Download dokument () af 20

179328
Modelkode: N4-4-800-S15-PV-NA

Eaton Moeller series NZM - Molded Case Circuit Breaker. Molded Case Switch 4p 800A 1500VDC UL

General specifications

Product Name
Eaton Moeller series NZM switch-disconnector
Catalog Number
179328
EAN
4015081744145
Product Length/Depth
401 mm
Product Height
207 mm
Product Width
280 mm
Product Weight
22.723 kg
Compliances
RoHS conform
Certifications
UL 489B
UL489B
CE
UL (File No. E471671)
IEC 60947-3
CE marking
CCC
UL listed
Model Code
N4-4-800-S15-PV-NA

Delivery program

Application
  • Branch circuits, feeder circuits
  • Open areas
  • Utility buildings
Type
DC switch-disconnector
Circuit breaker frame type
N4
Number of poles
Four-pole
Amperage Rating
800 A
Features
Version as maintenance-/service switch
Version as emergency stop installation
Optionally with XR remote operator. Can be optionally controlled remotely with XU/XA shunt release.
Motor drive optional
Version as main switch
Special features
  • Max. 50 % trip by shunt/undervoltage release of mechanical life span
  • Main switch characteristics including positive drive to IEC/EN 60204, VDE 0113.
  • Isolating characteristics to IEC/EN 60947-3, VDE 0660.
  • For DC switching all 4 contacts must be connected in series -see information on jumper kit accessories.
  • Operating with ungrounded systems (e.g., IT), the installation must prevent a double ground fault
  • N4-4-...-S15-DC feeder unit and outgoer from the bottom only.
  • Suitable for 100%-rated application with enclosure minimum WxHxD of 1200 x 600 x 275 mm
  • No overcurrent protection.
  • Rated current = rated uninterrupted current: 800 A include jumpers at 65 °C

Technical Data - Electrical

Voltage rating
1500 V - 1500 V
Rated operating voltage Ue (UL) - max
1500 V DC
Rated insulation voltage (Ui)
1500 V
Current rating (Iu) at 40°C with terminal jumpers
800 A
Current rating (Iu) at 65°C with terminal jumpers
800 A
Rated operational current
800 CSA (DC-21B)
Rated short-time withstand current (t = 0.1 s)
34 kA
Amperage Rating
800 A
Electrical connection type of main circuit
Screw connection
Number of operations per hour - max
60
Handle type
Rocker lever
Utilization category
DC-21 A
Overvoltage category
III
Pollution degree
3
Lifespan, electrical
500 operations

Technical Data - Mechanical

Mounting Method
Ground mounting
Intermediate mounting
Fixed
Distribution board installation
Built-in device fixed built-in technique
Mounting Method
Ground mounting
Intermediate mounting
Fixed
Distribution board installation
Built-in device fixed built-in technique
Degree of protection
IP20
Degree of protection (IP), front side
IP20
Number of auxiliary contacts (change-over contacts)
0
Number of auxiliary contacts (normally closed contacts)
0
Number of auxiliary contacts (normally open contacts)
0
Number of switches
1
Handle color
Black
Switch positions
I, +, 0
Special features
  • Max. 50 % trip by shunt/undervoltage release of mechanical life span
  • Main switch characteristics including positive drive to IEC/EN 60204, VDE 0113.
  • Isolating characteristics to IEC/EN 60947-3, VDE 0660.
  • For DC switching all 4 contacts must be connected in series -see information on jumper kit accessories.
  • Operating with ungrounded systems (e.g., IT), the installation must prevent a double ground fault
  • N4-4-...-S15-DC feeder unit and outgoer from the bottom only.
  • Suitable for 100%-rated application with enclosure minimum WxHxD of 1200 x 600 x 275 mm
  • No overcurrent protection.
  • Rated current = rated uninterrupted current: 800 A include jumpers at 65 °C
Lifespan, mechanical
10000 operations

