Belgeyi İndir () / 20
Zor İşler Bizimle Kolay

STARLED-013

StarLED 20m Viewing Distance, Maintained/ Non Maintained, IP42, 150 lm, Mains Lighting up to 100 lm, 1H Autonomy, Manual Test, 3 Adhesive Exit Legends (L,R,D)

Genel Teknik Özellikler

Product Name
Eaton SafeLite emergency luminaire
Catalog Number
STARLED-013
EAN
3660191606428
Product Length/Depth
270 mm
Product Height
49 mm
Product Width
119 mm
Product Weight
0.32 kg

Ürün teknik özellikleri

Battery voltage
3.6 V
Battery number of cells
3
Battery quality
NiCd
Glow wire test
850 °C
Permissible ambient temperature - min
5 °C
Permissible ambient temperature - max
40 °C
Protection class
II
Degree of impact resistance (IK)
IK 04
Outdoor use compliance
No
Explosion protected
No
Degree of protection
IP42
Mode
Maintained / Non-Maintained (M / NM)
Lamp type
LED not exchangeable
With light source
Yes
Lamp holder
None
Type of indicator
Only single-sided
Monitoring equipment
None
Power supply system
Peripheral (individual battery)
Voltage type
AC
Apparent Power At Mains Operation
3.2 VA
Effective power at mains operation
2.7 W
Power factor
0.84
Wiring system
Continuous circuit/emergency circuit
With remote switch connection
No
Energy efficiency class
A
Conductor cross section
2.5
Connection type
Plug-in connection
Max. system power
2.7 W
Rated life time L70/B10 at 25 °C
60000 hour
Rated life time L70/B50 at 25 °C
60000 hour
Type of control gear
Electronic transformer
Type of wiring
Suitable for through wiring
Nominal voltage AC - max
230 V
Nominal voltage AC - min
230 V
Rated ambient temp acc. IEC62722-2-1 - Min
5 °C
Rated ambient temp acc. IEC62722-2-1 - Max
40 °C
Nominal operation time - min
1 hour
Nominal operation time - max
1 hour
Autonomy
1 hour
Energy efficiency class of the light source according to EU regulation 2019/2015
A
Suitable for standby switching
No
Suitable for continuous circuit
No
RAL-Number (Similar) Housing
9003
Mounting Method
Surface mounting/recessed mounting
Material housing
Plastic
Color housing
White
Material cover
Plastic, transparent
Limited surface temperature
No
Labelling type
Sticker
Pictogram included
True
Built-in Length
270 mm
Built-in Width
119 mm
Built-in height/depth
49 mm
Number Of Poles (Numeric)
2
Impact strength
IK04
Kind of luminaire
Safety and exit sign luminaire
Rated Luminous Flux Acc. IEC 62722-2-1
150 lm
Luminous flux at emergency operation
50 lm
Color temperature - max
5053 K
Color temperature - min
5053 K
Light distributor
Reflector
Energy efficiency class of the built-in lamp
A++, A+, A (LED)
Function
Escape route lighting/signage
Color of light
White
Color rendering index (CRI)
70-79
Luminaire With Limited Surface Temperature, Sign D
No
Number of lighting heads
8
Suitable for number of lamps
1
Viewing distance
20 m
Frequency
50/60 Hz
Main connection terminal
0.5 - 2.5mm²
Product branding
Eaton
Operating voltage - max
240 V
Operating voltage - min
220 V
Color temperature
5053 K
Power consumption mains operation - effective power (W)
2.7 W
Power consumption mains operation - apparent power (VA)
3.2 VA
Testing system
No testing system
With remote control
No
Constant light output (CLO)
No
Exchangeable control gear
No
Emergency function monitoring system
Test button
Emergency power supply system
Peripheral (individual battery)
Power consumption in emergency mode
2.7 W
With heating element for battery
No

Ürün teknik özelliklerini aktar