Căutare informații
Descărcați documentul () din 20
Noi facem să funcționeze  lucrurile importante*

263271
PLN6-B13/1N-DE

Eaton Moeller series xPole - PLN6 MCB. Miniature circuit breaker (MCB), 13 A, 1p+N, characteristic: B, DE

Specificații generale

Product Name
Eaton Moeller series xPole - PLN6 MCB
Catalog Number
263271
EAN
4015082632717
Product Length/Depth
71 mm
Product Height
82 mm
Product Width
17.6 mm
Product Weight
0.13 kg
Compliances
RoHS compliant
Certifications
IEC/EN 60898
Model Code
PLN6-B13/1N-DE

Delivery program

Application
Residential and commercial applications
Number of poles
Single-pole + N
Number of poles (total)
2
Number of poles (protected)
1
Tripping characteristic
B
Release characteristic
B
Amperage Rating
13 A
Nominal current
63 A
Type
  • Miniature circuit breaker
  • PLN6

Technical data - electrical

Voltage type
AC
Voltage rating
230 V AC
Voltage rating (IEC/EN 60898-1)
240 VAC
Rated operational voltage (Ue) - max
240 VAC
Rated insulation voltage (Ui)
440 V
Rated impulse withstand voltage (Uimp)
4 kV
Frequency rating - min
50 Hz
Frequency rating - max
60 Hz
Rated switching capacity (IEC/EN 60898-1)
6 kA
Rated service short-circuit breaking capacity (IEC/EN 60898-1) - Ics
6 kA
Rated short-circuit breaking capacity (IEC/EN 60898-1) - Icn at 230 V
6 kA
Selectivity class
3
Overvoltage category
III
Pollution degree
2
Lifespan, electrical
>4000 operating cycles
Direction of incoming supply
Bidirectional

Technical data - mechanical

Frame
45 mm
Width in number of modular spacings
1
Built-in depth
65.5 mm
Mounting width
17.7 mm
Mounting Method
Two lock-in position on DIN rail (EN/IEC 60715)
Mounting position
As required
Degree of protection
IP20 (device)
IP40 (when installed in enclosure)
Terminal capacity
1 mm² - 16 mm²
Terminals (top and bottom)
Screw-type with pressure plate
Connectable conductor cross section (solid-core) - min
1 mm²
Connectable conductor cross section (solid-core) - max
16 mm²
Connectable conductor cross section (multi-wired) - min
1 mm²
Connectable conductor cross section (multi-wired) - max
16 mm²
Terminal capacity of screw terminals for main cable
1 mm² - 16 mm²
Terminal protection
Touch-safe (EN 50274)
Contact position indicator color
Red = ON
Green = OFF
Tightening torque
Max. 1.2 Nm
Lifespan, mechanical
>10000 operating cycles

Design verification as per IEC/EN 61439 - technical data

Rated operational current for specified heat dissipation (In)
13 A
Ambient operating temperature - min
-25 °C
Ambient operating temperature - max
75 °C

Design verification as per IEC/EN 61439

10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard's requirements.
10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of assemblies
Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances
Meets the product standard's requirements.
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9.2 Power-frequency electric strength
Is the panel builder's responsibility.
10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material
Is the panel builder's responsibility.
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.

Additional information

Current limiting class
3
Features
Can be fitted with auxiliary accessories
Neutral conductor switches concurrently with the phase conductors
Functional group
Overcurrent protection
Functions
Overload protection
Short Circuit protection
Internal resistance at room temperature (single-pole, 50 Hz)
10.8 mΩ