A fotó reprezentatív
                                
                                
                                    
                                    Download
                                
                                
                                Eaton DS7 Soft starter, 32 A, 200 - 480 V AC, 24 V DC, Frame size: FS2, Communication Interfaces: SmartWire-DT
| Product Name | 
                                                Eaton DS7 Soft starter
                                             | 
| Catalog Number | 
                                                134950
                                             | 
| EAN | 
                                                4015081317653
                                             | 
| Product Length/Depth | 
                                                126 mm
                                             | 
| Product Height | 
                                                150 mm
                                             | 
| Product Width | 
                                                45 mm
                                             | 
| Product Weight | 
                                                0.4 kg
                                             | 
| Certifications | 
                                                IEC/EN 60947-4-2  UL 508 CSA-C22.2 No 14-05 CSA CSA-C22.2 No 0-M91 GB 14048.6 UkrSEPRO CSA22.2-14 UL C-Tick CE | 
| Model Code | 
                                                DS7-34DSX032N0-D
                                             | 
| Fault memory | 
                                                8 Faults
                                             | 
| Fitted with: | 
                                                Internal bypass  Internal bypass contacts | 
| Functions | 
                                                Current limitation, with PKE  Min. ramp time 1 s - fast switching (semiconductor contactor) Suppression of closing transients Soft start function Potential isolation between power and control sections Single direction Suppression of DC components for motors | 
| Interfaces | 
                                                SmartWire-DT (built-in)
                                             | 
| Class | 
                                                Other
                                             | 
| Connection to SmartWire-DT | 
                                                Yes
                                             | 
| Degree of protection | 
                                                NEMA 1  IP20 | 
| Frame size | 
                                                FS2
                                             | 
| Mains voltage - min | 
                                                200 V
                                             | 
| Mains voltage - max | 
                                                480 V
                                             | 
| Overvoltage category | 
                                                II
                                             | 
| Pollution degree | 
                                                2
                                             | 
| Product category | 
                                                SmartWire-DT slave
                                             | 
| Product category | 
                                                SmartWire-DT slave
                                             | 
| Radio interference class | 
                                                Class B (EN 55011)
                                             | 
| Suitable for | 
                                                Branch circuits, (UL/CSA)
                                             | 
| Type | 
                                                Soft starter for three-phase loads
                                             | 
| Voltage type | 
                                                DC
                                             | 
| Mounting position | 
                                                Vertical
                                             | 
| Shock resistance | 
                                                8 g, 11 ms, Mechanical
                                             | 
| Vibration resistance | 
                                                2M2 to EN 60721-3-2
                                             | 
| Altitude | 
                                                Above 1000 m with 1 % derating per 100 m  Max. 2000 m | 
| Ambient operating temperature - min | 
                                                -5 °C
                                             | 
| Ambient operating temperature - max | 
                                                40 °C
                                             | 
| Ambient storage temperature - min | 
                                                -25 °C
                                             | 
| Ambient storage temperature - max | 
                                                60 °C
                                             | 
| Climatic proofing | 
                                                Damp heat, cyclic, to IEC 60068-2-30  Damp heat, constant, to IEC 60068-2-3 | 
| Overload cycle | 
                                                AC-53a: 3 - 5: 75 - 10
                                             | 
| Rated operational current (Ie) at AC-53 | 
                                                32 A
                                             | 
| Rated operational voltage (Ue) - min | 
                                                230 V
                                             | 
| Rated operational voltage (Ue) - max | 
                                                480 V
                                             | 
| Short-circuit protection rating | 
                                                3 x 170M1366, Type „2“ coordination (additional with the fuses for coordination type „1“), Main conducting paths  PKM0-32 (+ CL-PKZ0), Type “1” coordination, Main conducting paths | 
| Supply frequency | 
                                                50/60 Hz, fLN, Main circuit
                                             | 
| Voltage rating - max | 
                                                480 V
                                             | 
| Assigned motor power at 200/208 V, 60 Hz, 3-phase | 
                                                10 HP
                                             | 
| Assigned motor power at 220/230 V, 60 Hz, 3-phase | 
                                                10 HP
                                             | 
| Assigned motor power at 460/480 V, 60 Hz, 3-phase | 
                                                25 HP
                                             | 
| Rated operational power at 220/230 V, 50 Hz | 
                                                7.5 kW
                                             | 
| Rated operational power at 400 V, 50 Hz | 
                                                15 kW
                                             | 
| Terminal capacity (flexible with ferrule) | 
                                                2 x (0.5 - 0.75) mm², Control circuit cables  1 x (0.5 - 1.5) mm², Control circuit cables 1 x (0.75 - 16) mm², Main cables 2 x (0.75 - 10) mm², Main cables | 
| Terminal capacity (solid) | 
                                                2 x (0.5 - 1.0) mm², Control circuit cables  1 x (0.75 - 16) mm², Main cables 2 x (0.75 - 10) mm², Main cables 1 x (0.5 - 2.5) mm², Control circuit cables | 
| Terminal capacity (solid/stranded AWG) | 
                                                18 - 6, Main cables  18 - 14, Control circuit cables | 
| Terminal capacity (stranded) | 
                                                1 x 16 mm², Main cables
                                             | 
| Screwdriver size | 
                                                PZ2, 1 x 6 mm, Terminal screw, Standard screwdriver  0.6 x 5.5 mm/1 x 6 mm, Terminal screws, Control circuit cables | 
