Vidensøgning
Download dokument () af 20
We make what matters work*

197514
EASY-E4-AC-8RE1P

Eaton Moeller® series EASY I/O expansion, For use with easyE4, 100 - 240 V AC, 110 - 220 V DC (cULus: 100-110 V DC)), Inputs/Outputs expansion (number) digital: 4, Push-In

Generelle specifikationer

Product Name
Eaton Moeller® series EASY I/O expansion
Catalog Number
197514
EAN
4015081940929
Product Length/Depth
58 mm
Product Height
90 mm
Product Width
36 mm
Product Weight
0.125 kg
Certifications
UL File No.: E205091
CE
UL hazardous location group A (acetylene)
UL hazardous location group C (ethylene)
UL hazardous location division 2
UL hazardous location group B (hydrogen)
UL hazardous location group D (propane)
UL hazardous location class I
cULus Ordinary Location
DNV
TAA00002HT
cULus Hazard Location
UL File No.: E523283
EN 61131-2
IEC 61131-2
EN IEC 61000-6-3
IEC 61000-6-3
EN IEC 61010-2-201
IEC 61010-2-201
UL 61010-1
UL 61010-2-201
CSA C22.2 No. 61010-1
CSA C22.2 No. 61010-2-201
UL 121201
CSA C22.2 No. 213
Model Code
EASY-E4-AC-8RE1P

Omgivelsesforhold, mekaniske

Drop and topple
50 mm Drop height, Drop to IEC/EN 60068-2-31
Height of fall (IEC/EN 60068-2-32) - max
0.3 m
Mounting position
Horizontal
Vertical
Shock resistance
15 g, Mechanical, acc. to IEC/EN61131-2, Half-sinusoidal shock 11 ms, 18 Impacts
Vibration resistance
8.4 - 150 Hz, 1 g constant acceleration
5 - 8.4 Hz, 3.5 mm constant amplitude
According to IEC/EN 61131-2

Kabel

Cable length
Digital inputs (AC): ≤ 40 m (unshielded)

Klimatiske miljøforhold

Air pressure
795 - 1080 hPa (operation)
Ambient operating temperature - max
55 °C
Ambient storage temperature - max
70 °C
Ambient operating temperature - min
-25 °C
Ambient storage temperature - min
-40 °C
Environmental conditions
Condensation: prevent with appropriate measures
Clearance in air and creepage distances according to EN 50178, EN 61010-2-201, UL61010-2-201, CSA-C22.2 NO. 61010-2-201
Relative humidity
5 - 95 % (IEC 60068-2-30, IEC 60068-2-78)

Kommunikation

Connection type
Push in terminals
LED indicator
Status indication of Power/RUN

Designverifikation

10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility.
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard's requirements.
10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of assemblies
Meets the product standard's requirements.
10.4 Clearances and creepage distances
Meets the product standard's requirements.
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9.2 Power-frequency electric strength
Is the panel builder's responsibility.
10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material
Is the panel builder's responsibility.
Equipment heat dissipation, current-dependent Pvid
1 W
Heat dissipation capacity Pdiss
0 W
Heat dissipation per pole, current-dependent Pvid
0 W
Static heat dissipation, non-current-dependent Pvs
3 W

Elektrisk nominel værdi

Power consumption
3 W
Power loss
8 VA
Rated breaking capacity
300000 Operations at AC-15, 250 V AC, 3 A (600 Ops./h)
200000 Operations at DC-13, L/R ≦ 150 ms, 24 V DC, 1 A (500 Ops./h)
Rated operational voltage
Power supply: 100 - 240 V AC (-15 %/+ 10 %)
Power supply: 100 - 240 V DC (-15 %/+ 10 %) (IEC)
Power supply: 100 - 110 V DC (-15 %/+ 10 %) (cULus)
Relay outputs: max. 300 V AC/DC
Inputs: shall be identical to the power supply voltage
Supply frequency
50/60 Hz (± 5%)
Supply voltage at AC, 50 Hz - max
264 VAC
Supply voltage at AC, 50 Hz - min
85 VAC
Supply voltage at DC - max
264 VDC
Supply voltage at DC - min
85 VDC
Uninterrupted current
1 A DC, at R 300 (UL/CSA)
10 A AC, at 240 V AC (UL/CSA)
8 A DC, at 24 V DC (UL/CSA)
5 A AC, max. thermal continuous current cos ϕ = 1 at B 300 (UL/CSA)

Elektromagnetisk kompatibilitet

Air discharge
8 kV
Burst impulse
2 kV, I/O port
2 kV, Power supply port
According to IEC/EN 61131-2
Contact discharge
6 kV
Electromagnetic fields
10 V/m at 0.08 - 1.0 GHz (according to IEC/EN 61131-2)
3 V/m at 1.0 - 6 GHz (according to IEC/EN 61131-2)
Immunity to line-conducted interference
10 V (according to IEC/EN 61131-2)
Radio interference class
Class B (EN 61000-6-3)
Surge rating
1 kV, Line-to-Line, Power supply port
2 kV, Line-to-Earth, Power supply port
1 kV, Line-to-Line, Input port
2 kV, Line-to-Earth, Input port
According to IEC/EN 61131-2
Voltage dips
10 ms at 100 V DC
20 ms at 100 V AC

Features & functions

Features
Expandable
Expansion device
Fitted with:
Relay output
Indication
Software used as status indication of digital I/Os

