Eaton S811 Soft starter, 850 A, 200 - 690 V AC, Us= 24 V DC, with control unit and pump algorithm, for 690-V grids, Frame size V
Product Name |
Eaton S811 Soft starter
|
Catalog Number |
169010
|
Model Code |
S811+V85V3S
|
EAN |
4015081655038
|
Product Length/Depth |
187.8 mm
|
Product Height |
420.8 mm
|
Product Width |
280.6 mm
|
Product Weight |
41.4 kg
|
Certifications |
CSA
UL 508 C-Tick CCC UL File No.: E202571 IEC/EN 60947-4-2 CE CSA22.2-14-1995 UL UL Category Control No.: NMFT GB14048 |
Global Catalog |
169010
|
Type |
Soft starter for three-phase loads, with control unit and pump algorithm, for 690-V grids
|
10.10 Temperature rise |
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
|
10.11 Short-circuit rating |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
10.12 Electromagnetic compatibility |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
10.13 Mechanical function |
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
|
10.2.2 Corrosion resistance |
Meets the product standard's requirements.
|
10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard's requirements.
|
10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard's requirements.
|
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects |
Meets the product standard's requirements.
|
10.2.4 Resistance to ultra-violet (UV) radiation |
Meets the product standard's requirements.
|
10.2.5 Lifting |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.6 Mechanical impact |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.7 Inscriptions |
Meets the product standard's requirements.
|
10.3 Degree of protection of assemblies |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.4 Clearances and creepage distances |
Meets the product standard's requirements.
|
10.5 Protection against electric shock |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.6 Incorporation of switching devices and components |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.7 Internal electrical circuits and connections |
Is the panel builder's responsibility.
|
10.8 Connections for external conductors |
Is the panel builder's responsibility.
|
10.9.2 Power-frequency electric strength |
Is the panel builder's responsibility.
|
10.9.3 Impulse withstand voltage |
Is the panel builder's responsibility.
|
10.9.4 Testing of enclosures made of insulating material |
Is the panel builder's responsibility.
|
Fitted with: |
Internal bypass
Motor overload protection Internal bypass contacts Display |
Pollution degree |
3
|
Class |
Adjustable
|
Climatic proofing |
Damp heat, cyclic, to IEC 60068-2-30
Damp heat, constant, to IEC 60068-2-3 |
Connection to SmartWire-DT |
No
|
Rated impulse withstand voltage (Uimp) |
4000 V
|
Frame size |
V
|
Altitude |
Max. 2000 m
Above 2000 m with 0.5 % derating per 100 m |
Number of inputs |
1 (current input)
|
Ambient operating temperature - max |
50 °C
|
Ambient operating temperature - min |
-30 °C
|
Ambient storage temperature - max |
70 °C
|
Ambient storage temperature - min |
-50 °C
|
Assigned motor power at 200/208 V, 60 Hz, 3-phase |
200 HP
|
Assigned motor power at 460/480 V, 60 Hz, 3-phase |
600 HP
|
Assigned motor power at 600 V, 60 Hz, 3-phase |
850 HP
|
Assigned motor power at 690 V, 60 Hz, 3-phase |
850 HP
|
Assigned motor power in-delta at 690 V, 60 Hz |
1300 HP
|
Equipment heat dissipation, current-dependent Pvid |
25 W
|
Heat dissipation capacity Pdiss |
0 W
|
Heat dissipation per pole, current-dependent Pvid |
0 W
|
Mains voltage - max |
690 V
|
Mains voltage - min |
200 V
|
Output voltage |
120 V AC/DC (relay outputs)
|
Number of outputs |
2 Relay Outputs (programmable)
|
Screwdriver size |
0.6 x 3.5 mm, Terminal screws, Control circuit cables
|
Voltage type |
DC
|
Rated operational voltage (Ue) - min |
200 V
|
