Eaton Moeller® series U-PKZ0 Undervoltage release PKZ0(4), PKE, AC, 400 V 50 Hz, Screw terminals
Product Name |
Eaton Moeller® series U-PKZ0 Accessory Undervoltage Release
|
Catalog Number |
073138
|
EAN |
4015080731382
|
Product Length/Depth |
68 mm
|
Product Height |
90 mm
|
Product Width |
24 mm
|
Product Weight |
0.126 kg
|
Certifications |
CE
CSA Class No.: 3211-05 UL File No.: E36332 CSA UL 508 CSA File No.: 165628 CSA-C22.2 No. 14 UL Category Control No.: NLRV IEC/EN 60947-4-1 UL |
Model Code |
U-PKZ0(400V50HZ)
|
Used with |
Motor protective circuit-breaker
|
Suitable as |
EMERGENCY STOP or EMERGENCY switching-off device in accordance with IEC/EN 60204 when combined with circuit breaker
|
10.10 Temperature rise |
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
|
10.11 Short-circuit rating |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
10.12 Electromagnetic compatibility |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
10.13 Mechanical function |
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
|
10.2.2 Corrosion resistance |
Meets the product standard's requirements.
|
10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard's requirements.
|
10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard's requirements.
|
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects |
Meets the product standard's requirements.
|
10.2.4 Resistance to ultra-violet (UV) radiation |
Meets the product standard's requirements.
|
10.2.5 Lifting |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.6 Mechanical impact |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.7 Inscriptions |
Meets the product standard's requirements.
|
10.3 Degree of protection of assemblies |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.4 Clearances and creepage distances |
Meets the product standard's requirements.
|
10.5 Protection against electric shock |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.6 Incorporation of switching devices and components |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.7 Internal electrical circuits and connections |
Is the panel builder's responsibility.
|
10.8 Connections for external conductors |
Is the panel builder's responsibility.
|
10.9.2 Power-frequency electric strength |
Is the panel builder's responsibility.
|
10.9.3 Impulse withstand voltage |
Is the panel builder's responsibility.
|
10.9.4 Testing of enclosures made of insulating material |
Is the panel builder's responsibility.
|
Electric connection type |
Screw connection
|
Rated control supply voltage (Us) at DC - max |
0 V
|
Rated control supply voltage (Us) at DC - min |
0 V
|
Rated operational current for specified heat dissipation (In) |
0 A
|
Rated operational voltage (Ue) at AC - max |
480 V
|
Rated operational voltage (Ue) at AC - min |
42 V
|
Rated operational voltage (Ue) at DC - max |
250 V
|
Rated operational voltage (Ue) at DC - min |
24 V
|
Static heat dissipation, non-current-dependent Pvs |
0.5 W
|
Product category |
Accessories
|
Ambient operating temperature - max |
55 °C
|
Ambient operating temperature - min |
-25 °C
|
Equipment heat dissipation, current-dependent Pvid |
0 W
|
Heat dissipation capacity Pdiss |
0 W
|
Heat dissipation per pole, current-dependent Pvid |
0 W
|
Number of contacts (change-over contacts) |
0
|
Number of contacts (normally closed contacts) |
0
|
Number of contacts (normally open contacts) |
0
|
Rated control supply voltage (Us) at AC, 50 Hz - max |
400 V
|
Rated control supply voltage (Us) at AC, 50 Hz - min |
400 V
|
Rated control supply voltage (Us) at AC, 60 Hz - max |
0 V
|
Rated control supply voltage (Us) at AC, 60 Hz - min |
0 V
|
Voltage type |
AC
|
Mounting position |
Can be fitted to left side of the motor protection switch
|
Suitable for |
Motor safety switch
|
Drop-out voltage |
0,7- 0,35 x Uc
|
Power consumption, pick-up, 50 Hz |
5 VA, Pull-in power, Coil in a cold state and 1.0 x Us
|
Power consumption, pick-up, 60 Hz |
5 VA, Pull-in power, Coil in a cold state and 1.0 x Us
|
Power consumption, sealing, 50 Hz |
3 VA, Coil in a cold state and 1.0 x Us
|
Power consumption, sealing, 60 Hz |
3 VA, Coil in a cold state and 1.0 x Us
|
Pick-up voltage |
0.85 - 1.1 V x Uc
|
Terminal capacity (solid/flexible with ferrule) |
1 x (0.75 - 2.5) mm²
2 x (0.75 - 2.5) mm² |
Terminal capacity (solid/stranded AWG) |
1 x (18 - 14)
2 x (18 - 14) |