Technical Data - Mechanical - Terminals

Standard terminals
Screw connection,Optional:Tunnel terminal,Rear-side connection,Strip connection
Terminal capacity (aluminum stranded conductor/cable)
Min. 185 mm² - 240 mm² (1x) at rear-side 1-hole module plate
Max. 70 mm² - 185 mm² (2x) at rear-side 1-hole module plate
50 mm² (4x) at rear-side 2-hole module plate
240 mm² (2x) at rear-side width extension
70 mm² - 240 mm² (6x) at rear-side width extension
NA: aluminum conductor not applicable
Terminal capacity (copper busbar)
M10 at rear-side screw connection
Min. 25 mm x 5 mm direct at switch rear-side connection
Max. 50 mm x 10 mm (2x) direct at switch rear-side connection
Min. 25 mm x 5 mm at rear-side 1-hole module plate
Max. 50 mm x 10 mm (2x) at rear-side 1-hole module plate
50 mm x 10 mm (2x) at rear-side 2-hole module plate
Min. 60 mm x 10 mm at rear-side width extension
Max. 80 mm x 10 mm (2x) at rear-side width extension
NA: same as for IEC
Terminal capacity (copper stranded conductor/cable)
50 mm² - 240 mm² (4x) at 4-hole tunnel terminal
120 mm² - 185 mm² (1x) direct at switch rear-side connection
50 mm² - 185 mm² (4x) direct at switch rear-side connection
Min. 120 mm² - 300 mm² (1x) at rear-side 1-hole module plate
Max. 95 mm² - 300 mm² (2x) at rear-side 1-hole module plate
Min. 95 mm² - 185 mm² (2x) at rear-side 2-hole module plate
Max. 35 mm² - 185 mm² (4x) at rear-side 2-hole module plate
300 mm² (4x) at rear-side width extension
95 mm² - 240 mm² (6x) at rear-side width extension
NA: AWG 0- kcmil 500 (4x) at 4-hole tunnel terminal
NA: kcmil 250 - kcmil 350 (1x) direct at switch rear-side connection
NA: AWG 0 - kcmil 350 (4x) direct at switch rear-side connection
NA: min. kcmil 250 - kcmil 600 (1x) at rear-side 1-hole module plate
NA: max. AWG 3/0 - kcmil 600 (2x) at rear-side 1-hole module plate
NA: min. AWG 3/0 - kcmil 350 (2x) at rear-side 2-hole module plate
NA: max. AWG 2 - kcmil 350 (4x) at rear-side 2-hole module plate
NA: kcmil 600 (4x) at rear-side width extension
NA: AWG 3/0 - kcmil 500 (6x) at rear-side width extension
Terminal capacity (copper strip)
Min. 6 segments of 16 mm x 0.8 mm at flat conductor terminal
Max. 10 segments of 32 mm x 1 mm (2x) at flat conductor terminal
10 segments of 50 mm x 1 mm (2x) at 1-hole module plate
Min. 10 segments of 50 mm x 1 mm (2x) at rear-side connection (punched)
Max. 10 segments of 50 mm x 1 mm (2x) at rear-side connection (punched)
10 segments of 80 mm x 1 mm (2x) at rear-side width extension
NA: same as for IEC

Design verification as per IEC/EN 61439 - technical data

Rated operational current for specified heat dissipation (In)
800 A
Equipment heat dissipation, current-dependent
95 W
Ambient operating temperature - min
-25 °C
Ambient operating temperature - max
70 °C
Ambient storage temperature - min
40 °C
Ambient storage temperature - max
70 °C

Design verification as per IEC/EN 61439

10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard's requirements.
10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of assemblies
Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances
Meets the product standard's requirements.
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9.2 Power-frequency electric strength
Is the panel builder's responsibility.
10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material
Is the panel builder's responsibility.
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.

Additional information

Functions
Interlockable
Voltage release optional
Photovoltaic applications
Disconnectors/main switches

Eksportér produktspecifikation

Serial Number Verified :
Authenticated:
The product is verified as being authentic; however, this does not guarantee the condition or fit for purpose of the product.

Godkend produkt

Indtast dit 16-17-cifrede serienummer
Det serienummer, du har indtastet, må ikke indeholde specialtegn. Det serienummer, du indtastede, er ikke korrekt, det skal være 16- eller 17-cifret. Det serienummer, du indtastede, blev ikke fundet. Prøv igen, eller rapportér dette problem for yderligere hjælp. Det serienummer, du har indtastet, matcher ikke med produktet. Kontrollér dit produkts serienummer, og prøv igen. Klik på her for at gå til produktsiden for det serienummer, du har indtastet Serienummeret er kendt af Eaton for at være mistænkeligt, prøv igen eller rapportér dette problem for yderligere hjælp.
Serienummer
Nulstil Serienummeret er kendt af Eaton for at være mistænkeligt, prøv igen eller rapportér dette problem for yderligere hjælp. Serienummeret genkendes ikke af Eaton og er ugyldigt. Brug denne formular til at rapportér dette problem for yderligere hjælp.
Indtast den 6-cifrede godkendelseskode
Det produkt, du indtastede, er mistænkeligt! Prøv igen, eller rapportér dette problem for yderligere hjælp. Den godkendelseskode, du indtaster, matcher ikke med vores oplysninger for dette serienummer. Prøv igen, eller rapportér dette problem for yderligere hjælp. Ugyldig godkendelseskode. Den skal være på seks tegn rapportér dette problem for yderligere hjælp. Godkendelseskode er påkrævet rapportér dette problem for yderligere hjælp.
Løs Captcha-udfordringen inden godkendelse.
Kontakt os for at rapportere problem
x
Rapportér et problem
Indtast dit fulde navn.
x
Tak, dit problem er blevet indsendt, og vores produktteam vil kontakte dig snarest.
Bemærk: Hvis fil(er) mangler i .zip-download, understøttes filtypen ikke ved bulk download.