| Tightening torque | 
                                                3.2 Nm  1.2 Nm, Screw terminals, Control circuit cables | 
| Current consumption | 
                                                50 mA, Control circuit, Regulator supply  1.6 mA, Control circuit, Digital inputs, External 24 V | 
| Drop-out time | 
                                                350 ms, Control circuit, Digital Inputs, DC operated
                                             | 
| Drop-out voltage | 
                                                0 - 3 V, DC operated
                                             | 
| Pick-up time | 
                                                250 ms at DC
                                             | 
| Pick-up voltage | 
                                                17.3 - 27 V DC
                                             | 
| Rated control supply voltage (Us) at AC, 50 Hz - min | 
                                                0 V
                                             | 
| Rated control supply voltage (Us) at AC, 50 Hz - max | 
                                                0 V
                                             | 
| Rated control supply voltage (Us) at AC, 60 Hz - min | 
                                                0 V
                                             | 
| Rated control supply voltage (Us) at AC, 60 Hz - max | 
                                                0 V
                                             | 
| Rated control supply voltage (Us) at DC - min | 
                                                24 V
                                             | 
| Rated control supply voltage (Us) at DC - max | 
                                                24 V
                                             | 
| Number of outputs | 
                                                2 Relay Outputs (TOR, Ready)
                                             | 
| Output voltage | 
                                                250 V AC (relay outputs)
                                             | 
| Protection | 
                                                Finger and back-of-hand proof, Protection against direct contact
                                             | 
| Rated control voltage (Uc) | 
                                                24 V DC  24 V DC (-15 %/+10 %) or via SmartWire-DT | 
| Rated operational current (Ie) at AC-11 | 
                                                1 A
                                             | 
| Application | 
 | 
| Current limitation | 
                                                (0 - 8) x Ie, Soft start function
                                             | 
| Delay time | 
                                                0 - 30 s, Soft start function, Ramp times
                                             | 
| Ramp/run-up time | 
                                                1 - 30 s
                                             | 
| Start voltage | 
                                                Min. 30 %, Soft start function, Start voltage = turn-off voltage  Max. 100 %, Soft start function, Start voltage = turn-off voltage | 
| Equipment heat dissipation, current-dependent Pvid | 
                                                1.5 W
                                             | 
| Heat dissipation capacity Pdiss | 
                                                0 W
                                             | 
| Heat dissipation per pole, current-dependent Pvid | 
                                                0 W
                                             | 
| Rated operational current for specified heat dissipation (In) | 
                                                32 A
                                             | 
| Static heat dissipation, non-current-dependent Pvs | 
                                                1.5 W
                                             | 
| 10.2.2 Corrosion resistance | 
                                                Meets the product standard's requirements.
                                             | 
| 10.2.3.1 Verification of thermal stability of enclosures | 
                                                Meets the product standard's requirements.
                                             | 
| 10.2.3.2 Verification of resistance of insulating materials to normal heat | 
                                                Meets the product standard's requirements.
                                             | 
| 10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects | 
                                                Meets the product standard's requirements.
                                             | 
| 10.2.4 Resistance to ultra-violet (UV) radiation | 
                                                Meets the product standard's requirements.
                                             | 
| 10.2.5 Lifting | 
                                                Does not apply, since the entire switchgear needs to be evaluated.
                                             | 
| 10.2.6 Mechanical impact | 
                                                Does not apply, since the entire switchgear needs to be evaluated.
                                             | 
| 10.2.7 Inscriptions | 
                                                Meets the product standard's requirements.
                                             | 
| 10.3 Degree of protection of assemblies | 
                                                Does not apply, since the entire switchgear needs to be evaluated.
                                             | 
| 10.4 Clearances and creepage distances | 
                                                Meets the product standard's requirements.
                                             | 
| 10.5 Protection against electric shock | 
                                                Does not apply, since the entire switchgear needs to be evaluated.
                                             | 
| 10.6 Incorporation of switching devices and components | 
                                                Does not apply, since the entire switchgear needs to be evaluated.
                                             | 
| 10.7 Internal electrical circuits and connections | 
                                                Is the panel builder's responsibility.
                                             | 
| 10.8 Connections for external conductors | 
                                                Is the panel builder's responsibility.
                                             | 
| 10.9.2 Power-frequency electric strength | 
                                                Is the panel builder's responsibility.
                                             | 
| 10.9.3 Impulse withstand voltage | 
                                                Is the panel builder's responsibility.
                                             | 
| 10.9.4 Testing of enclosures made of insulating material | 
                                                Is the panel builder's responsibility.
                                             | 
| 10.10 Temperature rise | 
                                                The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
                                             | 
| 10.11 Short-circuit rating | 
                                                Is the panel builder's responsibility. The specifications for the switchgear must be observed.
                                             | 
| 10.12 Electromagnetic compatibility | 
                                                Is the panel builder's responsibility. The specifications for the switchgear must be observed.
                                             | 
| 10.13 Mechanical function | 
                                                The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
                                             |