Căutare informații
Descărcați documentul () din 20
Noi facem să funcționeze  lucrurile importante*

170976
FRBMM-B10/1N/001-A

Eaton Moeller series xEffect - FRBm6/M RCBO - residual-current circuit breaker with overcurrent protection. RCD/MCB, 10A, 10mA, MCB trip type B, 1-phase+N, RCCB trip type: A

Specificații generale

Product Name
Eaton Moeller series xEffect - FRBmM RCBO - residual-current circuit breaker with overcurrent protection
Catalog Number
170976
EAN
4015081671007
Product Length/Depth
80 mm
Product Height
75 mm
Product Width
35 mm
Product Weight
0.202 kg
Compliances
CE Marked
RoHS conform
Certifications
CE
EN45545-2
IEC 61373
Model Code
FRBMM-B10/1N/001-A

Informații suplimentare

Current limiting class
3
Features
Concurrently switching N-neutral

Programul de livrare

Application
Switchgear for industrial and advanced commercial applications
Basic function
Combined RCD/MCB devices
Fault current rating
0.01 A
Number of poles
Single-pole + N
Number of poles (protected)
1
Number of poles (total)
2
Product range
FRBmM
Rated current
10 A
Release characteristic
B
Sensitivity type
Pulse-current sensitive
Tripping characteristic
B
Type
RCBO

Verificarea proiectării conform IEC/EN 61439

10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard's requirements.
10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of assemblies
Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances
Meets the product standard's requirements.
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9.2 Power-frequency electric strength
Is the panel builder's responsibility.
10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material
Is the panel builder's responsibility.

Verificarea designului conform cu IEC/EN 61439 - date tehnice

Ambient operating temperature - max
40 °C
Ambient operating temperature - min
-25 °C
Equipment heat dissipation, current-dependent
2.3 W
Heat dissipation capacity
0 W
Heat dissipation per pole, current-dependent
0 W
Rated operational current for specified heat dissipation (In)
10 A
Static heat dissipation, non-current-dependent
0 W

Technical data - electrical

Disconnection characteristic
Undelayed
Frequency rating
50 Hz
Impulse withstand current
Partly surge-proof, 250 A
Leakage current type
A
Pollution degree
2
Rated fault currents of product range
10, 30, 100, 300 MilliAmpere
Rated impulse withstand voltage (Uimp)
4 kV
Rated insulation voltage (Ui)
500 V
Rated operational voltage (Ue) - max
240 V
Rated short-circuit breaking capacity (EN 60947-2)
15 kA
Rated short-circuit breaking capacity (EN 61009-1)
10 kA
Rated short-circuit breaking capacity (EN 61009)
10 kA
Rated short-circuit breaking capacity (IEC 60947-2)
15 kA
Rated switching capacity
10 kA
Rated switching capacity (IEC/EN 61009)
10 kA
Surge current capacity
0.25 kA
Tripping
Non-delayed
Voltage rating
240 V - 240 V
Voltage type
AC

Technical data - mechanical

Built-in depth
75.5 mm
Connectable conductor cross section (multi-wired) - max
25 mm²
Connectable conductor cross section (multi-wired) - min
1 mm²
Connectable conductor cross section (solid-core) - max
25 mm²
Connectable conductor cross section (solid-core) - min
1 mm²
Degree of protection
IP20
Mounting Method
DIN rail
Width in number of modular spacings
2

Exportați specificațiile produsului

Notă: Dacă fișierul(e) lipsesc din descărcarea .zip, atunci tipul de fișier nu este suportat pentru descărcarea în masă.
Serial Number Verified :
Authenticated:
The product is verified as being authentic; however, this does not guarantee the condition or fit for purpose of the product.

Autentificare produs

Intrpduceți numărul de serie de 16-17 cifre
Numărul de serie pe care l-ați introdus nu trebuie să conțină caractere speciale. Numărul de serie pe care l-ați introdus nu este corect și ar trebui să conțină 16 sau 17 cifre. Numărul de serie pe care l-ați introdus nu a fost găsit. Vă rugăm să încercați din nou sau raportați o problemă pentru asistență suplimentară. Numărul de serie pe care l-ați introdus nu se potrivește produsului. Verificați numărul de serie al produsului și încercați din nou. Click aici pentru a naviga pe pagina produsului pentru numărul de serie pe care l-ați introdus Numărul de serie este cunoscut de către Eaton ca fiind suspect, vă rugăm să încercați din nou sau raportați o problemă pentru asistență suplimentară.
Număr de serie
Resetare Numărul de serie este cunoscut de către Eaton ca fiind suspect, vă rugăm să încercați din nou sau raportați o problemă pentru asistență suplimentară. Numărul de serie nu este recunoscut de către Eaton și este invalid. Vă rugăm să utilizați acest formular pentru raportați o problemă pentru asistență suplimentară.
Introduceți un cod de autentificare de 6 cifre
Produsul pe care l-ați introdus este suspect! Vă rugăm să încercați din nou sau raportați o problemă pentru asistență suplimentară. Codul de autentificare pe care l-ați introdus nu se potrivește înregistrărilor noastre pentru acest număr de serie. Vă rugăm să încercați din nou, sau raportați o problemă pentru asistență suplimentară. Cod de autentificare invalid. Lungimea trebuie să fie de 6 caractere raportați o problemă pentru asistență suplimentară. Codul de autentificare este necesar raportați o problemă pentru asistență suplimentară.
A completa provocarea Captcha înainte de autentificare.
x
Raportați o problemă
Vă rugăm să introduceți numele dumneavoastră complet.
x
Vă mulțiumim, problema dumneavoastră a fost trimisă, iar echipa noastră de produse vă va contacta în curând.