorporation of switching devices and components |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.7 Internal electrical circuits and connections |
Is the panel builder's responsibility.
|
10.8 Connections for external conductors |
Is the panel builder's responsibility.
|
10.9.2 Power-frequency electric strength |
Is the panel builder's responsibility.
|
10.9.3 Impulse withstand voltage |
Is the panel builder's responsibility.
|
10.9.4 Testing of enclosures made of insulating material |
Is the panel builder's responsibility.
|
10.10 Temperature rise |
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
|
10.11 Short-circuit rating |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
10.12 Electromagnetic compatibility |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
10.13 Mechanical function |
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
|
Features |
Protection unit
Motor drive optional |
Functions |
System and cable protection
|
Special features |
|