Eaton EU2E SmartWire-DT T-Connector for IP69K I/O modules, 24 V DC, four parameterizable inputs/outputs with power supply, two M12 I/O sockets EU2E-SWD-4DD-1
Product Name |
Eaton EU2E Digital module
|
Catalog Number |
180406
|
Model Code |
EU2E-SWD-4DD-1
|
EAN |
4015081755592
|
Product Length/Depth |
110 mm
|
Product Height |
40 mm
|
Product Width |
80 mm
|
Product Weight |
0.08 kg
|
Certifications |
UL
CSA IEC/EN 61131-2 UL File No.: E170645 |
Catalog Notes |
Plug configuration (X1: 1 I/O, X2: 3 I/O)
|
Global Catalog |
180406
|
Type |
Digital modules
|
Features |
Overload proof (with diagnostics)
Digital inputs configurable Fieldbus connection over separate bus coupler possible Short-circuit protection (sensor supply) Overload protection (sensor supply) Digital outputs configurable |
Air discharge |
8 kV, according to IEC 61131-2, level 3, ESD
|
10.10 Temperature rise |
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
|
10.11 Short-circuit rating |
Is the panel builder's responsibility.
|
10.12 Electromagnetic compatibility |
Is the panel builder's responsibility.
|
10.13 Mechanical function |
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
|
10.2.2 Corrosion resistance |
Meets the product standard's requirements.
|
10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard's requirements.
|
10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard's requirements.
|
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects |
Meets the product standard's requirements.
|
10.2.4 Resistance to ultra-violet (UV) radiation |
Meets the product standard's requirements.
|
10.2.5 Lifting |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.6 Mechanical impact |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.7 Inscriptions |
Meets the product standard's requirements.
|
10.3 Degree of protection of assemblies |
Meets the product standard's requirements.
|
10.4 Clearances and creepage distances |
Meets the product standard's requirements.
|
10.5 Protection against electric shock |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.6 Incorporation of switching devices and components |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.7 Internal electrical circuits and connections |
Is the panel builder's responsibility.
|
10.8 Connections for external conductors |
Is the panel builder's responsibility.
|
10.9.2 Power-frequency electric strength |
Is the panel builder's responsibility.
|
10.9.3 Impulse withstand voltage |
Is the panel builder's responsibility.
|
10.9.4 Testing of enclosures made of insulating material |
Is the panel builder's responsibility.
|
Electric connection type |
Screw connection
|
Number of inputs (digital) |
4
|
Pollution degree |
3
|
Burst impulse |
2 kV, Supply cable, according to IEC/EN 61131-2, Level 3
1 kV, SmartWire-DT cable, according to IEC/EN 61131-2, Level 3 1 kV, Signal cable, according to IEC/EN 61131-2, Level 3 |
Climatic proofing |
Damp heat, constant, to IEC 60068-2-3
Dry heat to IEC 60068-2-2 |
Connection to SmartWire-DT |
Yes
|
Air pressure |
795 - 1080 hPa (operation)
|
Category (EN 954-1) |
None
|
Explosion safety category for dust |
None
|
Environmental conditions |
Condensation: permissible
|
Input |
Max. 4 Freely configurable inputs/outputs
|
Explosion safety category for gas |
None
|
Output current |
0.5 A
|
Mounting method |
Screw fixing (M4)
Wall mounting/direct mounting Mounting section (Clip M20) DIN rail Rail mounting possible |
Current consumption |
70 mA, Max. current consumption per M12 I/O plug, Sensor supply, SmartWire-DT network
75 mA, SmartWire-DT network, 24 V, without sensor and without I/O supply |
Voltage type |
DC
|
Mounting position |
As required
|
Output |
Max. 4 Transistor Outputs
Max. 4 Freely configurable inputs/outputs |
Contact discharge |
4 kV, according to IEC/EN 61131-2, Level 2, ESD
