Eaton Moeller® series DILM Auxiliary contact module, 2 pole, Ith= 10 A, 1 N/O, 1 NC, Side mounted, Spring-loaded terminals, DILM40 - DILM225A
Product Name |
Eaton Moeller® series DILM auxiliary contact module
|
Catalog Number |
278428
|
Model Code |
DILM1000-XHIC11-SI
|
EAN |
4015082784287
|
Product Length/Depth |
77 mm
|
Product Height |
77 mm
|
Product Width |
15 mm
|
Product Weight |
0.037 kg
|
Certifications |
CSA
VDE 0660 CSA-C22.2 No. 14-05 IEC/EN 60947-4-1 CE UL CSA Class No.: 3211-04 CSA File No.: 012528 UL 508 UL Category Control No.: NKCR UL File No.: E29184 IEC/EN 60947 |
Features |
Interlocked opposing contacts within an auxiliary contact module (according to IEC 60947-5-1 Annex L)
|
Functions |
For standard applications
|
Fitted with: |
Interlocked opposing contacts
|
Number of poles |
Two-pole
|
Electric connection type |
Spring clamp connection
|
Lifespan, electrical |
1,300,000 Operations (at 230 V, AC-15, 3 A)
|
Model |
Top mounting
|
Mounting method |
Side mounting
|
Overvoltage category |
III
|
Pollution degree |
3
|
Protection |
Finger and back-of-hand proof, Protection against direct contact when actuated from front (EN 50274)
|
Rated impulse withstand voltage (Uimp) |
6000 V
6000 V AC |
Type |
Side-mounting auxiliary contacts
|
Ambient operating temperature - min |
-25 °C
|
Ambient operating temperature - max |
60 °C
|
Ambient operating temperature (enclosed) - min |
-25 °C
|
Ambient operating temperature (enclosed) - max |
40 °C
|
Ambient storage temperature - min |
-40 °C
|
Ambient storage temperature - max |
80 °C
|
Climatic proofing |
Damp heat, constant, to IEC 60068-2-78
Damp heat, cyclic, to IEC 60068-2-30 |
Terminal capacity (flexible with ferrule) |
1 x (1 - 2.5) mm²
2 x (1 - 2.5) mm² |
Terminal capacity (solid) |
2 x (1 - 2.5) mm²
1 x (1 - 2.5) mm² |
Terminal capacity (solid/stranded AWG) |
16 - 14
|
Screwdriver size |
0.6 x 3.5 mm, Spring-loaded terminals
|
Rated operational current (Ie) at AC-15, 220 V, 230 V, 240 V |
6 A
|
Rated operational current (Ie) at AC-15, 380 V, 400 V, 415 V |
4 A
|
Rated operational current (Ie) at AC-15, 500 V |
1.5 A
|
Rated operational current (Ie) at DC-13, 24 V |
2 A
|
Rated operational current (Ie) at DC-13, 60 V |
1.5 A
|
Rated operational current (Ie) at DC-13, 110 V |
0.8 A
|
Rated operational current (Ie) at DC-13, 220 V, 230 V |
0.3 A
|
Rated insulation voltage (Ui) |
690 V
|
Rated operational voltage (Ue) at AC - max |
500 V
|
Rated conditional short-circuit current (Iq) |
1 kA at 500 V
|
Short-circuit protection rating |
Max. 16 A gG/gL, Fuse, Without welding, Auxiliary contacts
|
Short-circuit protection rating without welding |
16 A gG/gL, 500 V, Max. Fuse, Contacts
|
Switching capacity (auxiliary contacts, general use) |
1 A, 250 V DC, (UL/CSA)
15 A, 600 V AC, (UL/CSA) |
Switching capacity (auxiliary contacts, pilot duty) |
A600, AC operated (UL/CSA)
P300, DC operated (UL/CSA) |
Control circuit reliability |
λ < 5 x 1/10⁷ (1 failure at 2,000,000 operations for Uₑ = 24 V DC, Umin = 17 V, Imin = 5.4 mA)
|
Number of contacts (change-over contacts) |
0
|
Number of contacts (normally closed contacts) |
1
|
Number of contacts (normally open contacts) |
1
|
Safe isolation |
440 V AC, Between coil and auxiliary contacts, According to EN 61140
440 V AC, Between auxiliary contacts, According to EN 61140 |
Equipment heat dissipation, current-dependent Pvid |
0 W
|
Heat dissipation capacity Pdiss |
0 W
|
Rated operational current for specified heat dissipation (In) |
4 A
|
10.2.2 Corrosion resistance |
Meets the product standard's requirements.
|
10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard's requirements.
|
10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard's requirements.
|
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects |
Meets the product standard's requirements.
|
10.2.4 Resistance to ultra-violet (UV) radiation |
Meets the product standard's requirements.
|
10.2.5 Lifting |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.6 Mechanical impact |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.7 Inscriptions |
Meets the product standard's requirements.
|
10.3 Degree of protection of assemblies |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.4 Clearances and creepage distances |
Meets the product standard's requirements.
|
10.5 Protection against electric shock |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.6 Incorporation of switching devices and components |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.7 Internal electrical circuits and connections |
Is the panel builder's responsibility.
|
10.8 Connections for external conductors |
Is the panel builder's responsibility.
|
10.9.2 Power-frequency electric strength |
Is the panel builder's responsibility.
|
10.9.3 Impulse withstand voltage |
Is the panel builder's responsibility.
|
10.9.4 Testing of enclosures made of insulating material |
Is the panel builder's responsibility.
|
10.10 Temperature rise |
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
|
10.11 Short-circuit rating |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
10.12 Electromagnetic compatibility |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
10.13 Mechanical function |
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
|