Eaton XC Compact PLC, 24 V DC, ethernet, RS232, SWDT
Product Name |
Eaton XC Compact PLC
|
Catalog Number |
167850
|
EAN |
4015081644254
|
Product Length/Depth |
50.6 mm
|
Product Height |
102.6 mm
|
Product Width |
155 mm
|
Product Weight |
0.3 kg
|
Certifications |
UL File No.: E205091
Certified by UL for use in Canada DNV GL UL UL508 CE cULus CSA Class No.: none UL 508 CSA File No.: UL report applies to both US and Canada UL Category Control No.: NRAQ EN 61131 IEC/EN 61131-2, CE |
Catalog Notes |
CoDeSys Runtime (license inclusive)
|
Model Code |
XC-152-E3-11
|
Features |
Integrated Web server
|
10.10 Temperature rise |
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
|
10.11 Short-circuit rating |
Is the panel builder's responsibility.
|
10.12 Electromagnetic compatibility |
Is the panel builder's responsibility.
|
10.13 Mechanical function |
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
|
10.2.2 Corrosion resistance |
Meets the product standard's requirements.
|
10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard's requirements.
|
10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard's requirements.
|
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects |
Meets the product standard's requirements.
|
10.2.4 Resistance to ultra-violet (UV) radiation |
Meets the product standard's requirements.
|
10.2.5 Lifting |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.6 Mechanical impact |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.7 Inscriptions |
Meets the product standard's requirements.
|
10.3 Degree of protection of assemblies |
Meets the product standard's requirements.
|
10.4 Clearances and creepage distances |
Meets the product standard's requirements.
|
10.5 Protection against electric shock |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.6 Incorporation of switching devices and components |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.7 Internal electrical circuits and connections |
Is the panel builder's responsibility.
|
10.8 Connections for external conductors |
Is the panel builder's responsibility.
|
10.9.2 Power-frequency electric strength |
Is the panel builder's responsibility.
|
10.9.3 Impulse withstand voltage |
Is the panel builder's responsibility.
|
10.9.4 Testing of enclosures made of insulating material |
Is the panel builder's responsibility.
|
Fitted with: |
Technology module
Other components Power supply Programming interface Libraries Memory unit Visualization Basic device Communication module Documentation Function module Engineering software Real time clock |
Connection to SmartWire-DT |
Yes
|
Battery runtime |
10 years typ.
|
Operating system |
Windows CE 5.0 (license included)
|
Connection type |
SWD: Blade terminal SWD4-8MF2
RS232: SUB-D, 9-pole (plug) Ethernet: RJ45 plug, 8-pole RS485: SUB-D, 9-pole (plug) |
Number of slots |
1 (for SD-Card)
|
Cycle time |
< 0.04 ms, for 1 k of instructions (Bit, Byte), memory
|
Number of modules |
99 (SmartWire-DT)
|
Data transfer rate |
57.6 kBit/s, RS232
100Base-TX, Ethernet 250 kBit/s, SmartWire-DT 10Base-T, Ethernet |
Degree of protection |
IP20
|
Functions |
Additional field bus interfaces
OPC Server Building blocks Web-server Ethernet function Remote Server SmartWire-DT master interface |
Supply voltage at DC - max |
24 VDC
|
Heat dissipation details |
|
Product category |
SmartWire-DT coordinators
|
Processor |
RISC CPU, 32 Bit, 400 MHz
|
Interfaces |
RS485
1 x RS232 (built-in) USB 2.0 (Host) 1 x USB device 2.0 (built-in) 1 x SmartWire-DT (built-in) 1 x USB host 2.0 (built-in) RS232 1 x Ethernet 10/100 Mbps (built-in) USB 2.0 |
Memory |
64 MByte Program memory code
|
Power loss |
Max. 8.5 W
|
Protocol |
TCP (basic interface)
SmartWire-DT (additional interface) IP (basic interface) SMTP (basic interface) UDP (basic interface) FTP (basic interface) HTTP (basic interface) |
Rated operational voltage |
20.4 - 28.8 V DC
|
Memory capacity |
64 MegaByte/4 kByte/32 kByte (Application/marker/retain data)
|
Ambient operating temperature - max |
55 °C
|
Ambient operating temperature - min |
0 °C
|
Ambient storage temperature - max |
60 °C
|
Ambient storage temperature - min |
-20 °C
|
Equipment heat dissipation, current-dependent Pvid |
0 W
|
Heat dissipation capacity Pdiss |
0 W
|
Heat dissipation per pole, current-dependent Pvid |
0 W
|
Rated operational current for specified heat dissipation (In) |
0 A
|
Static heat dissipation, non-current-dependent Pvs |
6 W
|