Eaton Moeller series xPole - mRB64/M4 RCBO - residual-current circuit breaker with overcurrent protection. MCB/RCD, 13 A_x, 100mA, MCB trip type C, 3p, RCCB trip type: A
Product Name |
Eaton Moeller series xPole - mRB64/M4 RCBO - residual-current circuit breaker with overcurrent protection
|
Catalog Number |
169588
|
Model Code |
mRBM4-13/3/C/01-A-UK-PT
|
EAN |
4015081660827
|
Product Length/Depth |
86 mm
|
Product Height |
75 mm
|
Product Width |
73 mm
|
Product Weight |
0.43 kg
|
Compliances |
CE Marked
RoHS conform |
Certifications |
CE
|
Application |
Switchgear for residential and commercial applications
|
Product range |
mRBM4-UK-PT
|
Basic function |
Combined RCD/MCB devices
|
Number of poles |
Three-pole
|
Number of poles (protected) |
3
|
Number of poles (total) |
3
|
Tripping characteristic |
C
|
Release characteristic |
C
|
Rated current |
13 A
|
Fault current rating |
0.1 A
|
Sensitivity type |
Type A, pulse-current sensitive
|
Type |
RCBO
|
Voltage type |
AC
|
Voltage rating |
230 V
|
Rated operational voltage (Ue) - max |
415 V
|
Rated insulation voltage (Ui) |
440 V
|
Rated impulse withstand voltage (Uimp) |
4 kV
|
Impulse withstand current |
Partly surge-proof, 250 A
|
Frequency rating |
50 Hz
|
Leakage current type |
A
|
Rated switching capacity |
10 kA
|
Rated switching capacity (IEC/EN 61009) |
10 kA
|
Rated short-circuit breaking capacity (EN 60947-2) |
0 kA
|
Rated short-circuit breaking capacity (EN 61009) |
10 kA
|
Rated short-circuit breaking capacity (EN 61009-1) |
10 kA
|
Rated short-circuit breaking capacity (IEC 60947-2) |
0 kA
|
Surge current capacity |
250 kA
|
Disconnection characteristic |
Undelayed
|
Tripping |
Non-delayed
|
Overvoltage category |
III
|
Pollution degree |
2
|
Width in number of modular spacings |
4
|
Built-in depth |
69.5 mm
|
Mounting Method |
DIN rail
|
Degree of protection |
IP20
|
Connectable conductor cross section (solid-core) - min |
1 mm²
|
Connectable conductor cross section (solid-core) - max |
25 mm²
|
Connectable conductor cross section (multi-wired) - min |
1 mm²
|
Connectable conductor cross section (multi-wired) - max |
25 mm²
|
Rated operational current for specified heat dissipation (In) |
13 A
|
Heat dissipation per pole, current-dependent |
0 W
|
Equipment heat dissipation, current-dependent |
9.4 W
|
Static heat dissipation, non-current-dependent |
0 W
|
Heat dissipation capacity |
0 W
|
Ambient operating temperature - min |
-25 °C
|
Ambient operating temperature - max |
40 °C
|
Current limiting class |
3
|
Support from Eaton
Need product support?
Phone: +44 (0) 1753 608 700 - option 3, then option 1