Reset
Eaton Moeller series NZMN4 PXR20 circuit breaker, 1200 A, 3-pole, Screw terminal, UL/CSA
| Product Name |
Eaton Moeller series NZM molded case circuit breaker electronic
|
| Catalog Number |
192553
|
| EAN |
4015081932818
|
| Product Length/Depth |
401 mm
|
| Product Height |
207 mm
|
| Product Width |
210 mm
|
| Product Weight |
21 kg
|
| Compliances |
RoHS conform
|
| Certifications |
IEC 60947-2
CE marking UL listed Specially designed for North America CSA (File No. 22086) CSA certified IEC CSA-C22.2 No. 5-09 UL/CSA UL 489 CSA (Class No. 1432-01) UL (Category Control Number DIVQ) UL (File No. E31593) |
| Model Code |
NZMN4-VX1200-NA
|
| Application |
Branch circuits, feeder circuits
|
| Type |
|
| Circuit breaker frame type |
NZM4
|
| Number of poles |
Three-pole
|
| Release system |
Electronic release
|
| Features |
Protection unit
Motor drive optional |
| Special features |
Circuit breaker
|
| Amperage Rating |
1200 A
|
| Instantaneous current setting (Ii) - min |
2 A
|
| Instantaneous current setting (Ii) - max |
15 A
|
| Overload current setting (Ir) - min |
480 A
|
| Overload current setting (Ir) - max |
1200 A
|
| Short delay current setting (Isd) - min |
2400 A
|
| Short delay current setting (Isd) - max |
12000 A
|
| Short-circuit release delayed setting - min |
800 A
|
| Short-circuit release delayed setting - max |
12000 A
|
| Short-circuit release non-delayed setting - min |
2400 A
|
| Short-circuit release non-delayed setting - max |
18000 A
|
| Rated short-circuit breaking capacity Ics (IEC/EN 60947) at 400/415 V, 50/60 Hz |
50 kA
|
| Electrical connection type of main circuit |
Screw connection
|
| Handle type |
Rocker lever
|
| Voltage rating |
690 V - 690 V
|
| Rated operating voltage Ue (UL) - max |
600 V
|
| Amperage Rating |
1200 A
|
| Instantaneous current setting (Ii) - min |
2 A
|
| Instantaneous current setting (Ii) - max |
15 A
|
| Overload current setting (Ir) - min |
480 A
|
| Overload current setting (Ir) - max |
1200 A
|
| Short delay current setting (Isd) - min |
2400 A
|
| Short delay current setting (Isd) - max |
12000 A
|
| Short-circuit release delayed setting - min |
800 A
|
| Short-circuit release delayed setting - max |
12000 A
|
| Short-circuit release non-delayed setting - min |
2400 A
|
| Short-circuit release non-delayed setting - max |
18000 A
|
| Rated short-circuit breaking capacity Ics (IEC/EN 60947) at 400/415 V, 50/60 Hz |
50 kA
|
| Electrical connection type of main circuit |
Screw connection
|
| Handle type |
Rocker lever
|
| Mounting Method |
Fixed
Built-in device fixed built-in technique |
| Degree of protection |
IP20
|
| Protection against direct contact |
Finger and back-of-hand proof to DIN EN 50274/VDE 0106 part 110
|
| Number of auxiliary contacts (change-over contacts) |
0
|
| Number of auxiliary contacts (normally closed contacts) |
0
|
| Number of auxiliary contacts (normally open contacts) |
0
|
| Position of connection for main current circuit |
Front side
|