Eaton DM1 Variable frequency drive, 230 V AC, 3-phase, 32 A, 7.5 kW, IP20/NEMA0, Radio interference suppression filter, Brake chopper, FS4
Product Name |
Eaton DM1 Variable frequency drive
|
Catalog Number |
3-5023-003A
|
EAN |
4015081980284
|
Product Length/Depth |
195 mm
|
Product Height |
300 mm
|
Product Width |
184 mm
|
Product Weight |
6.3 kg
|
Certifications |
CUL
UkrSEPRO CSA-C22.2 No. 274-17 UL CE UL Listed IEC/EN61800-5 IEC/EN 61800-2 CE marking Certified by UL for use in Canada RoHS, ISO 9001 UL report applies to both US and Canada IEC/EN 61800-3 IEC/EN 61800-5-1 CSA-C22.2 No. 274-13 C-Tick UL File No.: E134360 UL Category Control No.: NMMS, NMMS7 UL 508C IEC/EN61800-3 EAC |
Model Code |
DM1-32032EB-N20B-EM
|
Product Category |
Variable frequency drives
|
Features |
Temperature-controlled fan
Parameterization: Fieldbus Parameterization: Keypad Parameterization: Power Xpert inControl |
10.10 Temperature rise |
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
|
10.11 Short-circuit rating |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
10.12 Electromagnetic compatibility |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
10.13 Mechanical function |
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
|
10.2.2 Corrosion resistance |
Meets the product standard's requirements.
|
10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard's requirements.
|
10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard's requirements.
|
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects |
Meets the product standard's requirements.
|
10.2.4 Resistance to ultra-violet (UV) radiation |
Meets the product standard's requirements.
|
10.2.5 Lifting |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.6 Mechanical impact |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.7 Inscriptions |
Meets the product standard's requirements.
|
10.3 Degree of protection of assemblies |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.4 Clearances and creepage distances |
Meets the product standard's requirements.
|
10.5 Protection against electric shock |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.6 Incorporation of switching devices and components |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.7 Internal electrical circuits and connections |
Is the panel builder's responsibility.
|
10.8 Connections for external conductors |
Is the panel builder's responsibility.
|
10.9.2 Power-frequency electric strength |
Is the panel builder's responsibility.
|
10.9.3 Impulse withstand voltage |
Is the panel builder's responsibility.
|
10.9.4 Testing of enclosures made of insulating material |
Is the panel builder's responsibility.
|
Fitted with: |
Radio interference suppression filter
IGBT inverter Internal DC link Brake chopper PC connection |
Pollution degree |
2
|
Climatic proofing |
< 95 average relative humidity (RH), no condensation, no corrosion
|
Connection to SmartWire-DT |
Yes
In conjunction with DXG-NET-SWD SmartWire DT module |
Operating mode |
U/f control
|
Frame size |
FS4
|
Air volume capacity |
129 m³/h
|
Altitude |
Max. 3000 m
Max. 2000 m for Corner Grounded TN Systems Max. 1000 m Above 1000 m with 1 % derating per 100 m |
Environmental class |
3C2, 3S2 (Air quality)
|
Application in domestic and commercial area permitted |
Yes
|
Mains switch-on frequency |
Maximum of one time every 60 seconds
|
Application in industrial area permitted |
Yes
|
Ambient operating temperature - max |
50 °C
|
Ambient operating temperature - min |
-10 °C
|
Ambient storage temperature - max |
70 °C
|
Ambient storage temperature - min |
-40 °C
|
Assigned motor current IM at 230 V, 50 Hz, 110% overload |
38 A
|
Assigned motor current IM at 230 V, 50 Hz, 150% overload |
26.4 A
|
Assigned motor current IM at 230 V, 60 Hz, 110% overload |
42 A
|
Mains voltage tolerance |
200 - 240 V (-15 %/+10 %, at 50/60 Hz)
|
Mounting position |
Vertical
|
Rated conditional short-circuit current (Iq) |
100 kA
|
Relative symmetric net frequency tolerance |
10 %
|
Relative symmetric net voltage tolerance |
10 %
|
Protection |
Finger and back-of-hand proof, Protection against direct contact (BGV A3, VBG4)
|
Resolution |
0.01 Hz (Frequency resolution, setpoint value)
