Vidensøgning
Download dokument () af 20
We make what matters work*

197223
EASY-E4-DC-6AE1

Eaton Moeller® series EASY I/O expansion, For use with easyE4, 24 V DC, Inputs expansion (number) analog: 4, screw terminal EASY-E4-DC-6AE1

Generelle specifikationer

Product Name
Eaton Moeller® series EASY I/O expansion
Catalog Number
197223
EAN
4015080892847
Product Length/Depth
58 mm
Product Height
90 mm
Product Width
36 mm
Product Weight
0.1 kg
Certifications
UL File No.: E205091
CE
UL hazardous location group B (hydrogen)
UL hazardous location division 2
UL hazardous location group C (ethylene)
UL hazardous location group A (acetylene)
UL hazardous location group D (propane)
UL hazardous location class I
cULus Ordinary Location
DNV
TAA00002HT
cULus Hazard Location
UL File No.: E523283
EN 61131-2
IEC 61131-2
EN IEC 61000-6-3
IEC 61000-6-3
EN IEC 61010-2-201
IEC 61010-2-201
UL 61010-1
UL 61010-2-201
CSA C22.2 No. 61010-1
CSA C22.2 No. 61010-2-201
UL 121201
CSA C22.2 No. 213
Model Code
EASY-E4-DC-6AE1

Omgivelsesforhold, mekaniske

Drop and topple
50 mm Drop height, Drop to IEC/EN 60068-2-31
Height of fall (IEC/EN 60068-2-32) - max
0.3 m
Mounting position
Horizontal
Vertical
Shock resistance
15 g, Mechanical, acc. to IEC/EN61131-2, Half-sinusoidal shock 11 ms, 18 Impacts
Vibration resistance
8.4 - 150 Hz, 1 g constant acceleration
5 - 8.4 Hz, 3.5 mm constant amplitude
According to IEC/EN 61131-2

Kabel

Cable length
Analog inputs: ≤ 10 m (shielded)
Analog outputs: ≤ 10 m (shielded)

Klimatiske miljøforhold

Air pressure
795 - 1080 hPa (operation)
Ambient operating temperature - max
55 °C
Ambient storage temperature - max
70 °C
Ambient operating temperature - min
-25 °C
Ambient storage temperature - min
-40 °C
Environmental conditions
Clearance in air and creepage distances according to EN 50178, EN 61010-2-201, UL61010-2-201, CSA-C22.2 NO. 61010-2-201
Condensation: prevent with appropriate measures
Relative humidity
5 - 95 % (IEC 60068-2-30, IEC 60068-2-78)

Kommunikation

Connection type
Screw terminal
LED indicator
Status indication of Power/RUN

Designverifikation

10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility.
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard's requirements.
10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of assemblies
Meets the product standard's requirements.
10.4 Clearances and creepage distances
Meets the product standard's requirements.
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9.2 Power-frequency electric strength
Is the panel builder's responsibility.
10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material
Is the panel builder's responsibility.
Equipment heat dissipation, current-dependent Pvid
0 W
Heat dissipation capacity Pdiss
0 W
Heat dissipation per pole, current-dependent Pvid
0 W
Static heat dissipation, non-current-dependent Pvs
2.5 W

Elektrisk nominel værdi

Power consumption
2.5 W
Rated operational voltage
Power supply: 24 V DC (-15 %/+ 20 %)
Supply voltage at DC - max
28.8 VDC
Supply voltage at DC - min
20.4 VDC

Elektromagnetisk kompatibilitet

Air discharge
8 kV
Burst impulse
2 kV, I/O port
2 kV, Power supply port
According to IEC/EN 61131-2
Contact discharge
6 kV
Electromagnetic fields
10 V/m at 0.08 - 1.0 GHz (according to IEC/EN 61131-2)
3 V/m at 1.0 - 6 GHz (according to IEC/EN 61131-2)
Immunity to line-conducted interference
10 V (according to IEC/EN 61131-2)
Radio interference class
Class B (EN 61000-6-3)
Surge rating
0.5 kV, Line-to-Line, Power supply port
1 kV, Line-to-Earth, Power supply port
According to IEC/EN 61131-2
Voltage dips
10 ms

