Reset
Eaton Moeller® series EASY I/O expansion, For use with easyE4, 24 V DC, Inputs expansion (number) analog: 4, screw terminal EASY-E4-DC-4PE1
| Product Name |
Eaton Moeller® series EASY I/O expansion
|
| Catalog Number |
197224
|
| EAN |
4015080892854
|
| Product Length/Depth |
58 mm
|
| Product Height |
90 mm
|
| Product Width |
36 mm
|
| Product Weight |
0.1 kg
|
| Certifications |
IEC/EN 61000-6-3
IEC 60068-2-30 CULus per UL 61010 IEC/EN 61131-2 IEC 60068-2-6 IEC 60068-2-27 IEC/EN 61000-6-2 EN 61010 EN 50178 CSA-C22.2 No. 61010 IEC 60664 IEC/EN 61000-4-2 UL Listed UL Category Control No.: NRAQ, NRAQ7 UL File No.: E205091 DNV GL CE UL hazardous location group A (acetylene) UL hazardous location group B (hydrogen) UL hazardous location division 2 UL hazardous location group C (ethylene) UL hazardous location class I UL hazardous location group D (propane) |
| Model Code |
EASY-E4-DC-4PE1
|
| Features |
Additional measurement aids: Filtering (software), smoothing of analog input signal (PT1 behavior), only with set sampling time, selectable per sensor: yes
Expandable Expansion device Measuring principle: Two or three wire per sensor, selectable by connection of sensor |
| Functions |
Card diagnostic
Diagnostics below lower measurement range |
| Degree of protection |
IP20
|
| Insulation resistance |
According to EN 50178, EN 61010-2-201, UL61010-2-201, CSA-C22.2 NO. 61010-2-201
|
| Mounting method |
Rail mounting possible
Top-hat rail fixing (according to IEC/EN 60715, 35 mm) Wall mounting/direct mounting Screw fixing using fixing brackets ZB4-101-GF1 (accessories) Front build in possible |
| Mounting method |
Rail mounting possible
Top-hat rail fixing (according to IEC/EN 60715, 35 mm) Wall mounting/direct mounting Screw fixing using fixing brackets ZB4-101-GF1 (accessories) Front build in possible |
| Overvoltage category |
III
|
| Pollution degree |
2
|
| Product category |
Control relays easyE4
|
| Protocol |
TCP/IP
MODBUS |
| Residual ripple |
≤ 5 %
|
| Resolution |
12 Bit (0- 4095, digital, scaling per sensor)
|
| Software |
EASYSOFT-SWLIC/easySoft
|
| Type |
easyE4 extension
|
| Voltage type |
DC
|
| Drop and topple |
50 mm Drop height, Drop to IEC/EN 60068-2-31
|
| Height of fall (IEC/EN 60068-2-32) - max |
0.3 m
|
| Mounting position |
Horizontal
Vertical |
| Shock resistance |
15 g, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 11 ms, 18 Impacts
|
| Vibration resistance |
57 - 150 Hz, 2 g constant acceleration
10 - 57 Hz, 0.15 mm constant amplitude According to IEC/EN 60068-2-6 |
| Air pressure |
795 - 1080 hPa (operation)
|
| Ambient operating temperature - min |
-25 °C
|
| Ambient operating temperature - max |
55 °C
|
| Ambient storage temperature - min |
-40 °C
|
| Ambient storage temperature - max |
70 °C
|
| Environmental conditions |
Condensation: prevent with appropriate measures
Clearance in air and creepage distances according to EN 50178, EN 61010-2-201, UL61010-2-201, CSA-C22.2 NO. 61010-2-201 |
| Relative humidity |
5 - 95 % (IEC 60068-2-30, IEC 60068-2-78)
|
| Air discharge |
8 kV
|
| Burst impulse |
2 kV, Signal cable
According to IEC/EN 61000-4-4 2 kV, Supply cable |
| Contact discharge |
6 kV
|
| Electromagnetic fields |
10 V/m at 0.8 - 1.0 GHz (according to IEC EN 61000-4-3)
1 V/m at 2.0 - 2.7 GHz (according to IEC EN 61000-4-3) 3 V/m at 1.4 - 2 GHz (according to IEC EN 61000-4-3) |
| Immunity to line-conducted interference |
10 V (according to IEC/EN 61000-4-6)
|
| Radio interference class |
Class B (EN 61000-6-3)
|
| Surge rating |
According to IEC/EN 61000-4-5, power pulses (Surge), EMC
