Nuotrauka reprezentatyvi
Download
Eaton DS7 Soft starter, 32 A, 200 - 480 V AC, 24 V DC, Frame size: FS2, Communication Interfaces: SmartWire-DT
| Product Name |
Eaton DS7 Soft starter
|
| Catalog Number |
134950
|
| EAN |
4015081317653
|
| Product Length/Depth |
126 mm
|
| Product Height |
150 mm
|
| Product Width |
45 mm
|
| Product Weight |
0.4 kg
|
| Certifications |
IEC/EN 60947-4-2
UL 508 CSA-C22.2 No 14-05 CSA CSA-C22.2 No 0-M91 GB 14048.6 UkrSEPRO CSA22.2-14 UL C-Tick CE |
| Model Code |
DS7-34DSX032N0-D
|
| Type |
Soft starter for three-phase loads
|
| 10.10 Temperature rise |
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
|
| 10.11 Short-circuit rating |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
| 10.12 Electromagnetic compatibility |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
| 10.13 Mechanical function |
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
|
| 10.2.2 Corrosion resistance |
Meets the product standard's requirements.
|
| 10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard's requirements.
|
| 10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard's requirements.
|
| 10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects |
Meets the product standard's requirements.
|
| 10.2.4 Resistance to ultra-violet (UV) radiation |
Meets the product standard's requirements.
|
| 10.2.5 Lifting |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.2.6 Mechanical impact |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.2.7 Inscriptions |
Meets the product standard's requirements.
|
| 10.3 Degree of protection of assemblies |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.4 Clearances and creepage distances |
Meets the product standard's requirements.
|
| 10.5 Protection against electric shock |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.6 Incorporation of switching devices and components |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.7 Internal electrical circuits and connections |
Is the panel builder's responsibility.
|
| 10.8 Connections for external conductors |
Is the panel builder's responsibility.
|
| 10.9.2 Power-frequency electric strength |
Is the panel builder's responsibility.
|
| 10.9.3 Impulse withstand voltage |
Is the panel builder's responsibility.
|
| 10.9.4 Testing of enclosures made of insulating material |
Is the panel builder's responsibility.
|
| Fitted with: |
Internal bypass
Internal bypass contacts |
| Pollution degree |
2
|
| Class |
Other
|
| Climatic proofing |
Damp heat, cyclic, to IEC 60068-2-30
Damp heat, constant, to IEC 60068-2-3 |
| Connection to SmartWire-DT |
Yes
|
| Frame size |
FS2
|
| Altitude |
Above 1000 m with 1 % derating per 100 m
Max. 2000 m |
| Ambient operating temperature - max |
40 °C
|
| Ambient operating temperature - min |
-5 °C
|
| Ambient storage temperature - max |
60 °C
|
| Ambient storage temperature - min |
-25 °C
|
| Assigned motor power at 200/208 V, 60 Hz, 3-phase |
10 HP
|
| Assigned motor power at 220/230 V, 60 Hz, 3-phase |
10 HP
|
| Assigned motor power at 460/480 V, 60 Hz, 3-phase |
25 HP
|
| Equipment heat dissipation, current-dependent Pvid |
1.5 W
|
| Heat dissipation capacity Pdiss |
0 W
|
| Heat dissipation per pole, current-dependent Pvid |
0 W
|
| Mains voltage - max |
480 V
|
| Mains voltage - min |
200 V
|
| Output voltage |
250 V AC (relay outputs)
|
| Number of outputs |
2 Relay Outputs (TOR, Ready)
|
| Screwdriver size |
PZ2, 1 x 6 mm, Terminal screw, Standard screwdriver
0.6 x 5.5 mm/1 x 6 mm, Terminal screws, Control circuit cables |
