Eaton Moeller® series DILM Paralleling link, for DILM17-32
| Product Name |
Eaton Moeller® series DILM paralleling link
|
| Catalog Number |
281194
|
| EAN |
4015082811945
|
| Product Length/Depth |
43 mm
|
| Product Height |
42 mm
|
| Product Width |
33 mm
|
| Product Weight |
0.055 kg
|
| Certifications |
IEC/EN 60947-4-1
CSA-C22.2 No. 14-05 UL 508 UL File No.: E29096 CSA File No.: 012528 CE CSA Class No.: 3211-03 UL Category Control No.: NLDX CSA UL |
| Catalog Notes |
AC1 current carrying capacity of the open contactor increases by a factor of 2.5
|
| Model Code |
DILM32-XP1
|
| Accessory/spare part type |
Connecting bridge
|
| Product category |
Accessories
|
| Protection |
Protected against accidental contact in accordance to VDE 0106 part 100
|
| Ambient operating temperature - min |
-25 °C
|
| Ambient operating temperature - max |
60 °C
|
| Terminal capacity |
1 x (16 - 50) mm²
1 x (16 - 35) mm² 16 mm², solid |
| Screwdriver size |
2, Terminal screw, Pozidriv screwdriver
|
| Tightening torque |
4 Nm, Screw terminal
|
| Short-circuit current rating (basic rating) |
5 kA, SCCR (UL/CSA)
125 A, max. Fuse, SCCR (UL/CSA) 125 A, max. CB, SCCR (UL/CSA) |
| Short-circuit current rating (high fault at 480 V) |
10/100 kA, Fuse, SCCR (UL/CSA)
10/65 kA, CB, SCCR (UL/CSA) 50/32 A, max. CB, SCCR (UL/CSA) 125/70 A, Class J, max. Fuse, SCCR (UL/CSA) |
| Short-circuit current rating (high fault at 600 V) |
10/22 kA, CB, SCCR (UL/CSA)
125/125 A, Class J, max. Fuse, SCCR (UL/CSA) 10/100 kA, Fuse, SCCR (UL/CSA) 50/32 A, max. CB, SCCR (UL/CSA) |
| Conventional thermal current Ith of main contacts (1-pole, open) |
100 A
|
| Equipment heat dissipation, current-dependent Pvid |
0.3 W
|
| Heat dissipation capacity Pdiss |
0 W
|
| Heat dissipation per pole, current-dependent Pvid |
0.1 W
|
| Rated operational current for specified heat dissipation (In) |
115 A
|
| Static heat dissipation, non-current-dependent Pvs |
0 W
|
| 10.2.2 Corrosion resistance |
Meets the product standard's requirements.
|
| 10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard's requirements.
|
| 10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard's requirements.
|
| 10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects |
Meets the product standard's requirements.
|
| 10.2.4 Resistance to ultra-violet (UV) radiation |
Meets the product standard's requirements.
|
| 10.2.5 Lifting |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.2.6 Mechanical impact |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.2.7 Inscriptions |
Meets the product standard's requirements.
|
| 10.3 Degree of protection of assemblies |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.4 Clearances and creepage distances |
Meets the product standard's requirements.
|
| 10.5 Protection against electric shock |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.6 Incorporation of switching devices and components |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.7 Internal electrical circuits and connections |
Is the panel builder's responsibility.
|
| 10.8 Connections for external conductors |
Is the panel builder's responsibility.
|
| 10.9.2 Power-frequency electric strength |
Is the panel builder's responsibility.
|
| 10.9.3 Impulse withstand voltage |
Is the panel builder's responsibility.
|
| 10.9.4 Testing of enclosures made of insulating material |
Is the panel builder's responsibility.
|
| 10.10 Temperature rise |
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
|
| 10.11 Short-circuit rating |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
| 10.12 Electromagnetic compatibility |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
| 10.13 Mechanical function |
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
|