Billedet er repræsentativt
Download
Eaton Moeller series NZM Undervoltage release, 110-130VAC, +2early N/O, for NZM1
| Product Name |
Eaton Moeller series NZM Undervoltage release
|
| Catalog Number |
259537
|
| EAN |
4015082595371
|
| Product Length/Depth |
37 mm
|
| Product Height |
66 mm
|
| Product Width |
32 mm
|
| Product Weight |
0.084 kg
|
| Compliances |
IEC
UL/CSA RoHS conform |
| Certifications |
UL (File No. E140305)
CSA certified UL (Category Control Number DIHS) IEC60947 CSA-C22.2 No. 5-09 UL listed CSA (File No. 22086) UL489 CE marking CSA (Class No. 1437-01) |
| Model Code |
NZM1-XUHIV110-130AC
|
| Type |
|
| Special features |
|
| Frame |
NZM1
|
| Fitted with: |
Two early-make auxiliary contacts
|
| Suitable for |
Off-load switch
|
| Used with |
NZM1(-4), N(S)1(-4)
|
| Rated control supply voltage |
110 - 130 V 50/60 Hz
|
| Rated control supply voltage (Us) at AC, 50 Hz - min |
110 V
|
| Rated control supply voltage (Us) at AC, 50 Hz - max |
130 V
|
| Rated control supply voltage (Us) at AC, 60 Hz - min |
110 V
|
| Rated control supply voltage (Us) at AC, 60 Hz - max |
130 V
|
| Voltage tolerance - min |
0.85
|
| Voltage tolerance - max |
1.1
|
| Drop-out voltage of undervoltage release AC/DC - min |
0.35 x Us
|
| Drop-out voltage of undervoltage release AC/DC - max |
0.7 x Us
|
| Power consumption |
0.8 W (sealing DC)
1.5 VA (sealing AC) |
| Pick-up power consumption at AC (undervoltage release) |
1.5 VA
|
| Pick-up power consumption at DC (undervoltage release) |
0.8 W
|
| Reaction time |
19 ms
|
| Minimum command time - min |
10 ms
|
| Minimum command time - max |
15 ms
|
| Electric connection type |
Screw connection
|
| Voltage type |
AC
|
| Rated control voltage (relay contacts) |
110 V AC
130 V AC |
| Rated control supply voltage |
110 - 130 V 50/60 Hz
|
| Rated control supply voltage (Us) at AC, 50 Hz - min |
110 V
|
| Rated control supply voltage (Us) at AC, 50 Hz - max |
130 V
|
| Rated control supply voltage (Us) at AC, 60 Hz - min |
110 V
|
| Rated control supply voltage (Us) at AC, 60 Hz - max |
130 V
|
| Voltage tolerance - min |
0.85
|
| Voltage tolerance - max |
1.1
|
| Drop-out voltage of undervoltage release AC/DC - min |
0.35 x Us
|
| Drop-out voltage of undervoltage release AC/DC - max |
0.7 x Us
|
| Power consumption |
0.8 W (sealing DC)
1.5 VA (sealing AC) |
| Pick-up power consumption at AC (undervoltage release) |
1.5 VA
|
| Pick-up power consumption at DC (undervoltage release) |
0.8 W
|
| Reaction time |
19 ms
|
| Minimum command time - min |
10 ms
|
| Minimum command time - max |
15 ms
|
| Electric connection type |
Screw connection
|
| Number of contacts (change-over contacts) |
0
|
| Number of contacts (normally closed contacts) |
0
|
| Number of contacts (normally open contacts) |
2
|
| Connection type |
With terminal block on the left-hand switch side
|