Завантажити документ () з 20
Ми забезпечуємо роботу найважливішого*

194606
Код моделі: CI43E-150-APZ

Eaton xEnergy Safety Ci LV systems LV switchgear. Ci-APZ enclosure with MM43 + 1x Rail

General specifications

Product Name
Eaton xEnergy Safety Ci meter enclosure APZ
Catalog Number
194606
EAN
9010238059085
Product Length/Depth
175 mm
Product Height
375 mm
Product Width
250 mm
Product Weight
99.999 kg
Compliances
RoHS conform
Certifications
EN 62208
EN 61439-2
Model Code
CI43E-150-APZ

Delivery program

Type
Basic enclosure Individual enclosures xEnergy Safety Ci
Color
Light gray (RAL 7035, base)
Gray
Transparent, smoky gray (cover)
Nominal current
1600 A

Technical Data - Electrical

Circuit integrity
None

Technical Data - Mechanical

Unit type
Single unit
Surface finishing
Resistant to corrosion
Surface protection
Other
Surface treatment
Resistant to corrosion
Enclosure material
Plastic
Width in number of modular spacings
15
Mounting depth with mounting plate
150 mm
Mounting method
Surface mounted (plaster)
Material
Glass-fibre reinforced polycarbonate (base)
Non-reinforced polycarbonate (cover)
Halogen free
Degree of protection
Other
IK10
IP65
Number of conduit inlets
76
Number of modules
1
Number of openings (flange plates)
4
Number of rows
1
Built-in depth
150 mm
Cover/door color
Transparent
Cover/door model
Closed
Cover/door type
None
Cover
Plate thickness (cabinet)
6 mm
Plate thickness (cover/door)
6 mm
Saline spray resistance
IEC 60068-2-11

Temperature-rise verification as per IEC 60890

Heat diss. ambient 35°C delta T: 20°C wall mount middle encl. top (IEC 60890)
20 W
Heat diss. ambient 35°C delta T: 35°C wall mount middle encl. top (IEC 60890)
40 W
Heat diss. ambient 35°C delta T:20°C wall mount individ. encl. top (IEC 60890)
22 W
Heat diss. ambient 35°C delta T:20°C wall mount starting encl. top (IEC 60890)
21 W
Heat diss. ambient 35°C delta T:35°C wall mount individ. encl. top (IEC 60890)
44 W
Heat diss. ambient 35°C delta T:35°C wall mount starting encl. top (IEC 60890)
42 W

Design verification as per IEC/EN 61439 - technical data

Temperature resistance
Temperature resistant: 85 °C (enclosure bolt)
Temperature resistant: -40 °C - 120 °C (enclosure)
Temperature resistant: 80 °C (gasket)
Ambient operating temperature details
-40 °C - 80 °C

Design verification as per IEC/EN 61439

10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects
Lower part: 960 °C / cover: 850 °C
10.2.4 Resistance to ultra-violet (UV) radiation
Not relevant to indoor installations.
10.2.5 Lifting
10 kg per enclosure with support frame and lifting aid met; assembled and secured as per the latest applicable instruction leaflet.
10.2.6 Mechanical impact
IK10
10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of assemblies
IP65
10.4 Clearances and creepage distances
Is the panel builder's responsibility.
10.5 Protection against electric shock
Protection class 2, therefore not applicable.
10.6 Incorporation of switching devices and components
Is the panel builder's responsibility.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9.2 Power-frequency electric strength
Ui = 1000 V AC
10.9.3 Impulse withstand voltage
8 kV
10.9.4 Testing of enclosures made of insulating material
Meets the product standard's requirements.
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility.
10.13 Mechanical function
Meets the product standard's requirements.

Additional information

Features
UV resistance beneath protective shield
Cover with overpressure release
Fitted with:
Mounting plate
Flammability characteristics (UL)
V1 (base) (UL94)
V2 (cover) (UL94)
Functions
Extension possible
Protection class
II
RAL-number
7035
Special features
With metric knockouts in all sides of the enclosure Include fixing straps for wall mounting Sealable cover fasteners With mounting plate and 1x mounting rail
Suitable for
Lightning protection
Outdoor use
Used with
Incorporation of a router of the metering point operator between the termination point of the line network (APL) and the ZSD meter station

Експортувати специфікацію продукту