Eaton DMV Switch-disconnector, 3p+N, 1000A, with shaft and handle
| Product Name |
Eaton DMV Switch-disconnector
|
| Catalog Number |
1814452
|
| EAN |
8711426104488
|
| Product Length/Depth |
310 mm
|
| Product Height |
110 mm
|
| Product Width |
250 mm
|
| Product Weight |
5 kg
|
| Certifications |
IEC/EN 60947
KEMA RoHS CE IEC/EN 60947-3 EAC Lloyds IEC/EN 60204 VDE 0660 |
| Model Code |
DMV-1000N/1+SH
|
| Fitted with: |
Operating shaft and knob
|
| Functions |
Optional Stop Function
|
| Number of poles |
Four-pole
|
| Accessories |
|
| Actuator color |
Other
|
| Actuator type |
Long turning handle
|
| Degree of protection |
NEMA Other
|
| Degree of protection (front side) |
IP00
|
| Lifespan, mechanical |
5,000 Operations
|
| Mounting method |
Surface mounting
|
| Mounting position |
As required
|
| Overvoltage category |
III
|
| Pollution degree |
3
|
| Product Category |
|
| Rated impulse withstand voltage (Uimp) |
12000 V
|
| Ambient operating temperature - min |
-25 °C
|
| Ambient operating temperature - max |
55 °C
|
| Ambient storage temperature - min |
-30 °C
|
| Ambient storage temperature - max |
80 °C
|
| Tightening torque |
28 Nm, Screw terminals
|
| Rated breaking capacity at 400/415 V (cos phi to IEC 60947-3) |
6072 A
|
| Rated breaking capacity at 500 V (cos phi to IEC 60947-3) |
4600 A
|
| Rated breaking capacity at 660/690 V (cos phi to IEC 60947-3) |
3496 A
|
| Rated insulation voltage (Ui) |
1000 V
|
| Rated operational current (Ie) at AC-21, 400 V, 415 V |
1000 A
|
| Rated operational current (Ie) at AC-21, 500 V |
1000 A
|
| Rated operational current (Ie) at AC-21, 690 V |
1000 A
|
| Rated operational current (Ie) at AC-22, 380 V, 400 V, 415 V |
1000 A
|
| Rated operational current (Ie) at AC-22, 500 V |
1000 A
|
| Rated operational current (Ie) at AC-22, 690 V |
1000 A
|
| Rated operational current (Ie) at AC-23A, 400 V, 415 V |
759 A
|
| Rated operational current (Ie) at AC-23A, 500 V |
575 A
|
| Rated operational current (Ie) at AC-23A, 690 V |
437 A
|
| Rated operational power at AC-23A, 400 V, 50 Hz |
425 kW
|
| Rated operational power at AC-23A, 500 V, 50 Hz |
425 kW
|
| Rated operational power at AC-23A, 690 V, 50 Hz |
425 kW
|
| Rated operational power at AC-3, 380/400 V, 50 Hz |
0 kW
|
| Rated operational voltage (Ue) at AC - max |
690 V
|
| Rated uninterrupted current (Iu) |
1000 A
|
| Uninterrupted current |
Rated uninterrupted current Iu is specified for max. cross-section.
|
| Breaking current |
70 kA (at In = 1000)
65 kA (at In = 630) |
| Let-through energy |
Max. 3200 kA²s (at In = 630)
Max. 4200 kA²s (at In = 1000) |
| Rated conditional short-circuit current (Iq) |
50 kA at In = 1000
100 kA |
| Rated short-time withstand current (Icw) |
36 kA, Contacts, 1 second
36 kA |
| Short-circuit protection rating |
1000/630, Fuse, Contacts
|
| Number of auxiliary contacts (change-over contacts) |
0
|
| Number of auxiliary contacts (normally closed contacts) |
0
|
| Number of auxiliary contacts (normally open contacts) |
0
|
| Heat dissipation per pole, current-dependent Pvid |
44.75 W
|
| Rated operational current for specified heat dissipation (In) |
1000 A
|