|
Overvoltage category |
II
|
Safety performance level (EN ISO 13849-1) |
None
|
SIL (IEC 61508) |
None
|
Ambient operating temperature - max |
70 °C
|
Ambient operating temperature - min |
-25 °C
|
Ambient storage temperature - max |
70 °C
|
Ambient storage temperature - min |
-40 °C
|
Equipment heat dissipation, current-dependent Pvid |
0 W
|
Heat dissipation capacity Pdiss |
0 W
|
Heat dissipation per pole, current-dependent Pvid |
0 W
|
Height of fall (IEC/EN 60068-2-32) - max |
0.3 m
|
Input current at signal 1 |
4 mA
|
Number of HW-interfaces (industrial ethernet) |
0
|
Number of HW-interfaces (other) |
0
|
Number of HW-interfaces (parallel) |
0
|
Number of HW-interfaces (RS-232) |
0
|
Number of HW-interfaces (RS-422) |
0
|
Number of HW-interfaces (RS-485) |
0
|
Number of HW-interfaces (serial TTY) |
0
|
Number of HW-interfaces (USB) |
0
|
Constant acceleration |
1 g, 8.4 - 150 Hz, according to IEC/EN 61131-2, Vibrations
|
Constant amplitude |
3,5 mm, 5 - 8.4 Hz, according to IEC/EN 61131-2, Vibrations
|
Surge rating |
1 kV, Surge I/O cables, Surge (IEC/EN 61131-2:2008, Level 1), EMC
0.5 kV, Surge power cables, Surge (IEC/EN 61131-2:2008, Level 1), EMC |
Potential isolation |
Input to input: no
Output to output: no Output to input: no Between Outputs to SmartWire-DT: no Inputs for SmartWire-DT: no |
Power loss |
1.8 W
|
Electromagnetic fields |
1 V/m at 2.0 - 2.7 GHz (according to IEC/EN 61131-2:2008)
10 V/m at 80 - 1000 MHz (according to IEC/EN 61131-2:2008) 3 V/m at 1.4 - 2 GHz (according to IEC/EN 61131-2:2008) |
Radiated RFI |
10 V (IEC/EN 61131-2:2008, Level 3)
|
Drop and topple |
50 mm Drop height, Drop to IEC/EN 60068-2-31
|
Protocol |
Other bus systems
|
Radio interference class |
Class A (EN 55011)
|
Number of outputs (digital) |
4
|
Relative humidity |
5 - 95 % (non-condensing, IEC/EN 60068-2-30)
|
Connection type |
SWD-IN : M12 plug (A-keyed), 5 pole
5-pin M12 socket (A-keyed), Supply and I/O sensor SWD-OUT: M12 socket (A-keyed), 5 pole |
Data transmission type |
Other
|
Data transfer rate |
2 MBit/s, SmartWire-DT
Setting automatically |
Degree of protection |
IP69K
|
Station |
SmartWire-DT slave, SmartWire-DT network
|
Input delay |
< 0.2 ms
|
Shock resistance |
30 g, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 11 ms, 9 Impacts
|
Short-circuit protection |
Outputs are short-circuit proof
|
Short-circuit tripping current |
Max. 1.2 A over 3 ms, Digital semi-conductor outputs
|
Lamp load |
≤ 3 W (at RLL)
|
Functions |
Short-circuit protection, outputs available
For connection of digital I/O signals |
System accessory |
Yes
|
Limit value type 1 |
High: > 15 V DC
Low: < 5 V DC |
Input current |
4 mA (at 24 V DC, Digital inputs)
|
LED indicator |
Status indication of display outputs: Yellow LED
Status indication of SmartWire-DT network: Green LED Status indication of input: Yellow LED |
Number of HW-interfaces (wireless) |
0
|
Number of interfaces (PROFINET) |
0
|
Operating temperature - max |
70 °C
|
Operating temperature - min |
-25 °C
|
Permitted voltage at input - max |
28.8 V
|
Permitted voltage at input - min |
20.4 V
|
Permitted voltage at output - max |
28.8 V
|
Permitted voltage at output - min |
20.4 V
|
Rated operational current for specified heat dissipation (In) |
0 A
|
Static heat dissipation, non-current-dependent Pvs |
1.8 W
|
Supply voltage at AC, 50 Hz - max |
0 VAC
|
Supply voltage at AC, 50 Hz - min |
0 VAC
|
Supply voltage at AC, 60 Hz - max |
0 VAC
|
Supply voltage at AC, 60 Hz - min |
0 VAC
|
Supply voltage at DC - max |
28.8 VDC
|
Supply voltage at DC - min |
0 VDC
|
Time delay at signal exchange - max |
0.2 ms
|
Time delay at signal exchange - min |
0 ms
|
Product category |
SmartWire-DT slave
|
Switching capacity |
IEC/EN 60947-5-1, utilization category DC-13, Digital outputs
|