Eaton EU5C SWD power supply for SWD modules and contactors
Product Name |
Eaton EU5C Accessory Power supply
|
Catalog Number |
116380
|
EAN |
4015081161102
|
Product Length/Depth |
125 mm
|
Product Height |
90 mm
|
Product Width |
35 mm
|
Product Weight |
0.16 kg
|
Certifications |
UL Category Control No.: NKCR
CSA CSA Class No.: 3211-07 IEC/EN 61131-2 UL File No.: E29184 EN 50178 UL CSA File No.: 2324643 |
Catalog Notes |
SmartWire-DT power supply for SmartWire-DT modules and for additionally feeding the control voltage for motor starters and contactors, as well as for establishing emergency stop groups
|
Model Code |
EU5C-SWD-PF2-1
|
Electric connection type |
Flat plug-in connection
|
Features |
Fieldbus connection over separate bus coupler possible
Overload proof |
Fitted with: |
Power supply module
Potential separation |
Functions |
For additional control voltage feeder for the motor starter and contactors
For the formation of emergency switching off groups for motor starters and contactors For feeding supply voltage in order to connect additional SmartWire-DT modules to the SmartWire-DT ribbon cable |
Degree of protection |
IP20
|
Mounting method |
Rail mounting possible
Wall mounting/direct mounting Top-hat rail fixing (according to IEC/EN 60715, 35 mm) |
Overvoltage category |
II
|
Pollution degree |
2
|
Product category |
SmartWire-DT accessories
|
Repetition rate |
1 s
|
Residual ripple |
≤ 5 % (input voltage)
|
Suitable as |
Segment module
|
Terminal capacity |
0.25 - 1.5 mm², flexible with ferrule
24 - 16 AWG, solid or stranded 0.2 - 1.5 mm², solid |
Voltage type |
DC
|
Constant acceleration |
1 g, 8.4 - 150 Hz, according to IEC/EN 61131-2, Vibrations
|
Constant amplitude |
3,5 mm, 5 - 8.4 Hz, according to IEC/EN 61131-2, Vibrations
|
Drop and topple |
50 mm Drop height, Drop to IEC/EN 60068-2-31
|
Height of fall (IEC/EN 60068-2-32) - max |
0.3 m
|
Mounting position |
As required
|
Shock resistance |
15 g, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 11 ms, 9 Impacts
|
Air pressure |
795 - 1080 hPa (operation)
|
Ambient operating temperature - min |
-25 °C
|
Ambient operating temperature - max |
55 °C
|
Ambient storage temperature - min |
-40 °C
|
Ambient storage temperature - max |
70 °C
|
Climatic proofing |
Damp heat, constant, to IEC 60068-2-3
Dry heat to IEC 60068-2-2 |
Environmental conditions |
Condensation: prevent with appropriate measures
|
Operating temperature - min |
-25 °C
|
Operating temperature - max |
55 °C
|
Relative humidity |
5 - 95 % (non-condensing, IEC/EN 60068-2-30)
|
Air discharge |
8 kV, according to IEC 61131-2, level 3, ESD
|
Burst impulse |
2 kV, Supply cable, according to IEC/EN 61131-2, Level 3
1 kV, SmartWire-DT cable, according to IEC/EN 61131-2, Level 3 |
Contact discharge |
4 kV, according to IEC/EN 61131-2, Level 2, ESD
|
Electromagnetic fields |
3 V/m at 1.4 - 2 GHz (according to IEC/EN 61131-2:2008)
1 V/m at 2.0 - 2.7 GHz (according to IEC/EN 61131-2:2008) 10 V/m at 80 - 1000 MHz (according to IEC/EN 61131-2:2008) |
Radiated RFI |
10 V (IEC/EN 61131-2:2008, Level 3)
|
Radio interference class |
Class A (EN 55011)
|
Surge rating |
0.5 kV, Supply cables/CAN/DP bus cable, Surge power cables, Surge (IEC/EN 61131-2:2008, Level 1), EMC
|
Voltage dips |
≤ 10 ms, Bridging voltage dips
|
Inrush current |
12.5 A (for 6 ms)
|
Power loss |
Normally 2.7 W
|
Rated control supply voltage |
24 V DC (UPOW, -15 %/+20 %)
24 V DC (UAUX, -15 %/+20 %) |
Rated operational current (Ie) - max |
0.7 A
|
Rated operational voltage |
Typically UAUX -0.2 V (for 24 V DC slaves)
14.5 V (± 3 % - SmartWire-DT) |
Short-circuit protection |
Yes, Short-circuit rating, SmartWire-DT supply voltage
No, external fuse FAZ Z3, Supply voltage UAux |
Supply current |
0.7 A, Imax, SmartWire-DT supply
3 A, Imax, Supply voltage UAux |
Supply voltage at AC, 50 Hz - min |
0 VAC
|
Supply voltage at AC, 50 Hz - max |
0 VAC
|
Supply voltage at DC - min |
20.4 VDC
|
Supply voltage at DC - max |
28.8 VDC
|
Connection |
2 x SmartWire-DT blade terminal SWD4-8MF2
|
Connection to SmartWire-DT |
Yes
|
Connection type |
SWD: 2 x plug, 8-pole
Push in terminals, Supply voltage |
LED indicator |
Status indication of Supply voltage: LED
|
Protocol |
Other bus systems
|
Explosion safety category for dust |
None
|
Explosion safety category for gas |
None
|
Potential isolation |
Between UPow and 15 V SmartWire-DT supply voltage: yes
|
Protection against polarity reversal |
Yes
Yes, for supply voltage (Siemens MPI optional) |
Equipment heat dissipation, current-dependent Pvid |
0 W
|
Heat dissipation capacity Pdiss |
0 W
|
Heat dissipation per pole, current-dependent Pvid |
0 W
|
Rated operational current for specified heat dissipation (In) |
0 A
|
Static heat dissipation, non-current-dependent Pvs |
2.7 W
|
10.2.2 Corrosion resistance |
Meets the product standard's requirements.
|
10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard's requirements.
|
10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard's requirements.
|
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects |
Meets the product standard's requirements.
|
10.2.4 Resistance to ultra-violet (UV) radiation |
Meets the product standard's requirements.
|
10.2.5 Lifting |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.6 Mechanical impact |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.7 Inscriptions |
Meets the product standard's requirements.
|
10.3 Degree of protection of assemblies |
Meets the product standard's requirements.
|
10.4 Clearances and creepage distances |
Meets the product standard's requirements.
|
10.5 Protection against electric shock |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.6 Incorporation of switching devices and components |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.7 Internal electrical circuits and connections |
Is the panel builder's responsibility.
|
10.8 Connections for external conductors |
Is the panel builder's responsibility.
|
10.9.2 Power-frequency electric strength |
Is the panel builder's responsibility.
|
10.9.3 Impulse withstand voltage |
Is the panel builder's responsibility.
|
10.9.4 Testing of enclosures made of insulating material |
Is the panel builder's responsibility.
|
10.10 Temperature rise |
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
|
10.11 Short-circuit rating |
Is the panel builder's responsibility.
|
10.12 Electromagnetic compatibility |
Is the panel builder's responsibility.
|
10.13 Mechanical function |
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
|