192486
Modelkode: NZMN3-AX600-NA

Eaton Moeller series NZMN3 PXR10 circuit breaker, 600 A, 3-pole, Screw terminal, UL/CSA

General specifications

Product Name
Eaton Moeller series NZM molded case circuit breaker electronic
Catalog Number
192486
EAN
4015081932146
Product Length/Depth
166 mm
Product Height
297 mm
Product Width
140 mm
Product Weight
7.142 kg
Compliances
RoHS conform
Certifications
IEC 60947-2
CE marking
UL/CSA
CSA (Class No. 1432-01)
Specially designed for North America
CSA (File No. 22086)
UL (File No. E31593)
CSA-C22.2 No. 5-09
IEC
CSA certified
UL 489
UL listed
UL (Category Control Number DIVQ)
Model Code
NZMN3-AX600-NA

Tekniske data – elektrisk

Application
Branch circuits, feeder circuits
Type
  • LI Overload and short-circuit protective device
  • R.m.s. value measurement and “thermal memory”
  • USB interface for configuration and test function with Power Xpert Protection Manager software
  • Switches conform to UL/CSA as well as the IEC regulations. IEC switching performance values are contained on the rating plate.
Circuit breaker frame type
NZM3
Number of poles
Three-pole
Release system
Electronic release
Features
Motor drive optional
Protection unit
Special features
Circuit breaker

Tekniske data – elektrisk

Rated operational current
600 A (660-690 V AC-3, making and breaking capacity)
600 A (690 V AC -1, making and breaking capacity)
Amperage Rating
600 A
Instantaneous current setting (Ii) - min
2 A
Instantaneous current setting (Ii) - max
800 A
Overload current setting (Ir) - min
240 A
Overload current setting (Ir) - max
600 A
Short-circuit release non-delayed setting - min
1200 A
Short-circuit release non-delayed setting - max
4800 A
Rated short-circuit breaking capacity Ics (IEC/EN 60947) at 400/415 V, 50/60 Hz
50 kA
Electrical connection type of main circuit
Screw connection
Handle type
Rocker lever

Tekniske data – kommunikation

Voltage rating
690 V - 690 V
Rated operating voltage Ue (UL) - max
600 V
Rated operational current
600 A (660-690 V AC-3, making and breaking capacity)
600 A (690 V AC -1, making and breaking capacity)
Amperage Rating
600 A
Instantaneous current setting (Ii) - min
2 A
Instantaneous current setting (Ii) - max
800 A
Overload current setting (Ir) - min
240 A
Overload current setting (Ir) - max
600 A
Short-circuit release non-delayed setting - min
1200 A
Short-circuit release non-delayed setting - max
4800 A
Rated short-circuit breaking capacity Ics (IEC/EN 60947) at 400/415 V, 50/60 Hz
50 kA
Electrical connection type of main circuit
Screw connection
Handle type
Rocker lever

Tekniske data – mekanisk

Mounting Method
Built-in device fixed built-in technique
Fixed
Degree of protection
IP20
Number of auxiliary contacts (change-over contacts)
0
Number of auxiliary contacts (normally closed contacts)
0
Number of auxiliary contacts (normally open contacts)
0
Position of connection for main current circuit
Front side

Eksportér produktspecifikation

Serial Number Verified :
Authenticated:
The product is verified as being authentic; however, this does not guarantee the condition or fit for purpose of the product.

Godkend produkt

Indtast dit 16-17-cifrede serienummer
The serial number you entered should not contain special charachter. The serial number you entered is not correct it should be of 16 or 17 digit. The serial number you entered was not found. Please try again or report this issue for further assistance. The serial number you entered does not match the product. Check your product's serial number and try again. Click here to navigate to the product page for the serial number you have entered The serial number is known to Eaton to be suspect, please try again or report this issue for further assistance.
Serial number
Reset The serial number is known to Eaton to be suspect, please try again or report this issue for further assistance. The Serial Number is not recognised by Eaton and is invalid. Please use this form to report this issue for further assistance.
Enter the 6 digit authentication code
The product you entered is suspect! Please try again or report this issue for further assistance. The authentication code you enter does not match our records for this serial number. Please try again, or report this issue for further assistance. Invalid Authentication code. Length must be 6 characters report this issue for further assistance. Authentication code is required report this issue for further assistance.
Complete Captcha challenge before authenticating.
Contact us to report-issue
x
Report an Issue
Please enter your full name.
x
Thank you, your issue has been submitted, our product team will contact with you soon.
Bemærk: Hvis fil(er) mangler i .zip-download, understøttes filtypen ikke ved bulk download.