Eaton Moeller® series PKZM0 Motor-protective circuit-breaker, 3p+1N/O+1N/C, Ir=1-1.6A, screw connection, large packaging PKZM0-1,6/NHI-E-11-GVP2

Especificaciones generales

Product Name
Eaton Moeller® series PKZM0 Motor-protective circuit-breaker
Catalog Number
088841
EAN
4015080888413
Product Length/Depth
76 mm
Product Height
93 mm
Product Width
45 mm
Product Weight
0.28 kg
Certifications
CE

Especificaciones del producto

Fitted with:
Auxiliary switch
Actuator type
Turn button
Adjustment range undelayed short-circuit release - max
25 A
Adjustment range undelayed short-circuit release - min
25 A
Device construction
Built-in device fixed built-in technique
Connection
Screw terminals
Electrical connection type of main circuit
Screw connection
Degree of protection
IP20
Number of poles
Three-pole
Functions
Phase failure sensitive
Terminal capacity (solid/stranded AWG)
18 - 10
18 - 16
Overload release current setting - max
1.6 A
Overload release current setting - min
1 A
Rated operational voltage (Ue) - max
690 V
Rated operational voltage (Ue) - min
690 V
Rated operational power at AC-3e, 220/230 V, 50 Hz
0.25 kW
Rated operational power at AC-3e, 380/400 V, 50 Hz
0.55 kW
Rated uninterrupted current (Iu)
1.6 A
Rated short-circuit breaking capacity Icu at 400 V AC
150 kA
Rated short-circuit breaking capacity Ics at 400 V AC
150 kA
Rated short-circuit breaking capacity Icu at 440 V AC
150 kA
Rated short-circuit breaking capacity Ics at 440 V AC
150 kA
Rated short-circuit breaking capacity Icu at 500 V AC
150 kA
Rated short-circuit breaking capacity Ics at 500 V AC
150 kA
Rated short-circuit breaking capacity Icu at 690 V AC
150 kA
Rated short-circuit breaking capacity Ics at 690 V AC
150 kA
Short-circuit current rating (group protection)
50 kA, 600 V High Fault, Fuse, SCCR (UL/CSA) with 600 A, 600 V High Fault, Fuse, SCCR (UL/CSA)
50 kA, 600 V High Fault, CB, SCCR (UL/CSA) with 600 A, 600 V High Fault, CB, SCCR (UL/CSA)
Tightening torque
1 Nm, Screw terminals, Control circuit cables
1.7 Nm, Screw terminals, Main cable
Switch off technique
Thermomagnetic
Terminal capacity (flexible with ferrule)
1 x (1 - 6) mm², Main circuit cables
2 x (1 - 6) mm², Main circuit cables
1 x (0.75 - 1.5) mm², Control circuit cables
2 x (0.75 - 1.5) mm², Control circuit cables
Power loss
5.36 W