| Voltage type |
DC
|
| Rated operational voltage (Ue) - min |
230 V
|
| Rated power three-phase motor, inline, at 230 V |
7.5 kW
|
| Rated power three-phase motor, inline, at 400 V |
15 kW
|
| Rated power three-phase motor, inside delta, at 230 V |
0 kW
|
| Rated power three-phase motor, inside delta, at 400 V |
0 kW
|
| Static heat dissipation, non-current-dependent Pvs |
1.5 W
|
| Voltage rating - max |
480 V
|
| Application |
|
| Product category |
SmartWire-DT slave
|
| Protection |
Finger and back-of-hand proof, Protection against direct contact
|
| Mounting position |
Vertical
|
| Drop-out voltage |
0 - 3 V, DC operated
|
| Overvoltage category |
II
|
| Degree of protection |
NEMA 1
IP20 |
| Current consumption |
50 mA, Control circuit, Regulator supply
1.6 mA, Control circuit, Digital inputs, External 24 V |
| Current limitation |
(0 - 8) x Ie, Soft start function
|
| Functions |
Current limitation, with PKE
Min. ramp time 1 s - fast switching (semiconductor contactor) Suppression of closing transients Soft start function Potential isolation between power and control sections Single direction Suppression of DC components for motors |
| Delay time |
0 - 30 s, Soft start function, Ramp times
|
| Overload cycle |
AC-53a: 3 - 5: 75 - 10
|
| Drop-out time |
350 ms, Control circuit, Digital Inputs, DC operated
|
| Pick-up voltage |
17.3 - 27 V DC
|
| Radio interference class |
Class B (EN 55011)
|
| Fault memory |
8 Faults
|
| Pick-up time |
250 ms at DC
|
| Interfaces |
SmartWire-DT (built-in)
|
| Rated control voltage (Uc) |
24 V DC
24 V DC (-15 %/+10 %) or via SmartWire-DT |
| Supply frequency |
50/60 Hz, fLN, Main circuit
|
| Terminal capacity (stranded) |
1 x 16 mm², Main cables
|
| Rated control supply voltage (Us) at AC, 50 Hz - max |
0 V
|
| Rated control supply voltage (Us) at AC, 50 Hz - min |
0 V
|
| Rated control supply voltage (Us) at AC, 60 Hz - max |
0 V
|
| Rated control supply voltage (Us) at AC, 60 Hz - min |
0 V
|
| Rated control supply voltage (Us) at DC - max |
24 V
|
| Rated control supply voltage (Us) at DC - min |
24 V
|
| Rated operational current (Ie) at AC-11 |
1 A
|
| Rated operational current (Ie) at AC-53 |
32 A
|
| Rated operational current for specified heat dissipation (In) |
32 A
|
| Rated operational power at 220/230 V, 50 Hz |
7.5 kW
|
| Rated operational power at 400 V, 50 Hz |
15 kW
|
| Rated operational voltage (Ue) - max |
480 V
|
| Vibration resistance |
2M2 to EN 60721-3-2
|
| Ramp/run-up time |
1 - 30 s
|
| Shock resistance |
8 g, 11 ms, Mechanical
|
| Suitable for |
Branch circuits, (UL/CSA)
|
| Tightening torque |
3.2 Nm
1.2 Nm, Screw terminals, Control circuit cables |
| Short-circuit protection rating |
3 x 170M1366, Type „2“ coordination (additional with the fuses for coordination type „1“), Main conducting paths
PKM0-32 (+ CL-PKZ0), Type “1” coordination, Main conducting paths |
| Start voltage |
Min. 30 %, Soft start function, Start voltage = turn-off voltage
Max. 100 %, Soft start function, Start voltage = turn-off voltage |
| Terminal capacity (flexible with ferrule) |
2 x (0.5 - 0.75) mm², Control circuit cables
1 x (0.5 - 1.5) mm², Control circuit cables 1 x (0.75 - 16) mm², Main cables 2 x (0.75 - 10) mm², Main cables |
| Terminal capacity (solid) |
2 x (0.5 - 1.0) mm², Control circuit cables
1 x (0.75 - 16) mm², Main cables 2 x (0.75 - 10) mm², Main cables 1 x (0.5 - 2.5) mm², Control circuit cables |
| Terminal capacity (solid/stranded AWG) |
18 - 6, Main cables
18 - 14, Control circuit cables |