|
Voltage rating - max |
240 V
|
Overvoltage category |
III
|
Communication interface |
Modbus RTU, built in
DeviceNet, optional PROFIBUS, optional SmartWire-DT, optional CANopen®, optional |
Converter type |
U converter
|
Degree of protection |
IP20
NEMA Other |
Protocol |
MODBUS
|
Assigned motor power at 230/240 V, 60 Hz, 1-phase |
10 HP
|
System configuration type |
TN-S, TN-C, TN-C-S, TT, IT
|
Electromagnetic compatibility |
1st and 2nd environments (according to EN 61800-3)
|
Assigned motor power at 230/240 V, 60 Hz, 3-phase, 110 % overload |
15 HP
|
Braking resistance |
6 Ω
|
Equipment heat dissipation, current-dependent Pvid |
432.4 W
|
Input current ILN at 110% overload |
53.1 A
|
Input current ILN at 150% overload |
35.4 A
|
Mains current distortion |
40 %
|
Current limitation |
0.1 - 2 x IH (CT), motor, main circuit
|
Number of slots |
1 (expansion)
|
Braking torque |
Max. 30 % MN, Standard - Main circuit
Max. 100 % of rated operational current Ie with external braking resistor - Main circuit Adjustable to 150 %, DC - Main circuit |
Cable length |
C2 ≤ 5 m, maximum motor cable length
C3 ≤ 25 m, maximum motor cable length |
Functions |
4-quadrant operation possible
|
Output voltage (U2) |
240 V AC, 3-phase
230 V AC, 3-phase |
Number of inputs (analog) |
1
|
Number of inputs (digital) |
4
|
Radio interference class |
C1: with external filter, for conducted emissions only
C2, C3: depending on the motor cable length, the connected load, and ambient conditions. External radio interference suppression filters (optional) may be necessary. Optional external radio interference suppression filter for longer motor cable lengths and for use in different EMC environments |
Number of outputs (digital) |
0
|
Starting current - max |
200 %, IH, max. starting current (High Overload), For 2 seconds every 20 seconds, Power section
|
Number of phases (input) |
3
|
Number of relay outputs |
2 (parameterizable, 1 changeover contact and 1 N/O, 3 A (240 V AC) / 3 A (24 V DC))
|
Number of phases (output) |
3
|
Power consumption |
432.4 W
|
Rated control supply voltage |
10 V DC (Us, max. 10 mA)
|
Rated control voltage (Uc) |
24 V DC (external, max. 100 mA options incl.)
|
Supply frequency |
50/60 Hz
|
Mains voltage - max |
240 V
|
Mains voltage - min |
200 V
|
Nominal output current I2N |
32.2 A
|
Number of HW-interfaces (industrial ethernet) |
0
|
Number of HW-interfaces (other) |
0
|
Number of HW-interfaces (parallel) |
0
|
Number of HW-interfaces (RS-232) |
0
|
Number of HW-interfaces (RS-422) |
0
|
Number of HW-interfaces (RS-485) |
1
|
Number of HW-interfaces (serial TTY) |
0
|
Number of HW-interfaces (USB) |
0
|
Number of interfaces (PROFINET) |
0
|
Number of outputs (analog) |
1
|
Output at linear load at rated output voltage - max |
7.5 kW
|
Output at quadratic load at rated output voltage - max |
11 kW
|
Output frequency - max |
400 Hz
|
Output frequency - min |
0 Hz
|
Output voltage - max |
240 V
|
Overload current IL at 110% overload |
52.8 A
|
Overload current IL at 150% overload |
48 A
|
Shock resistance |
0.75 mm (peak) at 10 - 57 Hz, max. 1 g at 57 - 150 Hz, according to EN 61800-5-1, EN 60068-2-6: 10 - 150 Hz
|
Suitable for |
Branch circuits, (UL/CSA)
|
Switching frequency |
3.6 kHz, 1 - 16 kHz adjustable, fPWM, Power section, Main circuit
|
Rated operational voltage |
230 V AC, 3-phase
240 V AC, 3-phase |
Short-circuit protection rating |
58 A, UL (Class CC or J), Safety device (fuse or miniature circuit-breaker), Power Wiring
|
Rated frequency - max |
66 Hz
|
Rated frequency - min |
45 Hz
|
Rated operational current (Ie) at 110% overload |
48 A
|
Rated operational current (Ie) at 150% overload |
32 A
|
Rated operational current for specified heat dissipation (In) |
48 A
|
Rated operational power at 220/230 V, 50 Hz, 1-phase |
7.5 kW
|
Rated operational power at 220/230 V, 50 Hz, 3-phase, 110% overload |
11 kW
|
Heat dissipation at current/speed |
157 W at 25% current and 0% speed
189.4 W at 25% current and 50% speed 221.8 W at 100% current and 50% speed 245.3 W at 50% current and 50% speed 262.7 W at 50% current and 90% speed 360.1 W at 100% current and 0% speed 402 W at 50% current and 0% speed 443.4 W at 100% current and 90% speed |