Dokumentum letöltése () 20
Működésbe hozzuk az igazán fontos dolgokat.*

169144
Modellkód: DX-LN3-370

Eaton DX Main choke, three-phase, 550 V + 0% (50/60 Hz), V AC, 370 A, 0.05 mH

General specifications

Product Name
Eaton DX Mains choke
Catalog Number
169144
EAN
4015081656226
Product Length/Depth
400 mm
Product Height
500 mm
Product Width
600 mm
Product Weight
24.3 kg
Certifications
UL 508C
CSA
CSA-C22.2 No. 14
UL report applies to both US and Canada
UL File No.: E167225
UL
IEC/EN61800-5
CE
IEC/EN61800-3
UL Category Control No.: XPTQ2, XPTQ8
IEC/EN 61558-2-20-2000
VDE 0570 Part 2-20/2001-04
Certified by UL for use in Canada
Model Code
DX-LN3-370

Jellemzők és funkciók

Fitted with:
PE stud
Connection lugs
Number of phases
3
Number of poles
Three-pole

Általános

Bore diameter
14 mm
Degree of protection
IP20
NEMA Other
Duty factor
100 %
Insulation class
B
Product Category
Accessories
Suitable as
Net reactance coil
Suitable for
Branch circuits, (UL/CSA)
Switching frequency
3 kHz
Used with
DA1

Környezeti feltételek, mechanikai

Mounting position
Suspended horizontally
Standing vertically
Free surrounding areas > 50 mm
Shock resistance
Shock duration: 11 ms
3 shocks
Vibration resistance
0 - 150 Hz, 1 g
10 - 55 Hz, 0.35 mm

Éghajlati környezeti viszonyok

Altitude
Max. 5000 m with current reduction
Max. 1000 m
Ambient operating temperature - max
40 °C
Ambient operating temperature - min
-25 °C
Ambient storage temperature - max
85 °C
Ambient storage temperature - min
-25 °C
Operating temperature details
-25 - 40 °C (up to 70 °C with current derating)

Csatlakozások

Tightening torque
15.5 Nm, Screw terminals

Csatlakozás

Connection lug
Cu 40 x 5 mm²

Villamos besorolás

Permissible connection voltage
Max. 550 V AC (50/60 Hz)
Rated current (Ith) at rated voltage DC - max
0 A
Rated frequency - min
50 Hz
Rated frequency - max
60 Hz
Rated inductance
0.05 mH
Rated operational current (Ie) - min
370 A
Rated operational current (Ie) - max
370 A
Rated operational voltage (Ue) - max
550 V
Relative short-circuit voltage
0 %
Voltage rating - max
480 V
Voltage sag Uk
2.5 %

Konstrukcióigazolás

Equipment heat dissipation, current-dependent Pvid
290 W
Heat dissipation capacity Pdiss
0 W
Heat dissipation per pole, current-dependent Pvid
0 W
Rated operational current for specified heat dissipation (In)
370 A
Static heat dissipation, non-current-dependent Pvs
0 W
10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard's requirements.
10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of assemblies
Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances
Meets the product standard's requirements.
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9.2 Power-frequency electric strength
Is the panel builder's responsibility.
10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material
Is the panel builder's responsibility.
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.

Termékjellemzők exportja

Megjegyzés: Ha fájl(ok) hiányoznak a letöltött .zip csomagból, akkor az illető fájltípus nem támogatott tömeges letöltés esetén