Download dokument () af 20

110107
Modelkode: NZM1-XSR-U

Eaton Moeller series NZM - Molded Case Circuit Breaker. Main switch assembly kit, bottom, red/yellow

General specifications

Product Name
Eaton Moeller series NZM operating element
Catalog Number
110107
EAN
4015081096831
Product Length/Depth
159 mm
Product Height
275 mm
Product Width
140 mm
Product Weight
5.8 kg
Compliances
UL/CSA
IEC
RoHS conform
Model Code
NZM1-XSR-U

Delivery program

Features
Lockable
Special features
  • External warning plate/designation label can be clipped on.
  • For enhanced busbar tag shroud on the incomer side, please order IP2X protection against contact with a finger.
Fitted with:
External warning plate/marking plate in German/English
NZM...-XV4 extension shaft
Door coupling rotary handle with rotary drive
Black and yellow lightning symbol
Padlock
Suitable for
Power circuit breaker
Switch disconnector
Emergency stop

Technical Data - Mechanical

Color
Black
Cover/door type
Door interlock lockable on OFF with max. 3 padlocks
Degree of protection / NEMA enclosure type
IP66
4X. 12
Special features
  • External warning plate/designation label can be clipped on.
  • For enhanced busbar tag shroud on the incomer side, please order IP2X protection against contact with a finger.

Design verification as per IEC/EN 61439

10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard's requirements.
10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of assemblies
Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances
Meets the product standard's requirements.
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9.2 Power-frequency electric strength
Is the panel builder's responsibility.
10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material
Is the panel builder's responsibility.
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.

Eksportér produktspecifikation