Rated power three-phase motor, inline, at 230 V |
200 kW
|
Rated power three-phase motor, inline, at 400 V |
450 kW
|
Rated power three-phase motor, inside delta, at 230 V |
200 kW
|
Rated power three-phase motor, inside delta, at 400 V |
750 kW
|
Static heat dissipation, non-current-dependent Pvs |
25 W
|
Voltage rating - max |
690 V
|
Application |
|
Protection |
Finger and back-of-hand proof, Protection against direct contact
|
Mounting position |
As required
|
Input current |
4 - 20 mA (Analog inputs)
|
Drop-out voltage |
0 - 3 V, DC operated
|
Overvoltage category |
II
|
Degree of protection |
IP00
NEMA Other |
Current consumption |
1400 mA, Control circuit, Regulator supply
150 mA, Control circuit, Digital inputs, External 24 V 10 A/150 ms, Control circuit, Regulator supply at peak performance (close bypass) at 24 V DC 100 mA, Control circuit, Digital inputs, External 24 V (no-load) |
Functions |
Min. ramp time 1 s - fast switching (semiconductor contactor)
Suppression of DC components for motors Current limitation Single direction Potential isolation between power and control sections Overload monitoring Soft start function Suppression of closing transients Underload monitoring |
Delay time |
0 - 120 s, Soft start function, Ramp times
|
Overload cycle |
AC-53a: 4.0 - 32: 99 - 3
|
Drop-out time |
100 ms, DC operated
|
Pick-up voltage |
21.6 - 26.4 V DC
|
Radio interference class |
Class A (EN 55011)
|
Fault memory |
10 Faults
|
Pick-up time |
100 ms at DC
|
Interfaces |
Modbus RTU (built-in)
|
Kickstart |
100% (Kickstart voltage)
Max. 2000 ms (Kickstart Duration) |
Rated control voltage (Uc) |
24 V DC (-10 %/+10 %)
24 V DC |
Supply frequency |
50/60 Hz, fLN, Main circuit
|
Terminal capacity (stranded) |
1 x (2.5 - 4) mm², Control circuit cables
2 x (1 - 2.5) mm², Control circuit cables 2 x (120 - 240) mm², Main cables 6 x (120 - 240) mm², Main cables 4 x (70 - 240) mm², Main cables |
Rated control supply voltage (Us) at AC, 50 Hz - max |
0 V
|
Rated control supply voltage (Us) at AC, 50 Hz - min |
0 V
|
Rated control supply voltage (Us) at AC, 60 Hz - max |
0 V
|
Rated control supply voltage (Us) at AC, 60 Hz - min |
0 V
|
Rated control supply voltage (Us) at DC - max |
24 V
|
Rated control supply voltage (Us) at DC - min |
24 V
|
Rated operational current (Ie) at AC-11 |
3 A
|
Rated operational current (Ie) at AC-53 |
850 A
|
Rated operational current for specified heat dissipation (In) |
850 A
|
Rated operational power at 400 V, 50 Hz |
450 kW
|
Rated operational power at 500 V, 50 Hz |
560 kW
|
Rated operational power at 690 V, 50 Hz |
710 kW
|
Rated operational voltage (Ue) - max |
690 V
|
Ramp/run-up time |
360 s
|
Shock resistance |
15 g, Mechanical
|
Suitable for |
Branch circuits, not as BCPD, (UL/CSA)
|
Tightening torque |
0.4 Nm, Screw terminals, Control circuit cables
|
Short-circuit protection rating |
NZMN4-ME875, Type “1” coordination, Main conducting paths
|
Start voltage |
Max. 85 %, Soft start function, Start voltage = turn-off voltage
|
Startup class |
CLASS 20 (heavy starting duty 3 x Iₑ for 45 s)
CLASS 30 (6 x Iₑ for 30 s) CLASS 10 (star-delta replacement) |
Terminal capacity (flexible with ferrule) |
2 x (120 - 240) mm², Main cables
4 x (70 - 240) mm², Main cables 1 x (2.5 - 4) mm², Control circuit cables 2 x (1 - 2.5) mm², Control circuit cables 6 x (120 - 240) mm², Main cables |
Terminal capacity (solid) |
4 x (70 - 240) mm², Main cables
6 x (120 - 240) mm², Main cables 1 x (2.5 - 4) mm², Control circuit cables 2 x (1 - 2.5) mm², Control circuit cables 2 x (120 - 240) mm², Main cables |
Terminal capacity (solid/stranded AWG) |
2 x (4 - 500 kcmil), Main cables
4 x (4 - 500 kcmil), Main cables 2 x (14 - 12), Control circuit cables 6 x (4 - 500 kcmil), Main cables 1 x (14 - 12), Control circuit cables |