Reset
Eaton Moeller series xEffect - FAZ-NA, FAZ-RT MCB. Miniature circuit breaker (MCB), 6 A, 4p, characteristic: D, NA
| Product Name |
Eaton Moeller series xEffect - FAZ-NA, FAZ-RT MCB
|
| Catalog Number |
190831
|
| EAN |
4015081904785
|
| Product Length/Depth |
105 mm
|
| Product Height |
75.5 mm
|
| Product Width |
70.8 mm
|
| Product Weight |
0.478 kg
|
| Compliances |
RoHS conform
|
| Certifications |
IEC 60947-2
CSA-C22.2 No. 5-09 CSA (Class No. 1432-01) Specially designed for North America, suitable as BCPD UL 489 CSA (File No. 204453) North America (UL listed, CSA certified) UL (File No. E235139) UL (Category Control Number DIVQ) CE marking IEC/EN 60947-2 UL 489, CSA C22.2 No. 5 EN45545-2 IEC 61373 |
| Model Code |
FAZ-D6/4-NA
|
| Used with |
FAZ-XAA-NA110-415V AC 102036 (Shunt trip release)
FAZ-XAA-NA12-110V AC 102037 (Shunt trip release)
FAZ-NA Miniature circuit breaker FAZ-XAA-NA110-415V AC 102036 (Shunt trip release) FAZ-XAA-NA12-110V AC 102037 (Shunt trip release) |
| Amperage Rating |
6 A
|
| Voltage rating |
277 V AC / 480 V AC
|
| Features |
Additional equipment possible
|
| Accessories required |
Z-IHK-NA 113895
|
| 10.10 Temperature rise |
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
|
| 10.11 Short-circuit rating |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
| 10.12 Electromagnetic compatibility |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
| 10.13 Mechanical function |
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
|
| 10.2.2 Corrosion resistance |
Meets the product standard's requirements.
|
| 10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard's requirements.
|
| 10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard's requirements.
|
| 10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects |
Meets the product standard's requirements.
|
| 10.2.4 Resistance to ultra-violet (UV) radiation |
Meets the product standard's requirements.
|
| 10.2.5 Lifting |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.2.6 Mechanical impact |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.2.7 Inscriptions |
Meets the product standard's requirements.
|
| 10.3 Degree of protection of assemblies |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.4 Clearances and creepage distances |
Meets the product standard's requirements.
|
| 10.5 Protection against electric shock |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.6 Incorporation of switching devices and components |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.7 Internal electrical circuits and connections |
Is the panel builder's responsibility.
|
| 10.8 Connections for external conductors |
Is the panel builder's responsibility.
|
| 10.9.2 Power-frequency electric strength |
Is the panel builder's responsibility.
|
| 10.9.3 Impulse withstand voltage |
Is the panel builder's responsibility.
|
| 10.9.4 Testing of enclosures made of insulating material |
Is the panel builder's responsibility.
|
| Fitted with: |
Z-IS/SPE-1TE 274418
|
| Frame |
45 mm
|
| Pollution degree |
2
|
| Lifespan, mechanical |
10000 operations
|
| Mounting Method |
Top-hat rail IEC/EN 60715
|
| Degree of protection |
IP40 (when fitted)
UL/CSA Type: - IP20 (IEC) IP20 |
| Rated impulse withstand voltage (Uimp) |
4 kV
|
| Admissible back-up fuse - max |
125 A gL/gG
|
| Terminal protection |
Finger and hand touch safe, DGUV VS3, EN 50274
|
| Terminals (top and bottom) |
Lift terminal / ring-tongue
|
| Tripping characteristic |
D
|
| Ambient operating temperature - max |
75 °C
|
| Ambient operating temperature - min |
-25 °C
|
| Ambient operating temperature (UL) - max |
40 °C
|
| Built-in depth |
60 mm
|
| Connectable conductor cross section (multi-wired) - max |
25 mm²
|
| Connectable conductor cross section (multi-wired) - min |
1 mm²
|
| Connectable conductor cross section (solid-core) - max |
25 mm²
|
| Connectable conductor cross section (solid-core) - min |
1 mm²
|
| Current limiting class |
3
|
| Enclosure width |
105 mm
|
| Frequency rating - max |
60 Hz
|
| Frequency rating - min |
50 Hz
|
| Heat dissipation capacity |
0 W
|
| Heat dissipation per pole, current-dependent |
0 W
|
| Internal resistance at room temperature (single-pole, 50 Hz) |
32 mΩ
|
| Direction of incoming supply |
As required
|
| Width in number of modular spacings |
4
|
| Voltage rating (IEC/EN 60947-2) |
415 V
|
| Voltage rating (UL) |
480Y/277 V
|
| Voltage rating at DC |
60 V DC
|
| Ambient operating temperature (UL) - min |
-5 °C
|
| Voltage type |
AC
|
| Contact position indicator color |
Red / green
|
| Mounting position |
As required
|
| Overvoltage category |
III
|
| Number of poles |
Four-pole
|
| Functions |
Current limiting circuit breaker
|
| Lifespan, electrical |
min. 1500 operations
min. 6000 operations (UL) |
| Release characteristic |
D
|
| Type |
|
| Special features |
|
| Application |
|
| Mounting width |
17.7 mm
|
| Selectivity class |
3
|
| Mounting width per pole |
17.7 mm
|
| Number of poles (protected) |
4
|
| Number of poles (total) |
4
|
| Operational switching capacity |
7.5 kA
|
| Rated insulation voltage (Ui) |
440 V
|
| Rated operational current for specified heat dissipation (In) |
6 A
|
| Rated operational voltage (Ue) - max |
240 V
|
| Rated short-circuit breaking capacity (IEC/EN 60898-1) - Icn at 230 V |
10 kA
|
| Rated short-circuit breaking capacity (IEC/EN 60898-1)- Icn at 400 V |
15 kA
|
| Rated short-circuit breaking capacity (IEC 60947-2)- Icu at 230 V |
10 kA
|
| Rated short-circuit breaking capacity (IEC 60947-2)- Icu at 400 V |
14 kA
|
| Rated switching capacity (IEC/EN 60947-2) |
15 kA
|
| Static heat dissipation, non-current-dependent |
0 W
|
| Suitable for |
Flush-mounted installation
|
| Terminal capacity (control cable) |
25 mm² (1x)
|
| Terminal capacity of screw terminals for main cable |
10 mm² (2x)
|
| Tightening torque |
UL: 4 Nm (36 lb-in) for AWG 6
UL: 2.8 Nm (25 lb-in) for AWG 10 - AWG 8 Max. 2.4 Nm UL: 2.4 Nm (21 lb-in) for AWG 18 - AWG 12 |
| Power loss |
4.8 W
|