0.5 kV, Supply cables, symmetrical, EASY…DC, power pulses (Surge), EMC 1 kV, Supply cables, asymmetrical, power pulses (Surge), EMC |
| Voltage dips |
20 ms
≤ 10 ms, Bridging voltage dips |
| Terminal capacity |
0.2 - 2.5 mm² (22 - 12 AWG), flexible with ferrule
0.2 - 4 mm² (AWG 22 - 12), solid |
| Screwdriver size |
3.5 x 0.8 mm, Terminal screw
|
| Tightening torque |
0.6 Nm, Screw terminals
|
| Heat dissipation |
3.4 W (at 24 V DC)
|
| Inrush current |
12.5 A (for 6 ms)
|
| Power consumption |
1 W
|
| Power loss |
1 W
|
| Rated operational voltage |
24 V DC (-15 %/+ 20 % - power supply)
20.4 - 28.8 V DC |
| Supply voltage at DC - min |
20.4 VDC
|
| Supply voltage at DC - max |
28.8 VDC
|
| Short-circuit protection |
≥ 1A (T), Fuse, Power supply
|
| Connection type |
Screw terminal
|
| Cable length |
≤ 30 m, unscreened, Analog inputs temperature resistance Pt100 or Ni1000 sensors
|
| Input |
Input type resistance sensor: Platinum sensor Pt100 (according to DIN EN 60751, IEC 751)
Input type resistance sensor: Nickel sensor Ni1000 (according to DIN 43760) |
| Input current |
40 mA
|
| Number of inputs (analog) |
4
|
| Number of inputs (digital) |
0
|
| Number of outputs (analog) |
0
|
| Number of outputs (digital) |
0
|
| Explosion safety category for gas |
None
|
| Potential isolation |
Between Analog inputs PT100 or Ni1000 and Power supply: no
Between Analog inputs PT100 or Ni1000 and expansion units: yes Between Analog inputs PT100 or Ni1000 and Inputs: no |
| Protection against polarity reversal |
Yes, for supply voltage (Siemens MPI optional)
|
| Explosion safety category for dust |
None
|
| Equipment heat dissipation, current-dependent Pvid |
0 W
|
| Heat dissipation capacity Pdiss |
0 W
|
| Heat dissipation per pole, current-dependent Pvid |
0 W
|
| Rated operational current for specified heat dissipation (In) |
0 A
|
| Static heat dissipation, non-current-dependent Pvs |
1 W
|
| 10.2.2 Corrosion resistance |
Meets the product standard's requirements.
|
| 10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard's requirements.
|
| 10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard's requirements.
|
| 10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects |
Meets the product standard's requirements.
|
| 10.2.4 Resistance to ultra-violet (UV) radiation |
Meets the product standard's requirements.
|
| 10.2.5 Lifting |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.2.6 Mechanical impact |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.2.7 Inscriptions |
Meets the product standard's requirements.
|
| 10.3 Degree of protection of assemblies |
Meets the product standard's requirements.
|
| 10.4 Clearances and creepage distances |
Meets the product standard's requirements.
|
| 10.5 Protection against electric shock |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.6 Incorporation of switching devices and components |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.7 Internal electrical circuits and connections |
Is the panel builder's responsibility.
|
| 10.8 Connections for external conductors |
Is the panel builder's responsibility.
|
| 10.9.2 Power-frequency electric strength |
Is the panel builder's responsibility.
|
| 10.9.3 Impulse withstand voltage |
Is the panel builder's responsibility.
|
| 10.9.4 Testing of enclosures made of insulating material |
Is the panel builder's responsibility.
|
| 10.10 Temperature rise |
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
|
| 10.11 Short-circuit rating |
Is the panel builder's responsibility.
|
| 10.12 Electromagnetic compatibility |
Is the panel builder's responsibility.
|
| 10.13 Mechanical function |
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
|