Generelle oplysninger

Degree of protection
IP20
Duty factor
100 %
Input frequency
50/60 Hz (Digital inputs at AC)
Insulation resistance
According to EN IEC 61010-2-201, UL61010-2-201, CSA-C22.2 NO. 61010-2-218
Lifespan, electrical
25,000 Operations (Fluorescent lamp load 1 x 58 W at 230/240 V AC, conventional, compensated)
25,000 Operations (Fluorescent lamp load 10 x 58 W at 230/240 V AC, with upstream electrical device)
25,000 Operations (Fluorescent lamp load 10 x 58 W at 230/240 V AC, uncompensated)
25,000 Operations (Filament bulb load at 500 W, 115/120 V AC)
25,000 Operations (Filament bulb load at 1000 W, 230/240 V AC)
Lifespan, mechanical
10,000,000 Operations
Mounting method
Rail mounting possible
Front build in possible
Screw fixing using fixing brackets ZB4-101-GF1 (accessories)
Top-hat rail fixing (according to IEC/EN 60715, 35 mm)
Wall mounting/direct mounting
Overvoltage category
Power supply + Inputs + Right extension interface: III
Relay outputs: III
Left extension interface: III
Pollution degree
2
Product category
Control relays easyE4
Protection
B16 circuit breaker or 8 A (T) fuse, Protection of an Output relay
Rated impulse withstand voltage (Uimp)
Relay outputs: 6 kV (contact-coil)
Residual ripple
Power supply: ≤ 5 %
Software
EASYSOFT-SWLIC/easySoft
Switching frequency
0.5 Hz, Inductive load, Relay outputs
10 Hz, Relay outputs
2 Hz, Resistive load/lamp load, Relay outputs
Type
easyE4 extension
Used with
easyE4
Utilization category
B 300 Light Pilot Duty, UL/CSA Control Circuit Rating Codes AC
R 300 Light Pilot Duty, UL/CSA Control Circuit Rating Codes DC
Voltage type
AC/DC

Indgang/udgang

Delay time
Digital inputs (100 - 240 V DC): 0.5 ms typ., from 0 to 1
Digital inputs (100 - 240 V DC): 0.5 ms typ., from 1 to 0
Digital inputs (100 - 240 V AC 50 Hz): 25 ms typ., from 0 to 1
Digital inputs (100 - 240 V AC 50 Hz): 25 ms typ., from 1 to 0
Digital inputs (100 - 240 V AC 60 Hz): 21 ms typ., from 0 to 1
Digital inputs (100 - 240 V AC 60 Hz): 21 ms typ., from 1 to 0
Input current
4 x 0.25 mA (I1 - I4, at 115 V AC, 60 Hz, at signal 1)
4 x 0.5 mA (I1 - I4, at 230 VAC, 50 Hz, at signal 1)
Input voltage
Condition 0: 0 - 40 V AC/DC (Digital inputs)
Condition 1: 79 - 264 V AC/DC (Digital inputs)
Making/breaking capacity
28/28 VA (DC, at R 300)
3600/360 VA (AC, at B 300)
Number of inputs (analog)
0
Number of inputs (digital)
4
Number of outputs (analog)
0
Number of outputs (digital)
4
Output
4 Relay Outputs
min. recommended load: 12 V AC/DC > 500 mA
Parallel switching
Not permitted

Sikkerhed

Explosion safety category for dust
None
Explosion safety category for gas
None
Potential isolation
Power supply + Inputs + right Extension interface against Outputs: yes
POW+Inputs+right Extension interface vs. left Extension interface: yes
Outputs against left Extension interface: yes
Outputs against each other: yes
Protection against polarity reversal
Yes
Safe isolation
Relay outputs: 300 V AC, Between two contacts
Relay outputs: 300 V AC, Between coil and contact

Nominel kortslutningsværdi

Short-circuit protection
≥ 1A (T), Fuse, Power supply

Terminalkapaciteter

Terminal capacity
0.2 - 2.5 mm² (22 - 12 AWG), flexible with ferrule
0.2 - 2.5 mm², solid
0.2 - 2.5 mm², flexible
0.25 - 1,5 mm², solid or flexible with ferrule
AWG 24 - 14, solid or stranded

Eksportér produktspecifikation

Serial Number Verified :
Authenticated:
The product is verified as being authentic; however, this does not guarantee the condition or fit for purpose of the product.

Godkend produkt

Indtast dit 16-17-cifrede serienummer
Det serienummer, du har indtastet, må ikke indeholde specialtegn. Det serienummer, du indtastede, er ikke korrekt, det skal være 16- eller 17-cifret. Det serienummer, du indtastede, blev ikke fundet. Prøv igen, eller rapportér dette problem for yderligere hjælp. Det serienummer, du har indtastet, matcher ikke med produktet. Kontrollér dit produkts serienummer, og prøv igen. Klik på her for at gå til produktsiden for det serienummer, du har indtastet Serienummeret er kendt af Eaton for at være mistænkeligt, prøv igen eller rapportér dette problem for yderligere hjælp.
Serienummer
Nulstil Serienummeret er kendt af Eaton for at være mistænkeligt, prøv igen eller rapportér dette problem for yderligere hjælp. Serienummeret genkendes ikke af Eaton og er ugyldigt. Brug denne formular til at rapportér dette problem for yderligere hjælp.
Indtast den 6-cifrede godkendelseskode
Det produkt, du indtastede, er mistænkeligt! Prøv igen, eller rapportér dette problem for yderligere hjælp. Den godkendelseskode, du indtaster, matcher ikke med vores oplysninger for dette serienummer. Prøv igen, eller rapportér dette problem for yderligere hjælp. Ugyldig godkendelseskode. Den skal være på seks tegn rapportér dette problem for yderligere hjælp. Godkendelseskode er påkrævet rapportér dette problem for yderligere hjælp.
Løs Captcha-udfordringen inden godkendelse.
Kontakt os for at rapportere problem
x
Rapportér et problem
Indtast dit fulde navn.
x
Tak, dit problem er blevet indsendt, og vores produktteam vil kontakte dig snarest.

Register Product

Please complete the form to register your product