Eaton Moeller® series CI-K Insulated enclosure, HxWxD=280x200x125mm, +mounting rail
Product Name |
Eaton Moeller® series CI-K Insulated enclosure
|
Catalog Number |
206891
|
EAN |
4015082068912
|
Product Length/Depth |
125 mm
|
Product Height |
280 mm
|
Product Width |
200 mm
|
Product Weight |
0.91 kg
|
Certifications |
DIN EN 62208
IEC 60068-2-11 IEC/EN 60529 UL94: HB UL94: VO/1.5 mm thickness |
Catalog Notes |
Lamp indicator L‐… can be mounted in base knock-out M20/M25
|
Model Code |
CI-K5-125-TS
|
Type |
Basic enclosure
|
Features |
Halogen free
UV resistance beneath protective shield |
10.10 Temperature rise |
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
|
10.11 Short-circuit rating |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
10.12 Electromagnetic compatibility |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
10.13 Mechanical function |
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
|
10.2.2 Corrosion resistance |
Meets the product standard's requirements.
|
10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard's requirements.
|
10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard's requirements.
|
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects |
Meets the product standard's requirements.
|
10.2.4 Resistance to ultra-violet (UV) radiation |
Please enquire
|
10.2.5 Lifting |
Not applicable.
|
10.2.6 Mechanical impact |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.7 Inscriptions |
Meets the product standard's requirements.
|
10.3 Degree of protection of assemblies |
Meets the product standard's requirements.
|
10.4 Clearances and creepage distances |
Meets the product standard's requirements.
|
10.5 Protection against electric shock |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.6 Incorporation of switching devices and components |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.7 Internal electrical circuits and connections |
Is the panel builder's responsibility.
|
10.8 Connections for external conductors |
Is the panel builder's responsibility.
|
10.9.2 Power-frequency electric strength |
Is the panel builder's responsibility.
|
10.9.3 Impulse withstand voltage |
Is the panel builder's responsibility.
|
10.9.4 Testing of enclosures made of insulating material |
Meets the product standard's requirements.
|
Fitted with: |
Mounting rail to IEC/EN 60715
Weight of fitted components: max. 0.65 kg Control cable entry |
Climatic proofing |
Damp heat, cyclic, to IEC 60068-2-30
Damp heat, constant, to IEC 60068-2-78 |
Enclosure material |
1 Ω x 10¹³ (Surface resistance to IEC 60093)
Plastic |
Ambient operating temperature - max |
70 °C
|
Ambient operating temperature - min |
-25 °C
|
Equipment heat dissipation, current-dependent Pvid |
0 W
|
Heat dissipation capacity Pdiss |
35 W
|
Heat dissipation per pole, current-dependent Pvid |
0 W
|
Mounting depth |
93 mm
|
Mounting weight capacity - max |
1 kg
|
Rated operational current for specified heat dissipation (In) |
0 A
|
Static heat dissipation, non-current-dependent Pvs |
0 W
|
Product category |
Empty enclosures
|
Enclosure color |
Light gray, Operator (RAL 7035)
Light gray, Cover (RAL 7035) Black (RAL 9005) |
Environmental resistance |
Not resistant to benzene
Resistant against greases Resistant against alkalis Chemical resistant (Push-through membrane (CI-K1/CI-K2) and sealing material) Resistant against mineral oil Partly resistant to alcohol Chemical resistant (Base, Cover) Partly resistant to greases Resistant against benzene Partly resistant to benzene Resistant against gasoline Resistant against acids (< 10%) Resistant against alcohol Resistant against salt solutions Partly resistant to acids (> 10%) Not resistant to alkalis Not resistant to Mineral oil |
Cover material |
Glass-fiber reinforced polycarbonate
|
Degree of protection |
IP65
NEMA Other |
Model |
Surface mounting
|
Dielectric strength |
30 kV/mm, according to IEC 60243-1
|
Degree of protection (front side) |
IP65
|
Temperature resistance |
-40 - 80 °C (gasket)
-40 - 120 °C (enclosure) |
Suitable for |
Emergency stop
|
Flammability characteristics |
960 °C/1 mm thickness (base, cover; glow wire to VDE 0471 Part 2)
650 °C/1 mm thick (push-through membrane) to VDE 0471 Part 2) |
Knockouts |
Hard knockout version
Metric cable entry knockouts at the top, bottom and back plate |
Impact resistance |
IK06 (according to EN 50102)
|
Radiated heat dissipation with separate mounting |
35 W (at an ambient temperature of 20 °C)
|
Surface treatment |
Resistant to corrosion
|
Track resistance |
CTI 175 (base, to IEC 60112)
CTI 175 (cover, to IEC 60112) |
Water consumption |
0.29 % (According to DIN EN ISO 62)
|