Billedet er repræsentativt
Download
Eaton Moeller series NZM Undervoltage release, 24VDC, +2early N/O
Product Name |
Eaton Moeller series NZM Undervoltage release
|
Catalog Number |
259659
|
EAN |
4015082596590
|
Product Length/Depth |
42 mm
|
Product Height |
90 mm
|
Product Width |
30 mm
|
Product Weight |
0.132 kg
|
Compliances |
IEC
UL/CSA RoHS conform |
Certifications |
IEC60947
UL (File No. E140305) CE marking CSA (File No. 22086) CSA-C22.2 No. 5-09 UL (Category Control Number DIHS) UL listed CSA certified CSA (Class No. 1437-01) UL489 |
Model Code |
NZM2/3-XUHIV2024DC
|
Type |
Accessory
Undervoltage release
Undervoltage release with early-make auxiliary contact
|
Special features |
Undervoltage release with 2 early-make auxiliary contacts, e.g., for early-make connection of undervoltage release in main switch applications, as well as for interlock and load shedding circuits.
For use with emergency-stop devices in connection with an emergency-stop button.
When the under-voltage trip is switched off, accidental contact with the circuit breaker’s primary contacts is prevented when switched on.
Early make of auxiliary contacts on switching on and off (manual operation): approx. 20 ms
Cannot be used in conjunction with NZM...-XR... remote operator.
Undervoltage releases cannot be installed simultaneously with NZM...-XHIV... early-make auxiliary contact or NZM...-XA... shunt release.
|
Frame |
NZM2/3
|
Fitted with: |
Two separate early-make auxiliary contacts
|
Suitable for |
Off-load switch
|
Used with |
NZM2(-4), N(S)2(-4)
NZM3(-4), N(S)3(-4) |
Rated control supply voltage |
24 V DC
|
Rated control supply voltage (Us) at AC, 50 Hz - min |
0 V
|
Rated control supply voltage (Us) at AC, 50 Hz - max |
0 V
|
Rated control supply voltage (Us) at AC, 60 Hz - min |
0 V
|
Rated control supply voltage (Us) at AC, 60 Hz - max |
0 V
|
Rated control supply voltage (Us) at DC - min |
24 V
|
Rated control supply voltage (Us) at DC - max |
24 V
|
Voltage tolerance - min |
.85
|
Voltage tolerance - max |
1.1
|
Drop-out voltage of undervoltage release AC/DC - min |
0.35 x Us
|
Drop-out voltage of undervoltage release AC/DC - max |
0.7 x Us
|
Power consumption |
1.5 VA (sealing AC)
0.8 W (sealing DC) |
Pick-up power consumption at AC (undervoltage release) |
1.5 VA
|
Pick-up power consumption at DC (undervoltage release) |
0.8 W
|
Reaction time |
19 ms
|
Minimum command time - min |
10 ms
|
Minimum command time - max |
15 ms
|
Electric connection type |
Screw connection
|
Voltage type |
DC
|
Rated control voltage (relay contacts) |
24 V DC
|
Rated control supply voltage |
24 V DC
|
Rated control supply voltage (Us) at AC, 50 Hz - min |
0 V
|
Rated control supply voltage (Us) at AC, 50 Hz - max |
0 V
|
Rated control supply voltage (Us) at AC, 60 Hz - min |
0 V
|
Rated control supply voltage (Us) at AC, 60 Hz - max |
0 V
|
Rated control supply voltage (Us) at DC - min |
24 V
|
Rated control supply voltage (Us) at DC - max |
24 V
|
Voltage tolerance - min |
.85
|
Voltage tolerance - max |
1.1
|
Drop-out voltage of undervoltage release AC/DC - min |
0.35 x Us
|
Drop-out voltage of undervoltage release AC/DC - max |
0.7 x Us
|
Power consumption |
1.5 VA (sealing AC)
0.8 W (sealing DC) |
Pick-up power consumption at AC (undervoltage release) |
1.5 VA
|
Pick-up power consumption at DC (undervoltage release) |
0.8 W
|
Reaction time |
19 ms
|
Minimum command time - min |
10 ms
|
Minimum command time - max |
15 ms
|
Electric connection type |
Screw connection
|
Number of contacts (change-over contacts) |
0
|
Number of contacts (normally closed contacts) |
0
|
Number of contacts (normally open contacts) |
2
|
Connection type |
Contacts 3.23 and 3.24 with separate 3 m connection cables
|