Features & functions

Features
Expandable
Expansion device
Fitted with:
Analog output

Generelle oplysninger

Degree of protection
IP20
Insulation resistance
According to EN IEC 61010-2-201, UL61010-2-201, CSA-C22.2 NO. 61010-2-223
Mounting method
Front build in possible
Rail mounting possible
Wall mounting/direct mounting
Top-hat rail fixing (according to IEC/EN 60715, 35 mm)
Screw fixing using fixing brackets ZB4-101-GF1 (accessories)
Overvoltage category
Power supply + Inputs + Outputs + Right extension interface: II
Left extension interface: III
Pollution degree
2
Product category
Control relays easyE4
Residual ripple
Power supply: ≤ 5 %
Resolution
  • 12 Bit (value 0 - 4095, Analog inputs)
  • 12 Bit (value 0 - 4095, Analog outputs)
Software
EASYSOFT-SWLIC/easySoft
Type
easyE4 extension
Used with
easyE4
Voltage type
DC

Indgang/udgang

Accuracy
1 %, Analog inputs at -25 °C - 55 °C
Input
Voltage
Current
Input impedance
Analog as voltage: 12.12 kΩ
Analog as current: 250 Ω
Number of inputs (analog)
4
Number of inputs (digital)
0
Number of outputs (analog)
2
Number of outputs (digital)
0
Output
Current
Voltage
Signal range
4 - 20 mA, Analog outputs
0 - 20 mA, Analog inputs
0 - 10 V DC, Analog inputs
0 - 10 V DC, Analog outputs
4 - 20 mA, Analog inputs
0 - 20 mA, Analog outputs

Sikkerhed

Explosion safety category for dust
None
Explosion safety category for gas
None
Potential isolation
POW+Inputs+Outputs+right Extension interface vs. left Extension interface: yes
Protection against polarity reversal
Yes

Nominel kortslutningsværdi

Short-circuit protection
≥ 1A (T), Fuse, Power supply

Terminalkapaciteter

Screwdriver size
3.5 x 0.6 mm, Terminal screw
Terminal capacity
0.2 - 4 mm² (AWG 22 - 12), solid
0.2 - 2.5 mm², flexible with ferrule
0.2 - 2.5 mm², flexible without ferrule
Tightening torque
0.6 Nm, Screw terminals

Eksportér produktspecifikation

Serial Number Verified :
Authenticated:
The product is verified as being authentic; however, this does not guarantee the condition or fit for purpose of the product.

Godkend produkt

Indtast dit 16-17-cifrede serienummer
Det serienummer, du har indtastet, må ikke indeholde specialtegn. Det serienummer, du indtastede, er ikke korrekt, det skal være 16- eller 17-cifret. Det serienummer, du indtastede, blev ikke fundet. Prøv igen, eller rapportér dette problem for yderligere hjælp. Det serienummer, du har indtastet, matcher ikke med produktet. Kontrollér dit produkts serienummer, og prøv igen. Klik på her for at gå til produktsiden for det serienummer, du har indtastet Serienummeret er kendt af Eaton for at være mistænkeligt, prøv igen eller rapportér dette problem for yderligere hjælp.
Serienummer
Nulstil Serienummeret er kendt af Eaton for at være mistænkeligt, prøv igen eller rapportér dette problem for yderligere hjælp. Serienummeret genkendes ikke af Eaton og er ugyldigt. Brug denne formular til at rapportér dette problem for yderligere hjælp.
Indtast den 6-cifrede godkendelseskode
Det produkt, du indtastede, er mistænkeligt! Prøv igen, eller rapportér dette problem for yderligere hjælp. Den godkendelseskode, du indtaster, matcher ikke med vores oplysninger for dette serienummer. Prøv igen, eller rapportér dette problem for yderligere hjælp. Ugyldig godkendelseskode. Den skal være på seks tegn rapportér dette problem for yderligere hjælp. Godkendelseskode er påkrævet rapportér dette problem for yderligere hjælp.
Løs Captcha-udfordringen inden godkendelse.
Kontakt os for at rapportere problem
x
Rapportér et problem
Indtast dit fulde navn.
x
Tak, dit problem er blevet indsendt, og vores produktteam vil kontakte dig snarest.
Bemærk: Hvis fil(er) mangler i .zip-download, understøttes filtypen ikke ved bulk download.